Mr. Tommy Spicer
Wilkes County Schools
613 Cherry St. -
North Wilkesboro, NC 28659
Subject: Compliance Evaluation Inspection
North Wilkes High School WWTP
NPDES Permit# NC0076066
Wilkes County
Dear Spicer:
A Compliance Evaluation Inspection was performed by Division of Water Resources, Winston
Salem Regional Office, staff person Justin Henderson, on December 19, 2018. Mr. Tommy
Spicer, Operator in Responsible Charge (ORC), was present for this inspection. This type of
inspection consists of two basic parts: an in-office review of the facility files and self-monitoring
data and an on-site inspection of the facility While this inspection mostly reflects compliance
with Permit No. NC0076066, the following concerns requires your attention and action:
1) Significant holes were observed in two laterals in separate sand filters, resulting in
uneven distribution and ponding of effluent upon system dosing. Several remaining
laterals appeared to be unlevel containing high and low spots, which also was
contributing to uneven distribution and ponding of effluent. Observation of system dosing
should immediately be incorporated in the routine maintenance procedures and
performed at a frequency that will allow prevention of unevenly distribution and/or
ponding of effluent, as well as timely repair of damaged laterals within the sand filters.
2) There were no de-chlorination tablets present in the de-chlorination equipment at the
time of this inspection. Failure to properly maintain the dechlorination equipment and to
adequately replace tablets may result in effluent parameter violations. It is recommended
that weekly monitoring of dechlorination equipment be included in routine maintenance
procedures with monitoring frequencies increasing before and after high rainfall events
or high-water usage events.
3) Rust and corrosion was observed inside the effluent pump station control panel,
indicating that the pump station control panel no longer appeared to be weather-proof.
While, the control panel appeared to be operational at the time of this inspection, it is
strongly recommended that this panel be repaired or replaced with a weather-proof
panel box to ensure the integrity and reliably of the internal components, and to prevent
potential interruption of operations.
fab
`d( T I e"A.<t'hF ae
33nry1»rtmn/of EnNrmnmenti311llaQ
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1450 Hanes Mill Road,Suite 300 Winston-Salem,North Carolina 27103
336 776 980 0
4) Post-calibration records for portable meters were unavailable for review at time of this
inspection. Post-calibration of portable meters, utilized for effluent parameter analyses,
must be performed and documented, and records made available upon request. All
calibration records must be maintained for a period of at least 3 years per Permit
Condition Part II. Section D. (6.).
Please refer to the enclosed compliance inspection report form for additional observations and
comments. If you have any questions regarding this correspondence, please contact Justin
Henderson or me at (336) 776-9800.
Sin erely
41,
S -rri V. Knight, P.E.
Regional Supervisor
Water Quality Regional Operations
Divisions of Water Resources
enc: BIMS Inspection Report
cc: WSRO
Central Files
c NPDES Unit
•
•
D_E
NA7.1tF rfiiCl't.d
Departmmtnl£m1tmITBnta1 mauty
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1450 Hanes Mill Road,Suite 300 t Winston-Salem.North Carolina 27103
336.776.9800
` 1
United States Environmental Protection Agency Form Approved
EPA Washington,D C 20460 OMB No 2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A:National Data System Coding(i.e,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 2 IS I, 3 I NC0076066 111 121 18/12/19 117
181,.E 19I s I 20I
21I1II I I I I I III ' I I I 1 I I I I I I I I I I I I I I I I I I I I I I I I I r6
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA Reserved
67I I 70 LJI I 711 I 72 731
I 174
751 I I I I I I I80
Section B:Facility Data IL—JJ
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number) 09 OOAM 18/12/19 13/12/01
North Wilkes High School WWTP
Exit Time/Date Permit Expiration Date
2986 Traphill Rd
11 45AM 16/12/19 18/09/30
Hays NC 28635
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
///
Thomas J Spicer/ORC/336-651-4010/
Name,Address of Responsible OfficiaVTitle/Phone and Fax Number
Contacted
Bergie Speaks,613 Cherry St North Wilkesboro NC
No
28659//336-667-2021/3366679688
Section C Areas Evaluated During Inspection(Check only those areas evaluated)
El Permit • Flow Measurement • Operations&Maintenance II Records/Reports
• Self-Monitoring Program 111 Sludge Handling Disposal II Facility Site Review Effluent/Receiving Waters
Il Laboratory
Section D Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Justin L Henderson WSRO WQ//336-776-9701/ I /
rre. I jeAA
Signa ure of M`j agement iii A eviewer Agency/Office/Phone and Fax Numbers Date
wy.f 1/17/
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete
Page# 1
,I
NPDES yr/mo/day Inspection Type (Cont.) 1
31 NCoo76o66 111 121 10/12/19 117 18 i i
Section D Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
The following items of concern requiring your attention and action were identified during this inspection
1) Significant holes were observed in two laterals in separate sand filters, resulting in uneven
distribution and ponding of effluent upon system dosing. Several remaining laterals appeared to be
unlevel containing high and low spots,which also was contributing to uneven distribution and ponding
of effluent. Observation of system dosing should immediately be incorporated in the routine
maintenance procedures and performed at a frequency that will allow prevention of unevenly
distribution and/or ponding of effluent, as well as timely repair of damaged laterals within the sand
filters.
2) There were no de-chlorination tablets present in the de-chlorination equipment at the time of this
inspection. Failure to properly maintain the dechlonnation equipment and to adequately replace tablets
may result in effluent parameter violations. It is recommended that weekly monitoring of dechlorination
equipment be included in routine maintenance procedures with monitoring frequencies increasing
before and after high rainfall events or high-water usage events
3) Rust and corrosion was observed inside the effluent pump station control panel, indicating that the
pump station control panel no longer appeared to be weather-proof. While, the control panel appeared
to be operational at the time of this inspection, it is strongly recommended that this panel be repaired or
replaced with a weather-proof panel box to ensure the integrity and reliably of the internal components,
and to prevent potential interruption of operations
4) Post-calibration records for portable meters were unavailable for review at time of this inspection
Post-calibration of portable meters, utilized for effluent parameter analyses, must be performed and
documented, and records made available upon request.All calibration records must be maintained for
a period of at least 3 years per Permit Condition Part II.Section D. (6.).
Page# 2
r a
Permit. NC0076066 Owner-Facility: North Wilkes High School WWTP
Inspection Date: 12/19/2018 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping'? 1. 0 0 ❑
Does the facility analyze process control parameters, for ex MLSS, MCRT, Settleable ❑ 0 • ❑
Solids, pH, DO, Sludge Judge, and other that are applicable'? .
Comment
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ • ❑
application?
Is the facility as described in the permit'? 0 0 0
#Are there any special conditions for the permit'? 00110
Is access to the plant site restricted to the general public'? • ❑ 0 ❑
Is the inspector granted access to all areas for inspection'? • 0 ❑ 0
Comment
De-chlorination Yes No NA NE
Type of system'? Tablet
Is the feed ratio proportional to chlorine amount(1 to 1)? ❑ • ❑ ❑
Is storage appropriate for cylinders'? • 0 0 ❑
#Is de-chlorination substance stored away from chlorine containers'? III 0 ❑ ❑
Are the tablets the proper size and type? • ❑ ❑ 0
Comment The tablet dechlorinator was empty at time of this inspection. Montiorinq frequencies should
be increased before and after high rainfall events and/or high water usage events to ensure
an adequate supply of tablets are maintained
Are tablet de-chlorinators operational'? • 0 ❑ ❑
Number of tubes in use'? 0
Comment: The tubes were empy and in need of refilling at time of this inspection.
Septic Tank Yes No NA NE
(If pumps are used) Is an audible and visual alarm operational'? ❑ ❑ II ❑
Is septic tank pumped on a schedule'? • ❑ El
Are pumps or syphons operating properly'? III ❑ ❑ ❑
Are high and low water alarms operating properly'? ❑ ❑ I ❑
Comment
Page# 3
Permit: NC0076066 Owner-Facility: North Wilkes High School wwTP
Inspection Date: 12/19/2018 Inspection Type: Compliance Evaluation
Sand Filters (Low rate) Yes No NA NE
(If pumps are used)Is an audible and visible alarm Present and operational'? 0 ❑ E ❑
Is the distribution box level and watertight'? • ❑ ❑ ❑
Is sand filter free of ponding? ❑ • 0 ❑ ,
• Is the sand filter effluent re-circulated at a valid ratio'? ❑ 0 • ❑
#Is the sand filter surface free of algae or excessive vegetation'? • ❑ 0 ❑
#Is the sand filter effluent re-circulated at a valid ratio'?(Approximately 3 to 1) ❑ ❑ • ❑
Comment Significant pipe failures of two laterals was observed in separate sand filters at time of
inspection.These failure were resulting in uneven effluent distribution and ponding within the
sand filters. Laterals shall be repaired immediately. Routine maintenace procedures shall
included observation of system dosing at frequencies sufficient to prevent uneven
distribution, ponding, and allow for timely repair of damaged laterals.
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational? • 0 ❑ ❑
Are the tablets the proper size and type'? • ❑ ❑ ❑
Number of tubes in use'? 2
Is the level of chlorine residual acceptable'? • ❑ ❑ 0
Is the contact chamber free of growth, or sludge buildup'? M ❑ ❑ ❑
Is there chlorine residual prior to de-chlorination'? • 0 ❑ ❑
Comment'
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional'? ❑ 0 E ❑
Is sample collected below all treatment units? • ❑ 0 ❑
Is proper volume collected'? • ❑ 0 ❑'
Is the tubing clean'? 0 0 II ❑
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees ❑ 0 • ❑
Celsius)?
Is the facility sampling performed as required by the permit(frequency,sampling type M 0 ❑ ❑
representative)?
Comment.
Page# 4