HomeMy WebLinkAboutWQ0040285_Application (FTSE)_20190221Robinson, Jason
From: Paul Weeks <paul.weeks@sanfordnc.net>
Sent: Friday, February 22, 2019 12:13 PM
To: 'Scott Haberstroh'; Robinson, Jason; 'Lochan Basnet'
Cc: Bolich, Rick; Cashion, Ted
Subject: [External] RE: City of Sanford - Little Buffalo Lift Station improvements Project -
Wastewater Collection System Extension Permit (Permit No. WQ0040285)
Bgterni email. Do not click links or open attachments unless -you verify. Send all suspicious email as an attachment to-7
ireaort.sgain 0nc,cav
Jason,
I can confirm the upgrade and the intention of the City to operate and maintain the expanded station.
Best regards,
Paul M. Weeks Jr, P.E.
City of Sanford
City Engineer
225 E. Weatherspoon St
PO Box 3729
Sanford, NC 27330
(o) 919-777-1119
(o) 919.777-1122
From: Scott Haberstroh[mailto:Scott.Haberstroh@freese.com]
Sent: Friday, February 22, 2019 10:55 AM
To: Robinson, Jason <jason.t.robinson@ncdenr.gov>; Lochan Basnet <Lochan.Basnet@freese.com>
Cc: Bolich, Rick <rick.bolich@ncdenr.gov>; Cashion, Ted <ted.cashion@ncdenr.gov>; Paul Weeks
< Pau l.weeks@sanford nc.net>
Subject: RE: City of Sanford - Little Buffalo Lift Station Improvements Project - Wastewater Collection System Extension
Permit (Permit No. WQ0040285)
Jason,
Thank you for your help. I confirm that the Little Buffalo Lift Station will be a triplex pump station with a firm
capacity of 4420 gpm at 128 feet of head.
Thanks,
Scott
Scott Haberstroh, PE
Senior Project Manager
Freese and Nichols, Inc.
919-582-5867 office
617-997-7425 mobile
From: Robinson, Jason <iason.t.robinson@ncdenr.eov>
Sent: Friday, February 22, 2019 10:43 AM
To: Lochan Basnet <Lochan.Basnet@freese.com>
Cc: Bolich, Rick <rick; bolich@ncdenr.gov>; Cashion, Ted <ted.cashion@ncdenr.eov>; Paul Weeks
<pau1.weeks@sanfordnc.net>; Scott Haberstroh <Scott.Haberstroh Mreese.com>
Subject: RE: City of Sanford - Little Buffalo Lift Station Improvements Project - Wastewater Collection System Extension
Permit (Permit No. WQ0040285)
Hi Lochan,
We'll need an email from both the permittee (City of Sanford, Paul Weeks) AND the P.E. that signed and sealed the
application (Scott Haberstroh) confirming the requested changes.
The email will need to confirm that the permit should confirm that it will be a triplex pump station with an operational
point (largest pump out of service) of 4, 420 GPM at 128 feet of head.
Once we receive an email from both the permittee and engineer, we'll reissue the permit. We'll keep the emails for our
files.
Thanks,
Jason
------------
Jason T. Robinson, P.E.
Raleigh Regional Office
Water Quality Regional Operations
Division of Water Resources, DEQ
919-791-4200
`"Subscribe to Collection System & Sewer Permitting Updates"
-moil corr25pondence to and from this address may be subject to the North Carolina Public Records taw and may be disclosed to
third parties.
From: Robinson, Jason
Sent: Thursday, February 21, 2019 2:25 PM
ToAochan Basnet' <Lochan.Basnet@freese.com>
Cc: Bolich, Rick (rick.bolich(Mncdenr.eov) <rick.bolich@ncdenr.eov>; Cashion, Ted <ted.cashion@ncdenr.eov>; Paul
Weeks <paul.weeks@sanfordnc.net>
Subject: RE: City of Sanford - Little Buffalo Lift Station Improvements Project - Wastewater Collection System Extension
Permit (Permit No. WQ0040285)
Hi Lochan,
Section V111.3 and V111.4 of the application should be calculated with the largest pump out of service (since this is triplex,
both items should be calculated with two pump running). When we issue the permit, we use what's in Item VI11.4 in the
application.
I'll need to run this by our Permit Coordinator and Supervisor to see how they want to handle this.
We'll also need the permittee (Sanford) to approve this revision.
Thanks,
Jason
------------
Jason T. Robinson, P.E.
Raleigh Regional Office
Water Quality Regional Operations
Division of Water Resources, DEQ
919-791-4200
"*Subscribe to Collection System & Sewer Permitting Updates`*
E-mail correspondence to and from this address may be subject to the North Carolina Public Records Caw and may be disclosed to
third parties.
From: Lochan Basnet <Lochan.Basnet@freese.com>
Sent: Thursday, February 21, 2019 10:39 AM
To: Robinson, Jason <jason.t.robinson@ncdenr.eov>
Subject: [External] City of Sanford - Little Buffalo Lift Station Improvements Project - Wastewater Collection System
Extension Permit (Permit No. WQ0040285)
• Wemal email. t7.b not ejlck'links ar op- n attachments unless ynu-ve"Ify. Send all susplcious email as, an attachment to
Good morning Jason,
On behalf of the City of Sanford, we (Freese and Nichols, Inc.) had sent a Fast Track Sewer System Extension Application
package which is attached here in this email. In response, we received the Wastewater Collection System Extension
Permit (Permit No. WQ0040285). The permit (pg. 3) mentions "the improvements and operation of the existing pump
station to a 2,900 gallon per minute pump station with duplex pumps,...". As indicated in the application, through the
improvements, the City was looking to increase the permitted firm capacity to 6.36 MGD i.e. 4420 gallon per
minute. Further, the pump system is not a duplex pump system. As mentioned in the cover letter of the application
package, it is a 3-pump system. The operating point, indicated in the application, of 2,900 gpm at 80 feet of head is for
one (1) pump running. With two (2) pumps running, the operating point is 4,420 gallon per minute at 128 feet of head,
and this is what the City is looking to be permitted for. Could you please make this change on the permit? If there is any
additional documents that you would require from us or from the City, please let us know.
We greatly appreciate you help!
Regards,
Lochan Basnet, E.I.
Engineer 11
Freese and Nichols, Inc.
919-371-6452
This electronic mail message is intended exclusively for the individual or entity to which it is addressed. This message,
together with any attachment, may contain the sender's organization's confidential and privileged information. The
recipient is hereby notified to treat the information as confidential and privileged and to not disclose or use the
information except as authorized by sender's organization. Any unauthorized review, printing, retention, copying,
disclosure, distribution, retransmission, dissemination or other use of, or taking of any action in reliance upon, this
information by persons or entities other than the intended recipient is prohibited. If you received this message in error,
please immediately contact the sender by reply email and delete all copies of the material from any computer. Thank
you for your cooperation.