Subject: Compliance Evaluation Inspection
NPDES Permit No. NC0049662
Hawthorne Subdivision kVWTP
Wake County
Dear ivIr. Becker:
1
On December 19, 2018, Cory Larsen with Wake County Department of Environmental
Services, on behalf of the Division of Water Resources, performed a compliance evaluation
inspection of the subject wastewater treatment system to evaluate compliance with the
subject permit to discharge wastewater. Roger Tupps and Rob Boone (ORC) provided their
assistance for the inspection which was appreciated. Please refer to the attached inspection
report for full results.
On the day of the inspection, the plant was operating normally and producing clear effluent
through trains 3-4. The plant has been upgraded to better handle surge flows and denitrify
to meet more stringent nutrient effluent limitations, and no compliance issues were found
during the inspection.
If you have any questions regarding this inspection or ever require assistance maintaining
compliance with your permit, please contact Cory Larsen at 919-480-9998 /
cory.larsenGZwakei-,ov.com or me at (919) 791-4200.
Sincerely,
Rick Bolich, L.G., Assistant Regional Supervisor
Division of Water Resources, Water Quality
Regional Operations Section
Enclosure: DWR Inspection Report
cc: Wake County Department of Environmental Services File
RRO File
Do,:
Mz
^ `it.r'h �ar,tlir:a `:)• p:Ir! >;a'tt! rIf kir'.ir :n r eo ,d f; .�6!, r? ui':V stCr' e: utcn
EM�
Central Files
NPDES Permitting Unit
Roger Tupps - Aqua NC, Inc. (202 IvlacKenan Ct. Cary, NC 27511)
L'iled States Environtnentai Prwechen Agency Form Approved
EPA Wasningtcn 0 : 20a60 OMB No 2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A. National Data System Coding (i e , PCS)
Transaction Code
NPDES
yr,mo,day
nspect.c- Type Inspector Fac Type
.1 IN 1 2 1s 1
3 NCO049662 '11 12
18112r19
LJ 17 i B l 9 t 191 c I 20I uI
LJ
21Ill
I
6
Inspection Work Days
Factl ly Self -Monitoring Evaluation Rating
B 1
OA —Reserved
67
70 I_j
71 u
72 L f 73 Lr 174 751 I I I I 1 I 180
Section B Facility Data
Name and Location of Facility Inspected %For Industrial Users d'scharging to POT.Aj also ndude ntry Time/Date Permit Effective Date
P07VI name and NPDES Permit Number.
11 COAM 1a-1214 la:03.01
Hawthorne Subdivision VWVrP
N Hawthcme Way Exit TimelDate Permit Exp ration Date
Raleigh NC2760' t230PM 1a'12119 23:01,31
Names) of Onsite Representativeysi;Titles(s:.Phone and Fax Number..s, t , Faality Data
P1
Robert P. BonneVORC!!
Name, Address of Responsible Of vali7itle.Phone and Fax Number
Timothy Glenn Thomas P919.467-8712'9194661583 Contacted
No
Section C. Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement a Operations & Maintenance ■ RecordslReports
Self-Moniloring Program M Sludge Handling Disposal M Facility Site Review M Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Names) and Signature(s) of Inspecter(s) AgencylOfficelPhcne and Fax Numbers Date
Cor/ Larsen RRO MP919-856-7443.
grrw;<I-L --1--- 01/31/2019jjji
Signature of Management O A Reviewer AgencylOfficelPhene and Fax Numbers ate
EPA Form 3560-1 (Rev 4-94) Previous editions are obsolete,
NPOES yr-mWday In c-tion Typm
31 NC0049662 11 12 18/52119 17 18 ICI
LJ
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checkiists as necessary}
WCES inspected the WWTP on 12/18/18 with the assistance of Roger Tupps and Ron Boone' (ORC).
Trains 3 and 4 were in operation and producing good quality effluent. Upgrades are mostly complete
and equalization is available to prevent surge through the plant which had passed solids in the past.
No compliance issues were observed for followup. WCESrCL.
Pam#
Permit., NCO049662 Owner - Facility. Hatvthome Su@divir1on VNNTP
Inspection Dale: 1211912018 Inspection Type: Ccmpliance Evaluatian
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? M ❑ ❑ ❑
Does the facility analyze process control parameters. for ex. NILSS NICRT Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Plant has been refurbished in the last year and all 4 trains are available.
Two of four utilized no 3 and no 4 - largest)
Permit
Yes No NA NE
(If the present permit expires in 6 months or less) Has the permittee submitted anew
0
❑
❑
❑
application?
Is the facility as described in the permit?
M
❑
❑
❑
# Are there any special conditions for the permit?
0
❑
❑
❑
Is access to the plant site restricted to the general public?
❑
❑
❑
Is the inspector granted access to all areas for inspection?
❑
❑
❑
Comment: Permit was renewed in 2018
W/VTP secured with fencing.
Record Keening
Yes No NA NE
Are records kept and maintained as required by the permit?
❑
❑
❑
Is all required information readily available, complete and current?
❑
❑
❑
Are all records ma nta'ned for 3 years (lab. reg. required 5 years;?
❑
❑
❑
Are analytical results consistent w th data reported on DNIRs?
,
❑
❑
❑
Is the chain -of -custody complete?
■
❑
❑
❑
Dates times and location of sampl.ng
❑
Name of indiv'dual performing the sampling
❑
Results of analysis and calibration
❑
Dates of analysis
❑
Name of person performing analyses
❑
Transported COCs
❑
Are DN1Rs complete: do they include all permit parameters'?
0
❑
❑
❑
Has the facility submitted its annual compliance report to users and DVVQ?
0
❑
❑
❑
(If the facility is = or a 5 N1GD permitted flow; Do they operate 2417 with a certTed operas--r
❑
❑
a
❑
on each shift?
Is the ORC vis.tation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility class fcat on?
❑
❑
❑
Pagr-# 3
owner - Facility: Hmvthorne S6bd141SIOn wWr?
Permit: NCO049662 Inspection Type Ccmpliance £valuawn
Inspection Date: 1211912018
Yes No NA NE
Record Keepincl � ❑ ❑ ❑
Is the backup operator certified at one grade tens or greater than the facility dassifcation ■ ❑ ❑ ❑
Is a copy of the current NPDES permit available on site'? ❑ ❑ ■ ❑
Facility has copy of previous year's Annual Report on file for review?
Comment: Records were reviewed and looked complete._
ORC I)q, bench sheet ermitlab certification all resent.
Re orted concentraions on QMRs matched lab sheets.
Yes No NA NE
Effluent Ripe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debr s? Q
if effluent (diffuser pipes are required) are they operating properly?
Comment: Effluent pipe dischar es to ri ra aeration ad.
No foamin or evidence of solids in creek.
Yes No NA NE
Flow Measurement • Effluent
❑
❑
❑
# is flow meter used for reporting?
❑
❑
❑
is flow meter calibrated annually?
a
❑
❑
❑
Is the now meter operational?
❑
❑
❑
(if units are separated) Does the chart recorder matnh the flow mete?
1118
flow meter was calibrated S12b
Horizon
Comment: 1SCO 4210 ultrasonic measurement
En Berincl.
Prior da flow was 133,11 a GPO_
Yes No NA NE
Aerobic Digester
13
❑
❑
❑
Is the capacity adequate?
a
❑
❑
❑
Is the mixing adequate?
M
❑
❑
❑
Is the site free of excessive foaming in the tank 7
M
❑
❑
❑
# Is the odor acceptable?
IM
❑
❑
❑
# Is tankage available for properly waste sludge?
train has di ester tank. Both in use were aerated and acce table odor.
Comment: Each
Yes No NA NE
Chemical Feed
13 ❑ ❑ ❑
is containment adequate?
13 ❑ ❑ ❑
Is storage adequate?
❑ ❑ ❑
Are backup pumps available?
Page# 4
Permit: NC0049662 Owner - Facility: Hawthorne Subdivision WWTP
Inspection Date: 12H9l2018 Inspection Type: Compliance Evaluation
Chemical Feed Yes No NA NE
Is the site free of excessive leaking? ■ 11 ❑
Comment: Sodium aluminate fed to EQ (pH and TP control
Bar Screens
Type of bar screen
Yes No NA NE
a.Manual
b.Mechanical
Are the bars adequately screening debris?
S
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
El
El
El
Comment: Flow enters a mechanical static screen
screw lift to remove solids screened to a Waste
Industries dum ster.
Equalization Basins
Yes No NA NE
Is the basin aerated?
C-1
❑
11
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
❑
Are all pumps present?
❑
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
❑
# Is basin sizelvolume adequate?
Comment: EQ basin has been refurbished with new blowers and control. Two lift stations provide
influent.
Pump 1 and 2. hi h level alarm. telemet tested and worked -normally.
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
ff
Is the site free of excessive buildup of solids in center well of circular clarifier?
0
El
0
El
Are weirs level?
i
E3
❑
El
Is the site free of weir blockage?
0
❑
❑
Is the site free of evidence of short-circuiting?
,
El
❑
❑
Is scum removal adequate?
V
El
❑
❑
Is the site free of excessive floating sludge?
0
Page# 5
owner - Facility•
Hawthorne 5ubdivis on 'JIMM
Permit: NCO049662
Inspection Type
Compliance cvoluacan
Inspection DaW 121191201 B
Yes No NA NE
SecondarY Clarifier
❑ ❑ 0 ❑
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
M El 0 El
Is the overflow clear of excessive solids/pin floc
, ❑ ❑ ❑
(Approximately 1/4 of the sidwall depth)
Is the sludge blanket Vevey acceptable? (App Y
Comment: Clarifier 3 - aine needles affect skimmer efficient _ Some o u slud e.
column but not out of limits.
Clarifier 4 - algae in weir. some nine solids noted in water
if blanket depth exceeds
Sludge blanket sensors being installed and will noti o erator
set oint e. . 5 ft.
Effluent over weir was clear.
Post aeration was workin well.
Effluent TSS meter no longer utlized.
Yes No NA NE
Aeration Basins
Ext. Air
M--de of operation
Diffused
Type of aeration system
Is the basin free of dead spots?
❑ ❑ ❑
Are surface aerators and mixers operationai7
❑
Are the diffusers operational?
Is the foam the proper color for the treatment proceas?
0 ❑ ❑ ❑
Does the foam cover less than 25% of the basin's s irfa--e
Is the DO level acceptable?
11 El
Is the DO level acceptable?(1.0 to 3.0 m911)
Comment. Aeration basins were med. brown color with little foam.
Anoxic zone at head with rec cle rate to denitrify.
DO no. 3 = 1.32 m /L
DO no. 4 = 1.49 m /L.
Kaeser blower motors have variable fre-luency drives to provide
consistent DO
concentraion in basin.
Lange trains 3-4 redone with roundwater drains to revent floatation.
Yes No NA NE
Disinfection - UV
Are extra UV bulbs available on site?
M ❑ ❑ ❑
Are UV bulbs clean?
i ❑ ❑ ❑
Is UV intensity adequate?
0 ❑ ❑ Cl
Is transmittance at or above designed level?
M ❑ ❑ ❑
Is there a backup system on site?
e ❑ ❑ ❑
Is effluent clear and free of solids?
Page# 6
f
Permit: N00049662 Owner • Facility: Hawthorne Subdivssion toWVTP
Inspection Date: 12: 19:201 B Inspection Type: Compliance Evaluation
Disinfection - UV
Yes No NA NE
Comment: UV consists of 4 banks with 4 lamRs each. All were lit.
Bulbs replaced annually and as needed
Standby Power
Is automatically activated standby power available'?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement w!th a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Comment. Generator was transferred electrical load and cut on properly.
Effluent Sampling
Is composite sampling Flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than rr equal to 6 0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency. sampling type
representative)?
Comment: ISCO oom osite sampler 5800 operated and was cold.
Upstream / Downstream Sampling
Is the facility sampling performed as required by the permit tfrequency sampr�ng type and
sampling location)?
Comment: US/DS saMpli-nq Performed properlV.