HomeMy WebLinkAboutDEQ-CFW_00086404Title V Permit Number 03735T31
TITLE V AIR PERMIT DEVIATION SUMMARY REPORT
For Calendar Year 2007
Page 1 of 1
Emission
Source
Description
P
Source or
Control Device
ID No.(s)
Pollutant
Deviation
Description
Deviation
Date(s)
Deviation
Duration
Suspected Cause
of Deviation
Corrective Action
Taken
Nafion(D
None
VOC
The monthly
08/31/2007
6 days
A lack of
Area personnel
Resins
determination of
communication
have been given
Process (ID
VOC emissions for
between key
personal contacts
No. NS-G)
July 2007 is dated
personnel and the
stressing the
September 5, 2007,
absence of an
importance of
which was not within
information system
completing the
30 days of the end of
to notify other team
report in a timely
that month as
members of the
manner. In
specified by the
status of the
addition, electronic
permit.
monthly VOC
reminders have
determination.
been assigned to
key personnel.
Nafion®
NCD-Hdr-1
VOC
Electronic records of
10/03/2007
5 hours
The scrubber's flow
A DCS loop was
Vinyl Ethers
(Control device)
the parametric
and
transmitter was
added to monitor
North
monitoring of the
10/04/2007
removed from
running 3-hour
Process (ID
water scrubber
service to determine
average of scrubber
No. NS-B)
(NCD-Hdr-1)
whether the
injection flow rate
injection liquid flow
transmitter had
and alarm as output
rate were not
malfunctioned.
approaches permit
recorded.
This resulted in the
limit. Procedures
recorded three-hour
now specify the
average flow rate to
shutdown the
drop below the
scrubber and all
permitted minimum
users when 3-hour
flow rate.
average low alarm
is activated.