HomeMy WebLinkAboutNC0089770_NOV-2019-LM-0044_20190606t
Certified Mail # 7019 0160 0000 3479 8148
Return Receipt Requested
June 6, 2019
Lisa Kirby
City of Greenville
1500 Beatty St
Greenville, NC 27834
SUBJECT: NOTICE OF VIOLATION
Tracking Number: NOV-2019-LM-0044
Permit No. NCO089770
Town Creek Culvert Storm Drain Improvement
Pitt County
Dear Ms. Kirby:
A review of the January 2019 Discharge Monitoring Report (DMR) for the subject facility revealed the violation(s)
indicated below:
Limit Exceedance Violation(s):
Sample Limit Reported
Location Parameter Date Value Value Type of Violation
002 Effluent Zinc, Total (as Zn) (01092) 1/8/2019 49.3 52.7 Daily Maximum Exceeded
002 Effluent Copper, Total (as Cu) (01042) 1/16/2019 10.47 10.5 Daily Maximum Exceeded
002 Effluent
Zinc, Total (as Zn) (01092)
1/16/2019
49.3
168
Daily Maximum Exceeded
002 Effluent
Mercury, Total (as Hg) -
1/24/2019
12
41.7
Daily Maximum Exceeded
Concentration (COMER)
002 Effluent
Zinc, Total (as Zn) (01092)
1/24/2019
49.3
67.5
Daily Maximum Exceeded
002 Effluent
Oxygen, Dissolved (DO)
1/31/2019
5
0
Daily Minimum Not Reached
(00300)
002 Effluent
Zinc, Total (as Zn) (01092)
1/31/2019
36.5
67.9
Monthly Average Exceeded
MuethCssouna Department of Envartreertav Qu?ty I ?5les(cnmf WKar RRsou¢oas
Was?en�mSr Rt�Pouak�#�x'"�3 was4cirgton 3gmare A€a�v i. W.uR ar�A^�e N*r6i£aroavra 276$$
Monitoring Violation(s):
Sample Monitoring
Location Parameter Date Frequency Type of Violation
002
Effluent
Oxygen, Dissolved (DO) (00300)
1/5/2019
Weekly
Frequency Violation
002
Effluent
pH (00400)
1/5/2019
Weekly
Frequency Violation
002
Effluent
Turbidity (00070)
1/5/2019
Weekly
Frequency Violation
Remedial actions, if not already implemented, should be taken to correct any noted problems. The Division of
Water Resources may pursue enforcement actions for this and any additional violations. If the violations are of a
continuing nature, not related to operation and/or maintenance problems, and you anticipate remedial
construction activities, then you may wish to consider applying for a Special Order by Consent (SOC).
If you have any questions concerning this matter or to apply for an SOC, please contact Robbie Bullock of the
Washington Regional Office at 252-946-6481.
Cc: Laserfiche
Sincerely,
Boaz T"."
Robert Tankard, Assistant Regional Supervisor
Water Quality Regional Operations Section
Washington Regional Office
Division of Water Resources, NCDEQ
+� Narth Gnmbna ffepartmeat cf Env:raflm2nia+¢ve3itp ( 4s+r�vrtof Ydaier kikabl.'Y623
li'ash«n tiara Savona i}?fiue 1 B43 %Vashnngwn Square Mail I WashmgWrr. Kurth fam"a& 27888
292 946-6484