HomeMy WebLinkAboutDEQ-CFW_00086404Title V Permit Number 03735T31 TITLE V AIR PERMIT DEVIATION SUMMARY REPORT For Calendar Year 2007 Page 1 of 1 Emission Source Description P Source or Control Device ID No.(s) Pollutant Deviation Description Deviation Date(s) Deviation Duration Suspected Cause of Deviation Corrective Action Taken Nafion(D None VOC The monthly 08/31/2007 6 days A lack of Area personnel Resins determination of communication have been given Process (ID VOC emissions for between key personal contacts No. NS-G) July 2007 is dated personnel and the stressing the September 5, 2007, absence of an importance of which was not within information system completing the 30 days of the end of to notify other team report in a timely that month as members of the manner. In specified by the status of the addition, electronic permit. monthly VOC reminders have determination. been assigned to key personnel. Nafion® NCD-Hdr-1 VOC Electronic records of 10/03/2007 5 hours The scrubber's flow A DCS loop was Vinyl Ethers (Control device) the parametric and transmitter was added to monitor North monitoring of the 10/04/2007 removed from running 3-hour Process (ID water scrubber service to determine average of scrubber No. NS-B) (NCD-Hdr-1) whether the injection flow rate injection liquid flow transmitter had and alarm as output rate were not malfunctioned. approaches permit recorded. This resulted in the limit. Procedures recorded three-hour now specify the average flow rate to shutdown the drop below the scrubber and all permitted minimum users when 3-hour flow rate. average low alarm is activated.