Loading...
HomeMy WebLinkAboutWQ0004332_Insp Rpt 5-1-17_20190624Compliance Inspection Report Permit: WQ0004332 Effective: 12/01/14 Expiration: 11/30/19 Owner: Town of Edenton SOC: Effective: Expiration: Facility: Edenton Town-WWTF/Sids County: Chowan PO Box 300 Region: Washington Edenton NC 27932 Contact Person: Anne -Marie Marie Knighton Title: Phone: 252-482-7352 Directions to Facility: System Classifications: SI, Primary ORC: David Wayne Myers Secondary ORC(s): On -Site Representative(s): Related Permits: Inspection Date: 05/01/2017 Primary Inspector: Sarah A Toppen Secondary Inspector(s): Entry Time: 10:30AM Scott A Vinson Robert B Tankard Reason for Inspection: Routine Permit Inspection Type: Wastewater Irrigation Facility Status: ❑ Compliant Not Compliant Question Areas: Certification: 1001733 Phone: 252-333-8105 Exit Time: 12:30PM Phone: 252-946-6481 Phone :252-946-6481 Ext.208 Phone :252-946-6481 Ext.233 Inspection Type: Compliance Evaluation Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Miscellaneous Questions Treatment Flow Measurement -Water Treatment Treatment Barscreen Use Records Record Keeping Treatment Lagoons End Use -Irrigation Treatment Disinfection Treatment Flow Measurement Wells (See attachment summary) Page 1 of 6 Permit: WQ0004332 Owner - Facility: Town of Edenton Inspection Date: 05/01/2017 Inspection Type : Compliance Evaluation Reason for Visit: Routine Inspection Summary: On Monday, May 1, 2017 a compliance inspection was conducted with Sarah Toppen, Robert Tankard and Scott Vinson from WaRO. David Myers and Brad Arnold were present from the Town of Edenton. The Town of Edenton is currently under an Special Order by Consent (SOC) and the NDAR shows that the application rates are not being adhered to. An SOC was signed on April 24, 2017 because the spray irrigation fields have not been properly maintained and show signs of surface runoff, ponding and vegetative crop issues. Upstream and downstream monitoring points are required per the SOC if there is any discharge event. Attached to the inspection report is a map with the sampling points and the form (MR -3) that shall be completed in the event of any discharge. Treatment: A de -gritting unit and an air scrubber unit (not currently in use) is listed in the current permit but ORC stated that both units have been removed. Record Keeping: A July 2016 spot check was conducted on NDMRs. The ORC stated that the pH is written on a dry erase board and once entered into the NDMR it's erased. The recommendation made is to write pH in the operations log. A GW -59A is a questionaire for the wells. Everytime you complete GW -59, a GW -59A should be attached. A GW -59A form can be found on the NC DEQ Website. End Use -Irrigation: We spoke to the ORC about spray irrigation times. Fields should be rotated every two hours. MW -4 and MW -6 were observed tagged but the etching was no longer readable. Have tags redone so that the information can be read. Both the wells were locked and appeared to be in good condition. The ORC stated that Bionomics came out to check sludge levels at the lagoon November 2016. The Town of Edenton is currently in non-compliance and under a SOC so that certain parameters can be rectified in the current permit. The SOC schedule should be followed along with the current permit. If there are any questions let Washington Regional Office know. Page 2 of 6 Permit: WQ0004332 Owner - Facility: Town of Edenton Inspection Date: 05/01/2017 Inspection Type : Compliance Evaluation Reason for Visit: Routine Type Yes No NA NE Reuse (Quality) ❑ Infiltration System ❑ Single Family Spray, LR ❑ Activated Sludge Spray, LR ❑ Activated Sludge Spray, HR ❑ Recycle/Reuse ❑ Activated Sludge Drip, LR ❑ Single Family Drip ❑ Lagoon Spray, LR Treatment Yes No NA NE Are Treatment facilities consistent with those outlined in the current permit? ❑ 0 ❑ ❑ Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑ Comment: A de -gritting unit and an air scrubber unit (not currently in use) is listed in the current permit but ORC stated that both units have been removed. Treatment Flow Measurement -Influent Yes No NA NE Is flowmeter calibrated annually? ❑ ❑ ❑ Is flowmeter operating properly? ❑ ❑ ❑ Does flowmeter monitor continuously? ❑ ❑ ❑ Does flowmeter record flow? ❑ ❑ ❑ Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑ Comment: An ABB Instruments Magnetic Influent meter was calibrated by Chadwick Instrument Services Co., Inc on 10/21/2016. Treatment Flow Measurement -Water Use Records Is water use metered? Are the daily average values properly calculated? Comment: N/A Yes No NA NE Treatment Flow Measurement -Effluent Yes No NA NE Is flowmeter calibrated annually? ❑ ❑ ❑ Is flowmeter operating properly? ❑ ❑ ❑ Does flowmeter monitor continuously? ❑ ❑ ❑ Does flowmeter record flow? ❑ ❑ ❑ Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑ Comment: A Sea Metric Magnetic Probe EX201 Effluent flow meter was calibrated 10/21/2016 by Chadwick Instrument Service Co., Inc. Page 3 of 6 Permit: WQ0004332 Owner - Facility: Town of Edenton Inspection Date: 05/01/2017 Inspection Type : Compliance Evaluation Reason for Visit: Routine Treatment Barscreen Yes No NA NE Is it free of excessive debris? ❑ ❑ ❑ Is disposal of screenings in compliance? ❑ ❑ ❑ Are the bars spaced properly? ❑ ❑ ❑ Is the unit in good condition? 0 ❑ ❑ ❑ Comment: Treatment Disinfection Yes No NA NE Is the system working? ❑ ❑ ❑ Do the fecal coliform results indicate proper disinfection? ❑ ❑ ❑ Is there adequate detention time (-30 minutes)? ❑ ❑ ❑ Is the system properly maintained? ❑ ❑ ❑ If gas, does the cylinder storage appear safe? ❑ ❑ ❑ Is the fan in the chlorine feed room and storage area operable? ❑ ❑ ❑ ❑ Is the chlorinator accessible? ❑ ❑ ❑ If tablets, are tablets present? ❑ ❑ ❑ Are the tablets the proper size and type? ❑ ❑ ❑ Is contact chamber free of sludge, solids, and growth? ❑ ❑ ❑ ❑ If UV, are extra UV bulbs available? ❑ ❑ ❑ If UV, is the UV intensity adequate? ❑ ❑ ❑ # Is it a dual feed system? ❑ ❑ ❑ Does the Stationary Source have more than 2500 lbs of Chlorine (CAS No. 7782-50-5)? ❑ ❑ ❑ If yes, then is there a Risk Management Plan on site? ❑ ❑ ❑ If yes, then what is the EPA twelve digit ID Number? (1000- ) If yes, then when was the RMP last updated? Comment: Chlorine disinfection system is a single feed system (two cylinders are hooked up and when one is emptied the other comes online automatically). Open air roof top set up. The area was observed neat and organized. Approximately 1500 lbs of chlorine onsite. Record Keeping Yes No NA NE Is a copy of current permit available? 1:11:11:1 Are monitoring reports present: NDMR? ❑ ❑ ❑ NDAR? ❑ ❑ ❑ Are flow rates less than of permitted flow? ❑ ❑ ❑ Are flow rates less than of permitted flow? ❑ ❑ ❑ Are application rates adhered to? ❑ 0 ❑ ❑ Is GW monitoring being conducted, if required (GW -59s submitted)? ❑ ❑ ❑ Are all samples analyzed for all required parameters? ❑ ❑ ❑ Page 4 of 6 Permit: WQ0004332 Owner - Facility: Town of Edenton Inspection Date: 05/01/2017 Inspection Type : Compliance Evaluation Reason for Visit: Routine Are there any 2L GW quality violations? ❑ ❑ ❑ Is GW -59A certification form completed for facility? ❑ ❑ ❑ Is effluent sampled for same parameters as GW? ❑ ❑ ❑ ❑ Do effluent concentrations exceed GW standards? ❑ ❑ ❑ Are annual soil reports available? ❑ ❑ ❑ ❑ # Are PAN records required? ❑ ❑ ❑ # Did last soil report indicate a need for lime? ❑ ❑ ❑ If so, has it been applied? ❑ ❑ ❑ Are operational logs present? ❑ ❑ ❑ ❑ Are lab sheets available for review? ❑ ❑ ❑ Do lab sheets support data reported on NDMR? ❑ ❑ ❑ ❑ Do lab sheets support data reported on GW -59s? ❑ ❑ ❑ Are Operational and Maintenance records present? ❑ ❑ ❑ Were Operational and Maintenance records complete? ❑ ❑ ❑ Has permittee been free of public complaints in last 12 months? ❑ ❑ ❑ Is a copy of the SOC readily available? ❑ ❑ ❑ No treatment units bypassed since last inspection? ❑ 0 ❑ ❑ Comment: A July 2016 spot check was conducted on NDMRs. The ORC stated that the pH is written on a dry erase board and once entered into the NDMR it's erased. The recommendation made is to write pH in operations log. GW -59 was spot checked for the month of November 2016 and a soils report was dated September 22, 2016. A GW -59A is a questionaire for the wells. Everytime you complete GW -59s a GW -59A should be -44--1-- i End Use -Irrigation Yes No NA NE Are buffers adequate? ❑ ❑ ❑ ❑ Is the cover crop type specified in permit? ❑ ❑ ❑ Is the crop cover acceptable? ❑ ❑ ❑ Is the site condition adequate? ❑ ❑ ❑ Is the site free of runoff/ ponding? ❑ ❑ ❑ Is the acreage specified in the permit being utilized? ❑ ❑ ❑ Is the application equipment present? ❑ ❑ ❑ Is the application equipment operational? ❑ ❑ ❑ Is the disposal field free of limiting slopes? ❑ ❑ ❑ Is access restricted and/or signs posted during active site use? ❑ ❑ ❑ Are any supply wells within the CB? ❑ ❑ ❑ Page 5 of 6 Permit: WQ0004332 Owner - Facility: Town of Edenton Inspection Date: 05/01/2017 Inspection Type : Compliance Evaluation Reason for Visit: Routine Are any supply wells within 250' of the CB? ❑ ❑ ❑ How close is the closest water supply well? ❑ ❑ ❑ Is municipal water available in the area? 0 ❑ ❑ ❑ # Info only: Does the permit call for monitoring wells? 0 ❑ ❑ ❑ Are GW monitoring wells located properly w/ respect to RB and CB? 0 ❑ ❑ ❑ Are GW monitoring wells properly constructed, including screened interval? 0 ❑ ❑ ❑ Are monitoring wells damaged? ❑ 0 ❑ ❑ Comment: The facility is currently under an SOC because the spray irrigation fields have not been properly maintained and show signs of surface runoff, ponding and vegetative crop issues. MW -4 and MW -6 were observed tagged but the etching was no longer readable. Have tags redone so that the information can be read. Also, both were locked and appeared to be in good condition. Page 6 of 6