HomeMy WebLinkAboutWQ0040658_Add Info Letter_20190426ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
Director
JOSEPH C. WILSON — CHIEF ENGINEER
NORTH CAROLINA
Environmental Quality
April 26, 2019
CHARLOTTE WATER
9101 SOUTHERN PINES BOULEVARD, SUITE 250
CHARLOTTE, NORTH CAROLINA 28273
Subject: Application No. WQ0040658
Additional Information Request
Mallard Creek WRF Reuse Line
Extension to UNCC
Reclaimed Water Distribution Lines
Mecklenburg County
Dear Mr. Wilson:
Division of Water Resources' Central and Regional staff has reviewed the application package
received February 20, 2019. However, additional information is required before the review may be
completed. Please address the items on the attached pages no later than the close of business on May 27,
2019.
Please be aware that you are responsible for meeting all requirements set forth in North Carolina
rules and regulations. Any oversights that occurred in the review of the subject application package are
still the Applicant's responsibility. hi addition, any omissions made in responding to the outstanding items,
or failure to provide the additional information on or before the above requested date may result in your
application being returned as incomplete.
Please reference the subject application number when providing the requested information. All
revised and/or additional documentation shall be signed, sealed and dated (where needed), with two paper
copies and one electronic copy.
If you have any questions regarding this request, please do not hesitate to contact me at (919) 707-
3660 or tessa.monday@ncdenr.gov. Thank you for your cooperation.
Sincerely,
/tom f, jw '
Tessa Monday, Environmental Engineer
Division of Water Resources
cc: James Struve, PE — Hazen and Sawyer (Electronic Copy)
Permit Application File WQ0040658
D EQ �� North Carolina Department of Environmental Quality Division of Water Resources
512 North Salisbury Street 1 1617 Mail Service Center I Raleigh, North Carolina 27699-1617
NORTH CAROLINA
DepadmamofEnmron—WQuality
/� 919.707.9000
Mr. Joseph C. Wilson
April 26, 2019
Page 2 of 2
1. The application shall be signed in accordance with 15A NCAC 02T .0106(b). The application must be
signed by an elected official in the highest level of elected office or other authorized employee. An alternate
person may be designated as the signing official if a delegation letter is provided from a person who meets
the criteria in 15A NCAC 02T .0106(b).
2. Provide the highest and discharge (or connection to another distribution line) elevations in Table III.1.
3. Ensure that if the elevation difference exceeds 10 feet, air release valves are provided as required by 15A
NCAC 02T .0305(h)(5).
4. Provide copies of all relevant easements, road encroachments, floodplain compliance authorization, and
ACOE permit approval. For easements, any referenced plats or maps must be provided.
5. Provide documentation of the presence or absence of threatened or endangered species at the project site
utilizing information provided by the Department's Natural Heritage Program.
6. Per 15A NCAC 02U .0403, the separation requirements have not been met. At the crossings, the piping
and integrity testing procedures must meet water main standards in accordance with 15A NCAC 18C.
Address.
7. Per 15A NCAC 02U .0201, the specifications must be signed and sealed by a North Carolina Professional
Engineer.