HomeMy WebLinkAboutDEQ-CFW_00060891NCDENR
North Carolina Department of Environment and
Beverly Eaves perdue
Governor
Karen Wrigley, Plant Manager
Dupont — Fayetteville. Works
E.I. DuPont de Nemours & Company
22828 NC Hwy 87 West
Fayetteville, NC 28306-7332
Division of Water Qualify
Coleen H. Sullins
Director
July 2, 2009
Subject: Compliance Evaluation Inspection (CEI)
DuPont — Fayetteville Works
NPDES Permit No. NC0003573
Bladen County
Dear Ms. Wrigley:
Natural Resources
Dee Freeman
Secretary
Enclosed you will find a copy of the Compliance Evaluation Inspection (CEI) report for the
inspection conducted on June 25, 2009. As part of the inspection a tour of the Wastewater
Treatment Plant was conducted. All observations are in Section D. Summary of
Findings/Comments of this inspection report.
You are commended for the continued success of the wastewater treatment plant. We
appreciate the time and professional courtesy that was extended by your staff during the
inspection. If you have any questions or comments concerning this report or require
clarification on part(s) of this report, please feel free to contact me at (910) 433-3312.
Sincerely,
Dale Lopez
Environmental Specialist
Enclosures: EPA Water Compliance Inspection Report
Facility Site Review (checklist)
Regional Field Inspectors Check List for Field Parameters
cc: Marlene Page, Area Superintendent, DuPont — Fayetteville Works
Mike Johnson, Environmental Manager, DuPont — Fayetteville Works
Robert Geddie, ORC, DuPont — Fayetteville Works
FRO Files
Central Files
225 Green St., Suite 714, Fayetteville, NC 28301-5043
Phone: 910-033-3300 i FAX: 91OA86-0707 d Customer Service: 1-877-623-6748
Internet: www.ncwaterquality.org
An Equal Opporiurity ! Affirmative Action Employer
0[Le.
l Noi, - CarolT_l"1 a
NalialfirlIff
DEQ-CFW 00060891
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 iNI 2 L 31 NC0003573 111 121 09/06/25 1 17 181 CI 191sI 201 I
1 f t
Remarks
211111111IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII116
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------- —---------------- Reserved --------------- ------
671 2.0 169 701 41 71 I I 721 N I 73 W 74 751 1 1 1 1 1 1 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
Dupont Fayetteville Works
10:30 AM 09/06/25
07/07/01
Exit Time/Date
Permit Expiration Date
22828 NC Highway 87 West
Fayetteville NC 283067332
02:00 PM 09/06/25
11/10/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Robert J Geddie/ORC/910-678-1219/
Name, Address of Responsible Officialfritle/Phone and Fax Number
Michael Johnson,22828 NC Highway 87 West Fayetteville NC Contacted
283067332//910-678=1155/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Facility Site Review Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) an grt�ure(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Dale Lopez l \ FRO WQ//910-433-3300 Ext.712/ t %�
Signature of Ma Bement Q A Re ewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page # 1
DEQ-CFW 00060892
NPDES yrtmo/day Inspection Type
3I NC0003573 I11 12I 09/06/25 117 18i CI
(cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Consistant with last year's Compliance Inspection, this complex wastewater treatment facility appeared to
be very well operated and maintained, and continues to maintain a very high standard of wastewater
treatment. Please continue to keep up the good work! The following were noted during this inspection: 1)
*1 Clarifier was down because of low flow to the VWVf'P (approximately 50% flow) and routine maintenance,
2) Nafion was temporily down, 3) the retention tank (emergency spill tank) was inspected in April 2009 and
repairs performed on cracks, 4) in the future, the sludge holding tank will be repainted on the inside.
Page # 2
DEQ-CFW 00060893
Permit: NC0003573
Inspection Date: 06/25/2009
Owner - Facility: Dupont Fayetteville Works
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ■ Q Q Q
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH,- DO, Sludge ■ fl p
Judge, and other that are applicable? _ --_ -- _ - --
Comment:
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new application?
n
n
■
n
Is the facility as described in the permit?
■
n
n
n
# Are there any special conditions for the permit?
■
n
n
n
Is access to the plant site restricted to the general public?
■
n
n
n
Is the inspector granted access to all areas for inspection?
■
n
❑
Comment:
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
■
Cl
0
0
Is all required information readily available, complete and current?
■
n
n
n
Are all records maintained for 3 years (lab. reg. required 5 years)?
■
n
n
n
Are analytical results consistent with data reported on DMRs?
■
n
n
0
Is the chain -of -custody complete?
■
❑
❑
n
Dates, times and location..of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
■
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
■
Q
Q
Q
Has the facility submitted its annual compliance report to users and DWQ?
■
Q
❑
Q
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift?
n
n
■
Is the ORC visitation log available and current?
■
0
❑
Q
Is the ORC certified at grade equal to or higher than the facility classification?
■
n
n
Q
Is the backup operator certified at one grade less or greater than the facility classification?
■
n
n
n
Is a copy of the current NPDES permit available on site?
■
Page # 3
DEQ-CFW 00060894
Permit: NC0003573 Owner - Facility: Dupont Fayetteville Works
Inspection Date: 06/25/2009 Inspection Type: Compliance Evaluation
Record Keeping
Yes
No
NA
NE
Facility has copy of previous year's Annual Report on file for review?
n
n
n
■
Comment:
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
■
n
00
Are the receiving water free of foam other than trace amounts and other debris?
■
n
n
n
If effluent (diffuser pipes are required) are they operating properly?
n
n
■
n
Comment:
Flow Measurement - Effluent
Yes
No
NA
NE
# Is flow meter used for reporting?
■
n
00
Is flow meter calibrated annually?
■
n
n
n
Is the flow meter operational?
■
n
❑
n
(If units are separated) Does the chart recorder match the flow meter?
n
n
n
■
Comment:
Equalization Basins
Yes
No
NA
NE
Is the basin aerated?
n
n
n
■
Is the basin free of bypass lines or structures to the natural environment?
i
n
n
n
Is the basin free of excessive grease?
n
n
n
■
Are all pumps present?
■
n
n
n
Are all pumps operable?
■
n
n
n
Are float controls operable?
0
n
n
■
Are audible and visual alarms operable?
■
n
n
n
# Is basin size/volume adequate?
■
❑
n
Comment:
Secondary Clarifier
Yes
No
NA
NE
Is the clarifier free of black and odorous wastewater?
■
n
n
n
Is the site free of excessive buildup of solids in center well of circular clarifier?
■
n
n
n
Are weirs level?
■
n
n
n
Is the site free of weir blockage?
■
n
n
n
Is the site free of evidence of short-circuiting?
■
n
n
n
Is scum removal adequate?
■
n
n
n
Page # 4
DEQ-CFW 00060895
Permit: NC0003573
Inspection Date: 06/25/2009
Owner - Facility: Dupont Fayetteville Works
Inspection Type: Compliance Evaluation
Secondary Clarifier
Yes
No
NA
NE
Is the site free of excessive floating sludge?
■
❑
❑
❑
Is the drive unit operational?
■
❑
❑
n
Is the return rate acceptable (low turbulence)?
■
❑
❑
0
Is the overflow clear of excessive solids/pin floc?
■
n
❑
n
Is the sludge blanket level acceptable? (Approximately % of the sidewall depth)
■
❑
❑
❑
Comment:
Aeration Basins
Yes
No
NA
NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
❑
❑
❑
■
Are surface aerators and mixers operational?
❑
❑
■
❑
Are the diffusers operational?
■
❑
❑
❑
Is the foam the proper color for the treatment process?
n
❑
❑
■
Does the foam cover less than 25% of the basin's surface?
❑
❑
❑
■
Is the DO level acceptable?
■
❑
Q
❑
Is the DO level acceptable?(1.0 to 3.0 mg/I)
n
❑
0
■
Comment:
Laboratory
Yes
No
NA
NE
Are field parameters performed by certified personnel or laboratory?
■
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
■
❑
❑
❑
# Is the facility using a contract lab?
■
❑
❑
n
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)?
❑
❑
■
0
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
■
0
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
■
❑
Comment:
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
■
❑
❑
❑
Is sample collected below all treatment units?
■
❑
❑
❑
Is proper volume collected?
■
❑
❑
❑
Is the tubing clean?
■
0
n
❑
Page # 5
DEQ-CFW 00060896
i
Permit: NC0003573 Owner - Facility: Dupont Fayetteville Works
Inspection Date: 06/25/2009 Inspection Type: Compliance Evaluation
Effluent Sampling
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type representative)?
Comment:
Yes No NA NE
■on❑
moon
Page # 6
DEQ-CFW 00060897
Regional Field Inspectors Check List for Field Parameters
e
Name of site to be Inspected: DuPont Date: 06/ 09
Field certification # (if applicable): 5105 Inspector: Dale L
NPDES #: NC 0003573 Region: FRO
I. Circle the parameter or parameters performed at this site.
Residual Chlorine, Settleable Solids, �H, DO, Conductivity, em erature
11. Instrumentation:
A. Does the facility have the equipment necessary to analyze field parameters as circled above?
1. A pH meter Fisher Accu net 50 es No
2. A Residual Chlorine meter Yes No
3.
DO meter
Yes
No
4.
A Cone for settleable solids
Yes
No
5.
A thermometer or meter that measures temperature.
es
No
6.
Conductivity meter
Yes
No
III. Calibration/Analysis:
1. Is the pH meter calibrated with 2 buffers and
checked with a third buffer each day of use? Ye7s No
2. For Total Residual Chlorine, is a check standard
analyzed each day of use? Yes No
3. Is the air calibration of the DO meter performed
each day of use? Yes No
4. For Settleable Solids, is 1 liter of sample
settled for 1 hour? Yes No
5. Is the temperature measuring device calibrated
annually against a certified thermometer? 01/23/2009 es No
6. For Conductivity, is a calibration standard
analyzed each day of use? Yes No
DEQ-CFW 00060898
IV. Documentation:
1.
Is the date and time that the sample was collected documented?
es
No
2.
Is the sample site documented?
Ye7s
No
3.
Is the sample collector documented?
es
No
4.
Is the analysis date and time documented?
es
No
5.
Did the analyst sign the documentation?
es
No
6.
Is record of calibration documented?
es
No
7. For Settleable Solids, is sample volume and
1 hour time settling time documented? Yes No
8. For Temperature, is the annual calibration of
the measuring device documented? es No
Comments. -
pH 4 Buffer expiration date was January 2010
pH 7 Buffer expiration date was April 2010
pH 10 Buffer expiration date was January 2010
Please submit a copy of this completed form to the Laboratory Certification Program.
DWQ Lab Certification
Chemistry Lab
Courier # 52-01-01
FIELD INSPECTOR CHECKLIST REV. 04/23/2002
DEQ-CFW 00060899