HomeMy WebLinkAboutDEQ-CFW_00085941i i (SWU09
Qlly
North Carolina Department of Environment and Natural Resources
Division of Air Quality
Title V Annual Compliance Certification Forms
Facility Name: Vu.Pont Company — Fayetteville Works
Facility Address: 22828 NC Highway 87 W Fayetteville, NC 28306-7332
Facility Location: 22828 NC Highway 87 W Duart Township, Bladen Count
Facility ID Number: 0900009
Title V Permit Number: 03735T33
Start of Reporting Period: JanuM 1 2008
End of Reporting Period: December 312008
N
Compliance Statement (Check only one of the following options)
�.
During the reporting period specified above, this facility was in compliarice11with all terms a
conditions identified in the above referenced Title V Operating Permit. As such,; t}e
deviations, excess emissions events, or other reportable incidents including thoso
equipment malfunctions, breakdown, or upset conditions (please fill out the Compliance
Summary Report).
X During the reporting period specified above, this facility was in compliance with ALL terms and
conditions identified in the above referenced Title V Operating Permit, EXCEPT for the
deviations identified in the Deviation Summary Report (please fill out both the Compliance
Summary Report and Deviation Summary Report).
Does the above compliance statement differ from what is indicated on your most recent Title V Report
(i.e. last Semi -Annual Monitoring Report, Annual Emissions Inventory, etc)? ❑ Yes 0 No
Are you submitting this Annual Compliance Certification form to also fulfill a Title V Semi -Annual
Monitoring reporting requirement? ❑ Yes 0 No
Certification By Responsible Official
Based on information and belief formed after reasonable inquiry, the undersigned certifies under penalty
of law (federal rule 40 CFR 70.5(d)) that all information and statements provided in this form (inOmding
w.y
any attachments) are true, accurate, and complete."
rn
L� February 19, 2009
(Signature of Responsible ffici " (Date)
Name: Karen B. Wrigley
(Type or Print)
Number of Attached Pages (not including Instructions Page) 60
DEQ-CFW 00085941
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 1 of 54
Terms and Conditions
Records
Was
Emission
Source or
Deviation
Maintained
Deviation a.
Method(s) of
Permit
Condition
Source
Control
Device ID
?
?
non-
compliance
Determining
Compliance
Comments
Description
No.(s)
Condition
Summary
o
(Yes / N)
(Yes / No /
issue?
Status
Number
NA)
(Yes / No)
Emissions of particulate matter
No. 2/No. 6
PS-1 and
from the combustion of No. 2/No.
fuel oil -fired
PS-2
2.1(A)(1)(a)
6 fuel oil, that are discharged from
No
NA
NA
AP-42
boiler
this source into the atmosphere
calculation
shall not exceed 0.2667 pounds
per million Btu heat input.
2D .0503]
If emissions testing is required, the
No. 2/No. 6
PS-1 and
testing shall be performed in
fuel oil -fired
PS-2
2.1(A)(1)(b)
accordance General Condition JJ.
No
NA
NA
NA
boiler
[2D .2601]
No monitoring/recordkeeping/
No. 2/No. 6
PS-1 and
reporting is required for particulate
fuel oil -fired
PS-2
2.1(A)(l)(c)
emissions from the firing of No. 2
No
NA
NA
NA
boiler
or No. 6 fuel oil in these sources.
[2Q .0508(f)]
Emissions of sulfur dioxide from
No. 2/No. 6
PS-1 and
these sources shall not exceed 2.3
fuel oil -fired
PS-2
2.1(A)(2)(a)
pounds per million Btu heat input.
No
NA
NA
AP-42
boiler
[2D .0516]
calculation
If emissions testing is required, the
No. 2/No. 6
PS-1 and
testing shall be performed in
fuel oil -fired
PS-2
2.1(A)(2)(b)
accordance with 15A NCAC 2D
No
NA
NA
NA
boiler
.2601 and General Condition JJ
found in Section 3. [2D .2601]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 2 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Description
Device ID
Permit
Condition
?
Yes / No
( )
�
es / No /
compliance
Compliance
Comments
No.(s)
Condition
Summary
issue?
Status
Number
NA)
(Yes / No)
No monitoring/recordkeeping is
No. 2/No. 6
PS-1 and
required for sulfur dioxide
fuel oil -fired
PS-2
2.1(A)(2)(c)
emissions from No. 2 fuel oil
No
NA
NA
NA
boiler
burned in these sources. [2Q
.0508(f) and 2D .0501(c)(4)(A)]
The maximum sulfur content of
No. 2/No. 6
PS-1 and
any No. 6 fuel oil received and
Certificate of
fuel oil -fired
PS-2
2.1(A)(2)(d)
burned in the boiler shall not
No
Yes
NA
Analysis from
boiler
exceed 2.1 percent by weight. [2D
Oil Supplier
.0516]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 3 of 54
Emission
Source
Source or
Control
Device ID
Terms and Conditions
Deviation
?
Records
Maintained
?
Was
Deviation a
non-
compliance
Method(s) of
Determining
Compliance
Comments
Permit
Condition
Description
No.(s)
Condition
Summary
Y/ N
es o
( )
(Yes / No /
issue?
Status
Number
NA)
(Yes / No)
To assure compliance, the
No. 2/No. 6
PS-1 and
Permittee shall monitor the sulfur
fuel oil -fired
PS-2
2.1(A)(2)(e)
content of the No. 6 fuel oil by
No
Yes
NA
Certificate of
boiler
using fuel oil supplier certification
Analysis from
per shipment received. The results
Oil Supplier
of the fuel oil supplier
certifications shall be recorded in a
logbook on a quarterly basis and
include the following information:
i. Fuel oil supplier name;
ii. The maximum sulfur content
of the fuel oil received during
the quarter;
iii. The method used to determine
the maximum sulfur content of
the fuel oil; and
iv. A certified statement signed
by the responsible official that
the records of fuel oil supplier
certification submitted
represent all of the No. 6 fuel
oil fired during the period.
[2D .0516]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 4 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Device ID
Permit
Condition
?
?
compliance
Compliance
Comments
Description
No.(s)
Condition
Summary
Yes / No
( )
( Yes / No /
issue?
Status
Number
NA)
(Yes / No)
The Permittee shall submit a
No. 2/No. 6
PS-1 and
summary report of the fuel oil
fuel oil -fired
PS-2
2.1(A)(2)(f)
supplier certifications postmarked
No
Yes
NA
Title V
boiler
on or before January 30 of each
Semiannual
calendar year for the preceding
Summary
six-month period between July and
Report
December and July 30 of each
calendar year for the preceding
six-month period between January
and June. All instances of
deviations from the requirements
of this permit must be clearly
identified.
2D .0521
Visible emissions from the boiler
No. 2/No. 6
(ID No. PS-1) shall not be more
fuel oil -fired
PS-1
2.1(A)(3)(a)
than 40 percent opacity when
No
Yes
NA
Daily visible
boiler
averaged over a six -minute period.
emissions
However, six -minute averaging
observations
periods may exceed 40 percent not
more than once in any hour and
not more than four times in any
24-hour period. In no event shall
the six -minute average exceed 90
percent o aci 2D .0521]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 5 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Device ID
Permit
Condition
compliance
Compliance
Comments
Description
No.(s)
Condition
Summary
Yes / No
( )
Yes / No /
issue?
Status
Number
NA)
(Yes / No)
Visible emissions from the boiler
No. 2/No. 6
(ID No. PS-2) shall not be more
fuel oil -fired
PS-2
2.1(A)(3)(b)
than 20 percent opacity when
No
Yes
NA
Daily visible
boiler
averaged over a six -minute period.
emissions
However, six -minute averaging
observations
periods may exceed 20 percent not
more than once in any hour and
not more than four times in any
24-hour period. In no event shall
the six -minute average exceed 87
percent opacity.
[2D .0521]
If emissions testing is required, the
No. 2/No. 6
PS-1 and
testing shall be performed in
fuel oil -fired
PS-2
2.1(A)(3)(c)
accordance with 15A NCAC 2D
No
NA
NA
NA
boiler
.2601 and General Condition JJ.
[2D .2601]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 6 of 54
Emission
Source
Source or
Control
Device ID
Terms and Conditions
Deviation
?
Records
Maintained
?
Was
Deviation a
non-
compliance
Method(s) of
Determining
Compliance
Comments
Permit
Condition
Description
No.(s)
Condition
Summary
�1'
(Yes / No)
(Yes / No /
issue?
Status
Number
NA)
(Yes / No)
To assure compliance, each day
No. 2/No. 6
PS-1 and
that an affected source fires No. 6
fuel oil -fired
PS-2
2.1(A)(3)(d)
fuel oil, the Permittee shall
No
Yes
NA
Review of
boiler
observe the emission point of the
daily visible
affected source for any visible
emissions
emissions above normal. The
observation
daily observation must be made
records
for each day of the calendar year
period to ensure compliance with
this requirement. If visible
emissions from this source are
observed to be above normal, the
Permittee shall either:
i. Take appropriate action to
correct the above -normal
emissions as soon as
practicable and within the
monitoring period, or
ii. Demonstrate that the percent
opacity from the emission
points of the emission source is
below the limit given in Section
2.1 A.3.a. orb. above.
[2Q 0508(f ]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 7 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Description
Device ID
Permit
Condition
?
(Yes / No)
?
(Yes / No /
compliance
Compliance
Comments
No.(s)
Condition
Summary
�"y
issue?
Status
Number
NA)
(Yes / No)
The results of the monitoring shall
No. 2/No. 6
PS-1 and
be maintained in a logbook
fuel oil -fired
PS-2
2.1(A)(3)(e)
(written or electronic format) on-
No
Yes
NA
Review of
boiler
site and made available to an
daily visible
authorized representative upon
emissions
request. The logbook shall record
observation
the following:
records
i. The date and time of each
recorded action;
I The results of each
observation and/or test noting
those sources with emissions
that were observed to be in
noncompliance along with any
corrective actions taken to
reduce visible emissions; and
iii. The results of any corrective
actions performed.
[2 0508 f)]
No monitoring/recordkeeping/
No. 2/No. 6
PS-1 and
reporting is required for visible
fuel oil -fired
PS-2
2.1(A)(3)(f)
emissions from the firing of No. 2
No
NA
NA
NA
boiler
fuel oil in these sources. [2Q
.0508 (f)]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 8 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Description
Device ID
Permit
Condition
?
(Yes / No)
?
(Yes / No /
compliance
Compliance
Comments
No.(s)
Condition
Summary
ry
issue?
Status
Number
NA)
(Yes / No)
The Permittee shall submit a
No. 2/No. 6
PS-1 and
summary report of the
fuel oil -fired
PS-2
2.1(A)(3)(g)
observations postmarked on or
No
Yes
NA
Title V
boiler
before January 30 of each calendar
Semiannual
year for the preceding six-month
Summary
period between July and
Report
December and July 30 of each
calendar year for the preceding
six-month period between January
and June. All instances of
deviations from the requirements
of this permit must be clearly
identified.
[2 .0508(f)]
In order to avoid applicability of
No. 2/No. 6
15A NCAC 2D .0530(g) for major
fuel oil -fired
PS-2
2.1(A)(4)(a)
sources and major modifications,
No
Yes
NA
Emissions
boiler
the affected boiler (ID No. PS-2
determined
only) shall discharge into the
monthly using
atmosphere less than 25 tons of
AP-42 factors
particulate matter per consecutive
12-month period. [2 .0317]
In order to avoid applicability of
No. 2/No. 6
15A NCAC 2D .0530(g) for major
fuel oil -fired
PS-2
2.1(A)(4)(a)
sources and major modifications,
No
Yes
NA
Emissions
boiler
the affected boiler (ID No. PS-2
determined
only) shall discharge into the
monthly using
atmosphere less than 15 tons of
AP-42 factors
particulate matter under 10
microns per consecutive 12-month
period.. [2Q .0317]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 9 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Description
Device ID
Permit
Condition
?
Yes / No
( )
?
( Yes / No /
compliance
Compliance
Comments
No.(s)
Condition
Summary
issue?
Status
Number
NA)
(Yes / No)
In order to avoid applicability of
No. 2/No. 6
15A NCAC 2D .0530(g) for major
fuel oil -fired
PS-2
2.1(A)(4)(a)
sources and major modifications,
No
Yes
NA
Emissions
boiler
the affected boiler (ID No. PS-2
determined
only) shall discharge into the
monthly using
atmosphere less than 40 tons of
AP-42 factors
Nitrogen Oxide per consecutive
12-month period.
2 .0317]
In order to avoid applicability of
No. 2/No. 6
15A NCAC 2D .0530(g) for major
fuel oil -fired
PS-2
2.1(A)(4)(a)
sources and major modifications,
No
Yes
NA
Emissions
boiler
the affected boiler (ID No. PS-2
determined
only) shall discharge into the
monthly using
atmosphere less than 40 tons of
AP-42 factors
Sulfur Dioxide per consecutive 12-
month period.
[2Q .0317]
If emissions testing is required, the
No. 2/No. 6
Permittee shall perform such
fuel oil -fired
PS-2
2.1(A)(4)(b)
testing in accordance with General
No
NA
NA
NA
boiler
Condition JJ.
[2Q .2601]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 10 of 54
Emission
Source
Source or
Control
Device ID
Terms and Conditions
Deviation
?
Records
Maintained
?
Was
Deviation a
non-
compliance
Method(s) of
Determining
Compliance
Comments
Permit
Condition
Description
No.(s)
Condition
Summary
�'
(Yes / No)
(Yes / No /
issue?
Status
Number
NA)
(Yes / No)
The Permittee shall keep monthly
No. 2/No. 6
accounting records of the amount
fuel oil -fired
PS-2
2.1(A)(4)(c)
of fuel used and the sulfur content,
No
Yes
NA
Fuel
boiler
including certification of the fuel,
consumption
in a logbook (written or in
and sulfur
electronic format). The Permittee
content
shall be deemed in noncompliance
records
with 15A NCAC 2D .0530 if the
sulfur content of the fuel is not
monitored.
- -
[2Q.0508(fl]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 11 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Description
Device ID
Permit
Condition
?
(Yes / No)
?
(Yes / No /
compliance
Compliance
Comments
No.(s)
Condition
Summary
ry
NA)
issue?
Status
Number
(Yes / No)
The Permittee shall submit a semi -
No. 2/No. 6
annual summary report of
fuel oil -fired
PS-2
2.1(A)(4)(d)
monitoring and recordkeeping
No
Yes
NA
Semi-annual
boiler
activities. The report shall contain
reports to NC
the following:
Division of
i. The monthly particulate
Air Quality
matter, particulate matter
FRO
below 10 microns, nitrogen
oxide, and sulfur dioxide
emissions for the previous 17
months. The emissions must
be calculated for each of the
12-month periods over the
previous 17 months;
ii. The monthly quantities of No.
2/No. 6 fuel oil consumed for
the previous 17 months;
iii. The average sulfur content for
the fuel oil; and,
iv. All instances of deviations
from the requirements of this
permit must be clearly
identified.
[2 .0508(fl]
Emissions of particulate matter
from the affected source (ID No.
Monthly
Butacite®
BS-C
2.1(B)(1)(a)
BS-C) shall not exceed an
No
Yes
NA
visible
flake dryer
allowable emission rate.
emissions
[2D .0515)
logbook
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 12 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Device ID
Permit
Condition
?
?
compliance
Compliance
Comments
Description
No.(s)
Condition
Summary
Yes / No
( )
( Yes / No /
issue?
Status
Number
NA)
(Yes / No)
If emissions testing is required, the
testing shall be performed in
Butacite®
BS-C
2.1(B)(1)(b)
accordance with General
No
NA
NA
NA
flake dryer
Condition JJ. If the results of this
test are above the limit given in
Section 2.1 B.La. above, the
Permittee shall be deemed in
noncompliance with 15A NCAC
2D .0515.
[2D .2601]
Particulate matter emissions from
the Butacite® flaker dryer (ID No.
Butacite®
BS-C
2.1(13)(1)(c)
BS-C) shall be controlled by the
No
Yes
NA
Butacite®
flake dryer
bagfilter (ID No. BCD-C2) and
maintenance
cyclone separator (ID No. BCD-
records
Cl). To assure compliance, the
Permittee shall perform
inspections and maintenance as
recommended by the
manufacturer. As a minimum, the
inspection and maintenance
requirement shall include the
following:
i. A monthly visual inspection of
the system ductwork and
material collection unit for
leaks; and
ii. An annual internal inspection
of the bagfilter's structural
integrity.
2 .0508 ]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 13 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non- .
Determining
Source
Device ID
Permit
Condition
?
?
compliance
Compliance
Comments
Description
No.(s)
Condition
Summary
�'y
(Yes / No)
(Yes / No /
issue?
Status
Number
NA)
(Yes / No)
The results of inspection and
maintenance shall be maintained in
Butacite®
BS-C
2.1(B)(1)(d)
a logbook (written or electronic
No
Yes
NA
Butacite®
flake dryer
format) on -site and made available
Bagfilter
to an authorized representative
Logbook
upon request. The logbook shall
record the following:
i. The date and time of each
recorded action;
ii. The results of each inspection;
iii. The results of any
maintenance performed on the
bagfilters; and
iv. Any variance from
manufacturer's
recommendations, if any, and
corrections made.
[2D .0515]
The Permittee shall submit the
results of any maintenance
Butacite®
BS-C
2.1(B)(1)(e)
performed on the bagfilters within
No
Yes
NA
Butacite®
flake dryer
30 days of a written request by the
Bagfilter
DAQ.
Logbook
[2 .0508( ]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 14 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Description
Device ID
Permit
Condition
?
(Yes / No)
?
(Yes / No
compliance
Compliance
Comments
No.(s)
Condition
Summary
NA)
issue?
Status
Number
(Yes / No)
The Permittee shall submit a
summary report of monitoring and
Butacite®
BS-C
2.1(B)(1)(f)
recordkeeping activities
No
Yes
NA
Semi-annual
flake dryer
postmarked on or before January
reports to NC
30 of each calendar year for the
Division of
preceding six-month period
Air Quality
between July and December and
FRO
July 30 of each calendar year for
the preceding six-month period
between January and June. All
instances of deviations from the
requirements of this permit must
be clearly identified.
2D .0515
Visible emissions from the
affected source (ID No. BS-C)
Butacite®
BS-C
2.1(13)(2)(a)
shall not be more than 20 percent
No
Yes
NA
Monthly
flake dryer
opacity when averaged over a six-
visible
minute period. However, six-
emissions
minute averaging periods may
logbook
exceed 20 percent not more than
once in any hour and not more
than four times in any 24-hour
period. In no event shall the six -
minute average exceed 87 percent
o acity.[2D.0521]
If emissions testing is required, the
testing shall be performed in
Butacite®
BS-C
2.1(13)(2)(b)
accordance with 15A NCAC 2D
No
NA
NA
NA
flake dryer
.2601 and General Condition JJ.
[2D .2601]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 15 of 54
Emission
Source
Source or
Control
Device ID
Terms and Conditions
Deviation
?
Records
Maintained
?
Was
Deviation a
non-
compliance
Method(s) of
Determining
Compliance
Comments
Permit
Condition
Description
No.(s)
Condition
Summary
�3'
(Yes / No)
(Yes / No /
issue?
Status
Number
NA)
(Yes / No)
To assure compliance, once a
month the Permittee shall observe
Butacite®
BS-C
2.1(13)(2)(c)
the emission point of the affected
No
Yes
NA
Monthly
flake dryer
source for any visible emissions
visible
above normal. The monthly
emissions
observation must be made for each
logbook
month of the calendar year period
to ensure compliance with this
requirement. If visible emissions
from this source are observed to be
above normal, the Permittee shall
either:
i. Take appropriate action to
correct the above -normal
emissions as soon as
practicable and within the
monitoring period, or
ii. Demonstrate that the percent
opacity from the emission
points of the emission source
is below the limit given in
Section 2.1 B.2.a. above.
[2 .0508 f)]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 16 of 54
Emission
Source
Source or
Control
Device ID
Terms and Conditions
Deviation
?
Records
Maintained
?
Was
Deviation a
non-
compliance
Method(s) of
Determining
Compliance
Comments
Permit
Condition
Description
No.(s)
Condition
Summary
es / No
(Yes )
(Yes / No J
issue?
Status
Number
NA)
(Yes / No)
The results of the monitoring shall
Butacite®
be maintained in a logbook
flake dryer
BS-C
2.1(B)(2)(d)
(written or electronic format) on-
No
Yes
NA
Monthly
site and made available to an
visible
authorized representative upon
emissions
request. The logbook shall record
logbook
the following:
i. The date and time of each
recorded action;
ii. The results of each
observation and/or test noting
those sources with emissions
that were observed to be in
noncompliance along with any
corrective actions taken to
reduce visible emissions; and
iii. The results of any corrective
actions performed.
[2 .0508(
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 17 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Device ID
Permit
Condition
?
?
compliance
Compliance
Comments
Description
No.(s)
Condition
Summary
es o
Y/ N
( )
(Yes / No /
issue?
Status
Number .
NA)
(Yes / No)
The Permittee shall submit a
summary report of the
Butacite®
BS-C
2.1(13)(2)(e)
observations postmarked on or
No
Yes
NA
Semi-annual
flake dryer
before January 30 of each calendar
reports to NC
year for the preceding six-month
Division of
period between July and
Air Quality
December and July 30 of each
FRO
calendar year for the preceding
six-month period between January
and June. All instances of
deviations from the requirements
of this permit must be clearly
identified.
Emissions from the polyvinyl
butyral sheeting rotogravure
Butacite®
BS-D
2.1(B)(4)(a)
printing operation shall be
No
Yes
NA
1999
sheeting
controlled using a permanent total
Stationary
rotogravure
enclosure for the process area and
Source
printing
a multi -stage horizontal spray
Sampling
operation
scrubber (ID No. BCD-D1) that
Report
achieves an overall organic HAP
control efficiency of at least 95
percent.
[2Q .0508(f)]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 18 of 54
Emission
Source
Source or
Control
Device ID
Terms and Conditions
Deviation
?
Records
Maintained
?
Was
Deviation a
non-
compliance
Method(s) of
Determining
Compliance
Comments
Permit
Condition
Description
No.(s)
Condition
Summary
Yes / No
( )
(Yes / No /
issue?
Status
Number
NA)
(Yes / No)
The Permittee shall ensure the
proper performance of the
Butacite®
BS-D
2.1(B)(4)(b)
scrubber (ID No. BCD-D1) by
No
Yes
NA
Butacite®
sheeting
monitoring the following
IP21
rotogravure
operational parameters:
Data
printing
i. Water flow rate to each nozzle
Historian
operation
(minimum of 6 gallons per
minute, averaged over a three-
hour period).
ii. Air flow rate to each nozzle
(minimum of 63 standard
cubic feet per minute,
averaged over a three-hour
period).
iii. General area exhaust fan exit
velocity (minimum of 3,950
feet per minute, averaged over
a three-hour period).
[2D .1111]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 19 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Device ID
Permit
Condition
?
?
compliance
Compliance
Comments
Description
No.(s)
Condition
Summary
Yes / No
( )
( Yes / No /
issue?
Status
Number
NA)
(Yes / No)
The Permittee shall comply with
all applicable record keeping and
Butacite®
BS-D
2.1(B)(4)(c)
reporting requirements specified in
No
Yes
NA
Butacite®
sheeting
40 CFR Part 63, including the
IP21
rotogravure
following:
Data
printing
i. If an action taken by the
Historian
operation
Permittee during a startup,
shutdown, or malfunction is
not consistent with the affected
source's SSM plan, the
Permittee shall record the
actions taken and shall report
such actions.
ii. The Permittee shall submit to
the Regional Supervisor,
DAQ, a semi-annual summary
report.
iii. If the actions taken by the
Permittee during start-up,
shutdown, or malfunction
(SSM) are not completely
consistent with the SSM plan,
then the Permittee shall submit
an SSM report.
[2D .1111
Nafion®
Emissions of particulate matter
Emission
membrane
from the affected source (ID No.
AP-42
source NS-I
coating
NS-I
2.1(C)(1)(a)
NS-I) shall not exceed an
No
NA
NA
calculation
has no visible
allowable emission rate.
process
[2D .0515]
emissions
o-
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 20 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Description
Device ID
Permit
Condition
?
(Yes / No)
?
(Yes / No /
compliance
Compliance
Comments
No. s
()
Condition
Summary
issue?
Status
Number
NA)
(Yes / No)
Nafion®
If emissions testing is required, the
membrane
testing shall be performed in
NS-I
2.1(C)(1)(b)
accordance with General
No
NA
NA
NA
coating
Condition JJ.
process
[2D .2601]
The Permittee shall maintain
production records such that the
Nafion®
NS-I
2.1(C)(1)(c)
process rates "P" in tons per hour,
No
Yes
NA
Nafion®
membrane
as specified by the formulas
Production
coating
contained above (or the formulas
Records
process
contained in 15A NCAC 2D
.0515) can be derived, and shall
make these records available to a
DAQ authorized representative
upon request. 2 .0508(f)
The Permittee shall submit a
summary report of monitoring and
Nafion®
NS-I
2.1(C)(1)(d)
recordkeeping activities
No
Yes
NA
Semi-annual
membrane
postmarked on or before January
reports to NC
coating
30 of each calendar year for the
Division of
process
preceding six-month period
Air Quality
between July and December and
FRO
July 30 of each calendar year for
the preceding six-month period
between January and June. All
instances of deviations from the
requirements of this permit must
be clearly identified.
[2Q 0508(fl]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 21 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Device ID
Permit
Condition
compliance
Compliance
Comments
Description
No.(s)
Condition
Summary
(Yes / No)
(Yes / No !
issue?
Status
Number
NA)
(Yes / No)
Visible emissions from the
affected source (ID No. NS-I)
Nafion®
NS-I
2.1(C)(2)(a)
shall not be more than 20 percent
No
NA
NA
NA
Emission
membrane
opacity when averaged over a six-
source NS-I
coating
minute period. However, six-
has no visible
process
minute averaging periods may
emissions
exceed 20 percent not more than
once in any hour and not more
than four times in any 24-hour
period. In no event shall the six -
minute average exceed 87 percent
o aci . 2D .0521]
If emissions testing is required, the
testing shall be performed in
Nafion®
NS-I
2.1(C)(2)(b)
accordance with 15A NCAC 2D
No
NA
NA
NA
Emission
membrane
.2601 and General Condition JJ.
source NS-I
coating
If the results of this test are above
has no visible
process
the limit given in Section 2.1
emissions
C.2.a. above, the Permittee shall
be deemed in noncompliance with
15A NCAC 2D .0521.
[2D .2601]
No monitoring/recordkeeping/
reporting is required for visible
Emission
Nafion®
NS-I
2.1(C)(2)(c)
emissions from this source. [2Q
No
NA
NA
NA
source NS-I
membrane
.0508(f)]
has no visible
coating
emissions
process
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 22 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Device ID
Permit
Condition
?
?
compliance
Compliance
Comments
Description
No.(s)
Condition
Summary
(Yes / No)
(Yes / No /
issue?
Status
Number
NA)
(Yes / No)
In order to avoid applicability of
this regulation, the Vinyl Ethers
Vinyl Ethers
NS-B
2.1(C)(4)(a)
North process (ID No. NS-B) shall
No
Yes
NA
Monthly
North
discharge into the atmosphere less
Emissions
process
than 68.9 tons of VOCs per
Report
consecutive 12-month period.
[2 .0317
Calculations of VOC emissions
Vinyl Ethers
per month shall be made within 30
Monthly
North
NS-B
2.1(C)(4)(b)
days of the end of each month.
No
Yes
NA
Emissions
process
[2Q .0508(f)]
Report
The total amount of VOC
Vinyl Ethers
emissions shall be recorded
Monthly
North
NS-B
2.1(C)(4)(c)
monthly in a logbook (written or
No
Yes
NA
Emissions
process
electronic format).
Report
[2 .0317
The Permittee shall ensure the
proper performance of the Nafion
Vinyl Ethers
NS-B
2.1(C)(4)(d)
Baffle Plate -Type Tower
No
Yes
NA
Scrubber
North
Scrubbers (ID Nos. NCD-Hdr-I
Circulation
process
and NCD-Hdr-2) by monitoring
Flow Rate
the following operational
Logbook
parameters:
i. Injection liquid flow rate
(minimum of 7,000 kilograms
per hour, averaged over a
three-hour period).
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 23 of 54
Emission
Source
Source or
Control
Device ID
Terms and Conditions
Deviation
?
Records
Maintained
?
Was
Deviation a
non-
compliance
Method(s) of
Determining
Compliance
Comments
Permit
Condition
Description
No.(s)
Condition
Summary
ry
(Yes / No)
(Yes / No /
issue?
Status
Number
NA)
(Yes / No)
The Permittee shall record the
results of inspections in a scrubber
Vinyl Ethers
NS-B
2.1(C)(4)(e)
logbook (written or electronic
No
Yes
NA
Scrubber
North
records), which shall be kept on
Circulation
process
site and made available to Division
Flow Rate
of Air Quality personnel upon
Logbook and
request. Any variance from the
SAP
manufacturer's recommendations
Maintenance
or the permit monitoring
Historian
requirements, or the failure of the
air pollution control equipment to
operate in a normal and usual
manner, shall be investigated with
corrections made and dates of
action recorded in the log book.
The inspection and maintenance
activities, as well as required
monitoring for scrubbing liquid
flow rates, and scrubber pressure
drops, if appropriate, shall be
recorded. [2Q .0508(f)
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 24 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Device ID
Permit
Condition
?
?
compliance
Compliance
Comments
Description
No.(s)
Condition
Summary
es / No )
( Yes / No /
issue?
Status
Number
NA)
(Yes / No)
The Permittee shall submit a semi-
annual summary report, acceptable
Vinyl Ethers
NS-B
2.1(C)(4)(f)
to the Regional Air Quality
No
Yes
NA
Semi-annual
North
Supervisor, of monitoring and
reports to NC
process
recordkeeping activities. The
Division of
report shall contain the following:
Air Quality
i. The monthly VOC emissions
FRO
for the previous 17 months.
The emissions shall be
calculated for each of the 12-
month periods over the
previous 17 months.
[2 .0508(
In order to avoid applicability of
this regulation, the resins process
Monthly
Resins
NS-G
2.1(C)(5)(a)
(ID No. NS-G) shall discharge into
No
Yes
NA
Emissions
process
the atmosphere less than 40 tons of
Report
VOCs per consecutive 12-month
eriod. [2 .0317]
Calculations of VOC emissions
per month shall be made within 30
Monthly
Resins
NS-G
2.1(C)(5)(b)
days of the end of each month.
No
Yes
NA
Emissions
process
[2Q .0508(f)]
Report
The total amount of VOC
emissions shall be recorded
Monthly
Resins
NS-G
2.1(C)(5)(c)
monthly in a logbook (written or
No
Yes
NA
Emissions
process
electronic format).
Report
[2 .0317]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 25 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Description
Device ID
Permit
Condition
?
(Yes / No)
?
(Yes ! No /
compliance
Compliance
Comments
No.(s)
Condition
Summary
n'
issue?
Status
Number
NA)
(Yes / No)
The Permittee shall submit a semi-
annual summary report, acceptable
Resins
NS-G
2.1(C)(5)(d)
to the Regional Air Quality
No
Yes
NA
Semi-annual
process
Supervisor, of monitoring and
reports to NC
recordkeeping activities. The
Division of
report shall contain the following:
Air Quality
i. The monthly VOC emissions
FRO
for the previous 17 months.
The emissions shall be
calculated for each of the 12-
month periods over the
previous 17 months.
[2 .0508( ]
In order to avoid applicability of
this regulation, the HFPO process
HFPO
NS-A
2.1(C)(6)(a)
(ID No. NS-A) shall discharge into
No
Yes
NA
Monthly
process
the atmosphere less than 85.3 tons
Emissions
of VOCs per consecutive 12-
Report
month eriod. [2 .0317]
Calculations of VOC emissions
per month shall be made within 30
HFPO
NS-A
2.1(C)(6)(b)
days of the end of each month.
No
Yes
NA
Monthly
process
The Permittee shall be deemed in
Emissions
noncompliance with 15A NCAC
Report
2D .0530 if the amounts of VOC
containing materials or the VOC
emissions are not monitored and
recorded.
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 26 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Description
Device ID
Permit
Condition
?
(Yes / No)
?
(Yes / No /
compliance
Compliance
Comments
No.(s)
Condition
Summary
�Y
issue?
Status
Number
NA)
(Yes / No)
The total amount of VOC
emissions shall be recorded
Monthly
HFPO
NS-A
2.1(C)(6)(c)
monthly in a logbook (written or
No
Yes
NA
Emissions
process
electronic format).
Report
[2 .0317]
The Permittee shall submit a semi-
annual summary report, acceptable
HFPO
NS-A
2.1(C)(6)(d)
to the Regional Air Quality
No
Yes
NA
Semi-annual
process
Supervisor, of monitoring and
reports to NC
recordkeeping activities. The
Division of
report shall contain the following:
Air Quality
i. The monthly VOC emissions
FRO
for the previous 17 months.
The emissions shall be
calculated for each of the 12-
month periods over the
previous 17 months.
2 .0508(
The Permittee shall comply with all
applicable provisions contained in
Nafion®
NS-A
2.1(C)(7)(a)
Environmental Management
Yes
Yes
No
Records
See attached
processes
throughN
Commission Standard 15A NCAC
review
deviation
S-L
2D .1111, "Maximum Achievable
notification
Control Technology" (MACT) as
dated
promulgated in 40 CFR Part 63,
08/06/2008
Subpart FFFF by May 10, 2008, or
as provided in the rule.
[40 CFR 63.2445(b)]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 27 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Device ID
Permit
Condition
?
compliance
Compliance
Comments
Description
No.(s)
Condition
Summary
(Yes / No)
(Yes / No /
issue?
Status
Number
NA)
(Yes / No)
The Permittee shall submit a
Notification of Compliance Status
Notification
Nafion®
NS-A
2.1(C)(7)(b)
to the Fayetteville Regional in
No
Yes
NA
of
processes
throughN
accordance with 40 CFR
Compliance
S-L
63.2520(d) by October 7, 2008, or
Status Report
as provided in the rule.
submitted on
[2D .1111]
10/01/2008
Fluoro-
Emissions of particulate matter
products
from the affected source (ID No.
polymer
FS-A
2.1(D)(1)(a)
FS-A) shall not exceed an
No
NA
NA
AP-42
manufact'g
allowable emission rate.
Calculation
develop-
[2D .0515]
ment facility
Fluoro-
If emissions testing is required, the
products
testing shall be performed in
polymer
FS-A
2.1(D)(1)(b)
accordance with General
No
NA
NA
NA
manufact'g
Condition JJ.
develop-
[2D .2601]
ment facility
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 28 of 54
Emission
Source
Source or
Control
Device ID
Terms and Conditions
Deviation
?
Records
Maintained
?
Was
Deviation a
non-
compliance
Method(s) of
Determining
Compliance
Comments
Permit
Condition
Description
No.(s)
Condition
Summary
�1'
(Yes / No)
(Yes / No /
issue?
Status
Number
NA)
(Yes / No)
Fluoro-
Particulate matter emissions from
products
the Fluoroproducts polymer
polymer
FS-A
2.1(D)(1)(c)
manufacturing facility (ID No.
No
Yes
NA
Records
manufact'g
FS-A) shall be controlled by the
Review
develop-
bagfrlter (ID No. FCD-A2). To
ment facility
assure compliance, the Permittee
shall perform inspections and
maintenance. As a minimum, the
inspection and maintenance
requirement shall include the
following:
i. A monthly visual inspection
of the system ductwork and
material collection unit for
leaks; and
I An annual internal inspection
of the bagfilter's structural
integrity.
[2 .0508 (f)
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 29 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Description
Device ID
Permit
Condition
?
Yes / No
( )
?
( Yes / No /
compliance
Compliance
Comments
No.(s)
Condition
Summary
N`4)
issue?
Status
Number
(Yes / No)
Fluoro-
The results of inspection and
products
maintenance shall be maintained in
polymer
FS-A
2.1(D)(1)(d)
a logbook (written or electronic
No
Yes
NA
Records
manufact'g
format) on -site and made available
Review
develop-
to an authorized representative
ment facility
upon request. The logbook shall
record the following:
i. The date and time of each
recorded action;
ii. The results of each inspection;
iii. The results of any
maintenance performed on the
bagfilters; and
iv. Any variance from
manufacturer's
recommendations, if any, and
corrections made.
[2D .0515]
Fluoro-
The Permittee shall submit the
products
results of any maintenance
polymer
FS-A
2.1(D)(1)(e)
performed on the bagfilters within
No
Yes
NA
Records
manufact'g
30 days of a written request by the
Review
develop-
DAQ.
ment facility
[2Q .0508(f)]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 30 of 54
Source or
Terms and Conditions
Records
was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
min
Detering
Source
Description
Device ID
Permit
Condition
Condition
Summary
?
Y/ No
(es )
( Yes / No /
compliance
Compliance
Comments
No.(s)
NA)
issue?
Status
Number
(Yes / No)
Fluoro-
The Permittee shall submit a
products
summary report of monitoring and
polymer
FS-A
2.1(D)(1)(f)
recordkeeping activities
No
Yes
NA
Semi-annual
manufact'g
postmarked on or before January
reports to NC
develop-
30 of each calendar year for the
Division of
ment facility
preceding six-month period
Air Quality
between July and December and
FRO
July 30 of each calendar year for
the preceding six-month period
between January and June. All
instances of deviations from the
requirements of this permit must
be clearly identified.
[2D .0515
Fluoro-
Visible emissions from the
products
affected source (ID Nos. FS-A)
Polymer
FS-A
2.1(13)(2)(a)
shall not be more than 20 percent
No
NA
NA
Emission
manufact'g
opacity when averaged over a 6-
source FS-A
develop-
minute period. However, 6-minute
has no visible
ment facility
averaging periods may exceed 20
emissions
percent not more than once in any
hour and not more than four times
in any 24-hour period, and shall
the 6-minute average exceed 87
percent op acity. 2D .0521
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 31 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Description
Device ID
Permit
Condition
?
Yes { No
( )
?
( Yes { No I
compliance
Compliance
Comments
No.(s)
Condition
Summary
NA)
issue?
Status
Number
(Yes / No)
Fluoro-
If emissions testing is required, the
products
testing shall be performed in
polymer
FS-A
2.1(D)(2)(b)
accordance with 15A NCAC 2D
No
NA
NA
NA
manufact'g
.2601 and General Condition JJ.
develop-
[2D .2601]
ment facility
Fluoro-
No monitoring/recordkeeping/
products
reporting is required for visible
polymer
FS-A
2.1(D)(2)(c)
emissions from this source. [2Q
No
NA
NA
NA
manufact'g
.0508(f)]
develop-
ment facility
Fluoro-
In order to avoid applicability of
products
this regulation, the fluoroproducts
polymer
FS-A
2.1(D)(4)(a)
polymer manufacturing
No
Yes
NA
Monthly
manufact'g
development facility (ID No. FS-
Emissions
develop-
A) shall discharge into the
Report
ment facility
atmosphere less than 40 tons of
VOCs per consecutive t2-month
12 .0317
Fluoro-
_period.
Calculations of VOC emissions
products
per month shall be made within 30
polymer
FS-A
2.1(D)(4)(b)
days of the end of each month.
No
Yes
NA
Monthly
manufact'g
[2Q .0508(f)]
Emissions
develop-
Report
ment facility
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 32 of 54
Emission
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Source
Control
Deviation
Maintained
non-
Determining
Description
Device ID
No.(s)
Permit
Condition
Condition
Summary
?
Yes / No
( )
?
es / No /
compliance
Compliance
Comments
Number
NA)
issue?
Status
(Yes / No)
Fluoro-
The total amount of VOC
products
emissions shall be recorded
polymer
FS-A
2.1(1))(4)(c)
monthly in a logbook (written or
No
Yes
NA
Monthly
manufact'g
electronic format).
Emissions
develop-
[2Q .0317]
Report
ment facility
Fluoro-
The Permittee shall submit a semi -
products
annual summary report, acceptable
polymer
FS-A
2.1(1))(4)(d)
to the Regional Air Quality
No
Yes
NA
Semi-annual
manufact'g
Supervisor, of monitoring and
reports to NC
develop-
recordkeeping activities
Division of
ment facility
postmarked on or before January
Air Quality
30 of each calendar year for the
FRO
preceding six-month period
between July and December, and
July 30 of each calendar year for
the preceding six-month period
between January and June. The
report shall contain the following:
i. The monthly VOC emissions
for the previous 17 months.
The emissions shall be
calculated for each of the 12-
month periods over the
previous 17 months.
2 .0508(
0
0
0
w
c
w
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 33 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Detennining
Source
Description
Device ID
Permit
Condition
?
Y/ N
es o
( )
?
(Yes / No /
compliance
Compliance
Comments
No. s
()
Condition
Summary
rY
issue?
Status
Number
NA)
(Yes / No)
Emissions of particulate matter
discharged into the atmosphere
No. 2 fuel
PS -Temp
2.1(G)(1)(a)
from the combustion of fuel oil at
No
NA
NA
AP-42
oil -fired
the temporary boiler (ID No. PS-
calculation
temporary
Temp) shall not exceed 0.2426
boiler
pounds per million Btu heat input.
2D .0503]
If emissions testing is required, the
No. 2 fuel
testing shall be performed in
oil -fired
PS -Temp
2.1(G)(l)(b)
accordance General Condition 77.
No
NA
NA
NA
temporary
[2D .2601]
boiler
No monitoring/recordkeeping/
No. 2 fuel
reporting is required for particulate
oil -fired
PS -Temp
2.1(G)(1)(b)
emissions from the firing of No. 2
No
NA
NA
NA
temporary
fuel oil in this source for this
boiler
regulation.
[2 .0508(f)
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 34 of 54
Source or
Terms and Conditions
Records
was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Description
Device ID
Permit
Condition
?
Y es / No
( )
?
( Yes / No /
compliance
Compliance
Comments
No.(s)
Condition
Summary
NA)
issue?
Status
Number
(Yes / No)
The Permittee shall comply with
all applicable provisions, including
No. 2 fuel
PS -Temp
2.1(G)(2)(a)
the notification, testing,
No
NA
NA
NA
oil -fired
recordkeeping, and monitoring
temporary
requirements contained in
boiler
Environmental Management
Commission Standard 15A NCAC
2D .0524 "New Source
Performance Standards (NSPS) as
promulgated in 40 CFR Part 60
Subpart Dc, including Subpart A
"General Provisions."
[2D .0524
The maximum sulfur content of
No. 2 fuel
any fuel oil received and burned in
Certificate of
oil -fired
PS -Temp
2.1(G)(2)(b)
the boiler (ID No. PS -Temp) shall
No
Yes
NA
Analysis from
temporary
not exceed 0.5 percent by weight.
Oil Supplier
boiler
[2D .0524]
Visible emissions shall not exceed
20 percent opacity (6 minute
No. 2 fuel
PS -Temp
2.1(G)(2)(c)
average) except for one six -minute
No
NA
NA
Voluntary
oil -fired
period per hour but not more than
daily
temporary
27 percent opacity when firing fuel
observations
boiler
oil. [2D .0524]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 35 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Detern,;n *
Source
Description
Device ID
Permit
Condition
?
Yes / No
( )
?
( Yes / No /
compliance
Compliance
Comments
No.(s)
Condition
Summary
issue?
Status
Number
NA)
(Yes / No)
Within 60 days of installing any
temporary boiler, the Permittee
No. 2 fuel
PS -Temp
2.1(G)(2)(d)
shall conduct a Method 9 test (6-
No
Yes
NA
Method 9
oil -fired
minute average of 24
Performance
temporary
observations) to determine the
Test Report
boiler
opacity of stack emissions in
dated
accordance with 40 CFR 60.8, 40
05/06/2008
CFR 60.45c(a)(8), and General
Condition JJ found in Section 3 of
this permit.
[2D .0524
The Permittee shall retain a record
No. 2 fuel
of the quantity of No. 2 fuel oil
Fuel Oil
oil -fired
PS -Temp
2.1(G)(2)(e)
fired at the affected boiler each
No
Yes
NA
Consumption
temporary
calendar month. [49 CFR
Report
boiler
60.48c(g)]
[2Q .0508(f)]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 36 of 54
Emission
Source
Source or
Control
Device ID
Terms and Conditions
Deviation
?
Records
Maintained
?
was
Deviation a
non-
compliance
Method(s) of
Determ ining
Compliance
Comments
Permit
Condition
Description
No.(s)
Condition
Summary
(Yes )
es / No
( Yes / No /
issue?
Status
Number
NA)
(Yes / No)
The Permittee shall retain a copy
of the fuel supplier certification for
No. 2 fuel
PS -Temp
2.1(G)(2)(f)
any No. 2 fuel oil fired at the
No
Yes
NA
Certificates of
oil -fired
affected boiler. The fuel supplier
Analysis from
temporary
certification shall include the
Oil Supplier
boiler
following information:
i. The name of the oil supplier;
ii. The sulfur content of the oil
(in % by weight); and,
iii. A statement from the oil
supplier that the oil complies
with the specification under
the definition of distillate oil
in 40 CFR 60.41 c.
F213.05241
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 37 of 54
Emission
Source
Source or
Control
Device ID
Terms and Conditions
Deviation
?
Records
Maintained
?
Was
Deviation a
non-
compliance
Method(s) of
Determining
Compliance
Comments
Permit
Condition
Description
No.(s)
Condition
Summary
Yes / No
( )
( Yes / No /
issue?
Status
Number
NA)
(Yes / No)
The Permittee shall submit the
following written notifications to
No. 2 fuel
PS -Temp
2.1(G)(2)(g)
the Regional:
No
Yes
NA
Initial
oil -fired
i. An initial notification of the
notification
temporary
date of actual initial startup of
submitted on
boiler
the boiler within 15 days of
03/13/2008;
such date;
ii. An opacity observation
Opacity
notification indicate the
observation
anticipated date that the
notification
Permittee will be conducting
submitted on
the Method 9 opacity
03/31/2008;
observation at least 30 days
prior to such date; and,
Performance
iii. Performance test results with
Test Report
the results of the Method 9
submitted on
opacity observation, shall be
05/06/2008
submitted within 30 days of
the test.
CZQ.05 08(*]-
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 38 of 54
Emission
Source
Source or
Control
Device ID
Terms and Conditions
Deviation
?
Records
Maintained
?)
was
Deviation a
non-
compliance
Method(s) of
Determining
Compliance
Comments
Permit
Condition
Description
No.(s)
Condition
Summary
Y/ No
(es
Y/ No /
(es
issue?
Status
Number
NA)
(Yes / No)
Semiannual Report. In addition to
any other reporting required by 40
No. 2 fuel
PS -Temp
2.1(G)(2)(h)
CFR 60.48c or notification
No
Yes
NA
Semi-annual
oil -fired
requirements to the EPA, the
reports to NC
temporary
Permittee is required to provide a
Division of
boiler
semiannual summary report of the
Air Quality
sulfur content of the distillate fuel
FRO
oil fired, which includes:
i. Fuel supplier certification(s)
for distillate fuel oil, as
provided in Section 2.1 G.2.d.
of this permit;
ii. A certified statement signed
by the owner or operator that
the records of fuel supplier
certification(s) submitted
represents all of the fuel fired
at the affected boiler during
the semiannual period; and,
iii. All instances of deviations
from the requirements of this
permit must be clearly
identified.
[2D .0524
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 39 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Device ID
Permit
Condition
?
?
compliance
Compliance
Comments
Description
No.(s)
Condition
Summary
(Yes / No)
(Yes / No /
issue?
Status
Number
NA)
(Yes / No)
In order to avoid applicability of
15A NCAC 2D .0530(g) for major
No. 2 fuel
PS -Temp
2.1(G)(3)(a)
sources and major modifications,
No
Yes
NA
Monthly
oil -fired
the temporary boiler (ID No. PS-
Emissions
temporary
Temp) shall discharge into the
Report
boiler
atmosphere less 40 tons of sulfur
dioxide per consecutive twelve-
month period. [2 .0317]
If emissions testing is required, the
No. 2 fuel
testing shall be performed in
oil -fired
PS -Temp
2.1(G)(3)(b)
accordance with 15A General
No
NA
NA
NA
temporary
Condition 77.
boiler
[2D .2601]
The Permittee shall keep monthly
records of fuel usage in a logbook
No. 2 fuel
PS -Temp
2.1(G)(3)(c)
(written or in electronic format), as
No
Yes
NA
Monthly
oil -fired
follows:
Emissions
temporary
i. The total quantity (in 1,000
Report and
boiler
gal) of No. 2 fuel oil fired at
Certificates of
the boiler; and,
Analysis from
ii. The fuel oil supplier
Oil Supplier
certification for any fuel oil
fired at the boiler, including
the sulfur content of the oil (in
percent by weight).
[2 .0508( ]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 40 of 54
Emission
Source
Source or
Control
Device ID
Terms and Conditions
Deviation
�
Records
Maintained
?
Was
Deviation a
non-
compliance
Method(s) of
Determining
Compliance
Comments
Permit
Condition
Description
No.(s)
Condition
Summary
Yes / No
( )
( Yes / No /
issue?
Status
Number
NA)
(Yes / No)
The Permittee shall calculate
monthly and 12-month rolling S02
No. 2 fuel
PS -Temp
2.1(G)(3)(d)
emissions from the temporary
No
Yes
NA
Monthly
oil -fired
boiler within 30 days after the end
Emissions
temporary
of each calendar month.
Report
boiler
Calculations shall be recorded in a
logbook (written or electronic
format), according to the following
formulas:
i. Calculate S02 emissions from
the previous calendar month
using the given equation.
I Sum the S02 emissions from
the boiler for the previous 12-
month period to determine the
12-month rolling emission
total.
[2 .0317
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 41 of 54
Emission
Source
Source or
Control
Device ID
Terms and Conditions
Deviation
Records
Maintained
Was
Deviation a
non-
compliance
Method(s) of
Determining
Compliance
Comments
Permit
Condition
Description
No.(s)
Condition
Summary
ry
(Yes / No)
(Yes / No /
issue?
Status
Number
NA)
(Yes / No)
The Permittee shall submit a semi-
annual summary report, acceptable
No. 2 fuel
PS -Temp
2.1(G)(3)(e)
to the Regional Air Quality
No
Yes
NA
Semi-annual
oil -fired
Supervisor, of monitoring and
reports to NC
temporary
recordkeeping activities
Division of
boiler
postmarked on or before January
Air Quality
30 of each calendar year for the
FRO
preceding six-month period
between July and December, and
July 30 of each calendar year for
the preceding six-month period
between January and June. The
report shall contain the following:
i. The monthly S02 emissions
from the boiler for the
previous 17 months;
ii. The total S02 emissions from
the boiler for each 12-month
period ending during the six
month reporting period; and,
iii. All instances of deviations
from the requirements of this
permit must be clearly
identified.
[2 .0508(f)]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 42 of 54
Terms and Conditions
Records
Was
Emission
Source or
Deviation
Maintained
Deviation a
Method(s) of
Source
Control
Device ID
Permit
Condition
?
?
non-
compliance
Determining
Compliance
Comments
Description
No.(s)
Condition
Summary
s / No
(Yes )
( Yes / No /
issue?
Status
Number
NA)
(Yes / No)
Visible emissions from this source
Emission
(ID No. SGS-A) shall not be more
source SGS-A
SentryGlas
SGS-A
2.1(11)(1)(a)
than 20 percent opacity when
No
NA
NA
NA
has no visible
Manufac-
averaged over a six -minute period.
turing
However, six -minute averaging
emissions
periods may exceed 20 percent not
more than once in any hour and
not more than four times in any
24-hour period. In no event shall
the six -minute average exceed 87
percent opacity.
[2D .0521]
If emissions testing is required, the
testing shall be performed in
SentryGlas
SGS-A
2.1(11)(1)(b)
accordance with 15A NCAC 2D
No
NA
NA
NA
Manufac-
.2601and General Condition 7I. If
turing
the results of this test are above the
limit given in Section 2.1 H.La.
above, the Permittee shall be
deemed in noncompliance with
15A NCAC 2D .0521.
[2D .2601]
SentryGlas
No monitoring/recordkeeping/
Manufac-
reporting is required for visible
taring
SGS-A
2.1(H)(1)(c)
emissions from this source. [2Q
No
NA
NA
NA
.0508(f)]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 43 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Description
Device ID
Permit
Condition
?
Yes / No
( )
?
es / No /
compliance
Compliance
Comments
No.(s)
Condition
Summary
issue?
Status
Number
NA)
(Yes / No)
Emissions of particulate matter
Polyvinyl
from the Product Collection
Fluoride
FS-B and
2.1(I)(1)(a)
Systems at the polyvinyl fluoride
No
NA
NA
AP-42
Polymer
FS-C
manufacturing facilities (Vent
calculation
Manufac-
Nos. FEP-134 & FEP-C4) shall not
taring
exceed an allowable emission rate
Facilities No.
as calculated by the given
1 & 2
equation.
[2D .0515]
If emissions testing is required, the
Polyvinyl
testing shall be performed in
Fluoride
FS-B and
2.1(I)(1)(b)
accordance with General
No
NA
NA
NA
Polymer
FS-C
Condition JJ.
Manufac-
[2D .2601]
turing
Facilities No.
1&2
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 44 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Description
Device ID
Permit
Condition
Yes / No
( )
( Yes / No /
compliance
Compliance
Comments
No.(s)
Condition
Summary
issue?
Status
Number
NA)
(Yes / No)
The Permittee shall maintain
production records such that the
Polyvinyl
FS-B and
2.1(I)(1)(c)
process rates "P" in tons per hour,
No
Yes
NA
PVF
Fluoride
FS-C
as specified by the formulas
Production
Polymer
contained above (or the formulas
Records
Manufac-
contained in 15A NCAC 2D
turing
.0515) can be derived, and shall
Facilities No.
make these records available to a
1 & 2
DAQ authorized representative
upon request. The Permittee shall
be deemed in noncompliance with
15A NCAC 2D .0515 if the
production records are not
maintained.[2 .0508(f)]
The Permittee shall submit a
summary report of monitoring and
Polyvinyl
FS-B and
2.1(I)(1)(d)
recordkeeping activities
No
Yes
NA
Semi-annual
Fluoride
FS-C
postmarked on or before January
reports to NC
Polymer
30 of each calendar year for the
Division of
Manufac-
preceding six-month period
Air Quality
turing
between July and December and
FRO
Facilities No.
July 30 of each calendar year for
1 & 2
the preceding six-month period
between January and June. All
instances of deviations from the
requirements of this permit must
be clearly identified.
[2 oso8(t)I
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 45 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Description
Device ID
Permit
Condition
?
Yes / No
( )
?
( Yes / No /
compliance
Compliance
Comments
No.(s)
Condition
Summary
issue?
Status
Number
NA)
(Yes / No)
Visible emissions from the Product
Collection Systems at the
Polyvinyl
FS-B and
2.1(I)(2)(a)
polyvinyl fluoride manufacturing
No
Yes
NA
Monthly
Fluoride
FS-C
facilities (Vent Nos. FEP-B4 &
visual
Polymer
FEP-C4) shall not be more than 20
observations
Manufac-
percent opacity when averaged
turing
over a six -minute period.
Facilities No.
However, six -minute averaging
1 & 2
periods may exceed 20 percent not
more than once in any hour and
not more than four times in any
24-hour period. In no event shall
the six -minute average exceed 87 .
percent opacity. [21) .0521]
If emissions testing is required, the
testing shall be performed in
Polyvinyl
FS-B and
2.1(1)(2)(b)
accordance with 15A NCAC 2D
No
NA
NA
NA
Fluoride
FS-C
.2601 and General Condition JJ.
Polymer
If the results of this test are above
Manufac-
the limit given in Section 2.1 1.2.a.
turing
above, the Permittee shall be
Facilities No.
deemed in noncompliance with
•
1 & 2
15A NCAC 2D .0521.
[2D .2601]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 46 of 54
Emission
Source
Source or
Control
Device ID
Terms and Conditions
Deviation
?
Records
Maintained
Was
Deviation a
non-
compliance
Method(s) of
Determining
Compliance
Comments
Permit
Condition
Description
No.(s)
Condition
Summary
�'
(Yes / No)
(Yes / No /
issue?
Status
Number
NA)
(Yes / No)
To assure compliance, once a
month the Permittee shall observe
Polyvinyl
FS-B and
2.1(I)(2)(c)
the emission point of the affected
No
Yes
NA
Monthly
Fluoride
FS-C
source for any visible emissions
visual
Polymer
above normal. The monthly
observation
Manufac-
observation must be made for each
record
turing
month of the calendar year period
Facilities No.
to ensure compliance with this
1 & 2
requirement. If visible emissions
from this source are observed to be
above normal, the Permittee shall
either:
i. Take appropriate action to
correct the above -normal
emissions as soon as
practicable and within the
monitoring period, or
ii. Demonstrate that the percent
opacity from the emission
points of the emission source
is below the limit given in
Section 2.1 I.2.a. above.
[2Q.0508( f)]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 47 of 54
Emission
Source
Source or
Control
Device ID
Terms and Conditions
Deviation
Records
Maintained
Was
Deviation a
non-
compliance
Method(s) of
Determining
Compliance
Comments
Permit
Condition
Description
No.(s)
Condition
Summary
es / No
(Yes )
( Yes / No /
issue?
Status
Number
NA)
(Yes / No)
The results of the monitoring shall
be maintained in a logbook
Polyvinyl
FS-B and
2.1(I)(2)(d)
(written or electronic format) on-
No
Yes
NA
Monthly
Fluoride
FS-C
site and made available to an
visual
Polymer
authorized representative upon
observation
Manufac-
request. The logbook shall record
record
turing
the following:
Facilities No.
i. The date and time of each
1 & 2
recorded action;
ii. The results of each
observation and/or test noting
those sources with emissions
that were observed to be in
noncompliance along with any
corrective actions taken to
reduce visible emissions; and
iii. The results of any corrective
actions performed.
2 .0508(f)]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 48 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Device ID
Permit
Condition
?
?
compliance
Compliance
Comments
Description
No.(s)
Condition
Summary
ry
(Yes / No)
(Yes / No I
issue?
Status
Number
NA)
(Yes / No)
The Permittee shall submit a
summary report of the
Polyvinyl
FS-B and
2.1(1)(2)(e)
observations postmarked on or
No
Yes
NA
Semi-annual
Fluoride
FS-C
before January 30 of each calendar
reports to NC
Polymer
year for the preceding six-month
Division of
Manufac-
period between July and
Air Quality
turing
December and July 30 of each
FRO
Facilities No.
calendar year for the preceding
1 & 2
six-month period between January
and June. All instances of
deviations from the requirements
of this permit must be clearly
identified.
[2 .0508(f)]
In order to avoid applicability of
Polyvinyl
this regulation, the Polyvinyl
The PVF
Fluoride
FS-B and
2.1(I)(4)(a)
Fluoride (PVF) Manufacturing
No
NA
NA
NA
Manufac-
Polymer
FS-C
Facility No. 1 and No. 2 (ID Nos.
turing Facility
Manufac-
FS-B and FL-C) shall discharge
No. 2
tuning
into the atmosphere less than 40
(FS-C) has
Facilities No.
tons of VOCs per consecutive 12-
not started up
1 & 2
month period.
as of 12/31/08
[2Q .0317]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 49 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Description
Device ID
Permit
Condition
?
Yes / No
( )
�
( Yes / No /
compliance
Compliance
Comments
No.(s)
Condition
Summary
issue7
Status
Number
NA)
(Yes / No)
Polyvinyl
If emissions testing is required, the
Fluoride
Permittee shall perform such
Polymer
FS-B and
2.1(I)(4)(b)
testing in accordance with General
No
NA
NA
NA
Manufac-
FS-C
Condition JJ.
[2D .2601]
turing
Facilities No.
1&2
To demonstrate compliance with
the limit provided in Section 2.1
Polyvinyl
FS-B and
2.1(I)(4)(c)
I.4.a., each calendar month
No
NA
NA
NA
The PVF
Fluoride
FS-C
ollowin the initial start-up of the
Manufac-
Polymer
PVF Manufacturing Facility No. 2
turing Facility
Manufac-
(ID No. FS-C), the Permittee shall
No. 2
turing
create and retain production
(FS-C) has
Facilities No.
records and estimate associated
not started up
1 & 2
VOC emissions as specified.
as of 12/31/08
[2Q .0508(f)]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 50 of 54
Emission
Source or
Terms and Conditions
Deviation
Records
Maintained
Was
Deviation a
Method(s) of
Permit
Condition
Source
Control
Device ID
?
?
non-
compliance
Determining
Compliance
Comments
Description
No.(s)
Condition
Summary
Yes / No
( )
( Yes / No /
issue?
Status
Number
NA)
(Yes / No)
The Permittee shall submit a semi-
annual summary report of
Polyvinyl
FS-B and
2.1(I)(4)(d)
monitoring and recordkeeping
No
NA
NA
NA
The PVF
Fluoride
FS-C
activities. The report shall contain
Manufac-
Polymer
the following:
turing Facility
Manufac-
i. The monthly VOC emissions
No. 2
turing
from two affected polyvinyl
(FS-C) has
Facilities No.
fluoride manufacturing
not started up
1 & 2
operations for the previous 17
as of 12/31/08
calendar months;
ii. The 12-month rolling VOC
emissions for each 12-month
period ending during the
reporting period; and,
iii. All instances of deviations
from the requirements of this
permit must be clearly
identified.
[2 .osos(t)1
In order to avoid applicability of
No. 2/No. 6
this regulation, the affected boilers
fuel oil -fired
PS-1, PS-
2.2(A)(1)(a)
(ID Nos. PS-1, PS-2, and PS-
No
Yes
NA
Monthly
boilers
2, and
Temp) shall discharge into the
Emissions
and
PS -Temp
atmosphere less than 702.5 tons of
Report
No. 2 fuel
S02 per consecutive 12-month
oil -fired
period.
boiler
[2Q .0317]
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 51 of 54
Source or
Terms and Conditions
Records
Was
Deviation a
Method(s) of
Emission
Control
Deviation
Maintained
non-
Determining
Source
Description
Device ID
Permit
Condition
?
(Yes / No)
?
(Yes / No /
compliance
Compliance
Comments
No.(s)
Condition
Summary
�1'
NA)
issue?
Status
Number
(Yes / No)
If emissions testing is required, the
No. 2/No. 6
Permittee shall perform such
fuel oil -fired
PS-1, PS-
2.2(A)(1)(b)
testing in accordance with General
No
NA
NA
NA
boilers
2, and
Condition JJ.
and
PS -Temp
[2D .2601]
No. 2 fuel
oil -fired
boiler
The Permittee shall keep monthly
No. 2/No. 6
records of fuel usage in a logbook
fuel oil -fired
PS-1, PS-
2.2(A)(1)(c)
(written or in electronic format), as
No
Yes
NA
Fuel
boilers
2, and
follows:
Consumption
and
PS -Temp
i. The total quantity (in 1,000
Records and
No. 2 fuel
gal) of No. 2 and No. 6 fuel
Certificates of
oil -fired
oil fired at the affected
Analysis from
boiler
boilers; and,
Oil Supplier
ii. The fuel oil supplier
certification for any fuel oil
fired at the affected boilers,
including the sulfur content of
the oil (in percent by weight).
[2 .0508(
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 52 of 54
Emission
Source
Source or
Control
Device ID
Terms and Conditions
Deviation
?
Records
Maintained
?
Was
Deviation a
non-
compliance
Method(s) of
Determining
Compliance
Comments
Permit
Condition
Description
No. s
()
Condition
Summary(
Yes / No )
es / No /
issue?
Status
Number
NA)
(Yes / No)
The Permittee shall calculate
No. 2/No. 6
monthly and 12-month rolling S02
fuel oil -fired
PS-1, PS-
2.2(A)(1)(d)
emissions from the affected boilers
No
Yes
NA
Emissions
boilers
2, and
within 30 days after the end of
determined
and
PS -Temp
each calendar month. Calculations
monthly using
No. 2 fuel
shall be recorded in a logbook
AP-42 factors
oil -fired
(written or electronic format),
boiler
according to the following
formulas:
i. Calculate S02 emissions from
the previous calendar month
using the specified equation.
ii. Sum the S02 emissions from
the affected boilers for the
previous 12-month period to
determine the 12-month
rolling emission total.
[2 .0317]
0
m
p'
C�
n
I
0
0
0
w
ch
m
m
w
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 53 of 54
Emission
Source
Source or
Control
Device ID
Terms and Conditions
Deviation
?
Records
Maintained
?
Was
Deviation a
non-
compliance
Method(s) of
Determining
Compliance
Comments
Permit
Condition
Description
No.(s)
Condition
Summary
Y/ No
(es )
( Yes / No /
issue?
Status
Number
NA)
(Yes / No)
The Permittee shall submit a semi -
No. 2/No. 6
annual summary report of
fuel oil -fired
PS-1, PS-
2.2(A)(1)(e)
monitoring and recordkeeping
No
Yes
NA
Semi-annual
boilers
2, and
activities postmarked on or before
reports to NC
and
PS -Temp
January 30 of each calendar year
Division of
No. 2 fuel
for the preceding six-month period
Air Quality
oil -fired
between July and December, and
FRO
boiler
July 30 of each calendar year for
the preceding six-month period
between January and June. The
report shall contain the following:
i. The monthly S02 emissions
from two affected boilers for
the previous 17 calendar
months;
ii. The 12-month rolling SOz
emissions for each 12-month
period ending during the
reporting period; and,
iii. All instances of deviations
from the requirements of this
permit must be clearly
identified.
2 .0508(f)
Permit 03735T33
TITLE V AIR PERMIT COMPLIANCE SUMMARY REPORT
For Calendar Year 2008
Page 54 of 54
Emission
Source
Source or
Control
Device ID
Terms and Conditions
Deviation
?
Records
Maintained
?
Was
Deviation a
non-
compliance
Method(s) of
Determining
Compliance
Comments
Permit
Condition
Description
No.(s)
Condition
Summary
Yes / No
( )
( Yes / No /
issue?
Status
Number
NA)
(Yes / No)
40 CFR Part 68 "ACCIDENTAL
RELEASE PREVENTION
All sources
All
2.2(B)(4)
REQUIREMENTS: RISK
No
Yes
NA
Risk
MANAGEMENT PROGRAMS
Management
UNDER THE CLEAN AIR ACT,
Plan submittal
SECTION 112(r)" - The Permittee
shall comply with all applicable
requirements in accordance with
40 CFR Part 68 including
submitting a Risk Management
plan to EPA pursuant to 40 CFR
Part 68.150 prior to June 21, 1999
or as specified in 40 CFR Part
68.10.
40 CFR Part 68]