HomeMy WebLinkAboutDEQ-CFW_00060875nrr"".�rrix A,
NCDENR
North Carolina Department of Environment and Natural Resources
Beverly Eaves Perdue
Governor
Karen Wrigley, Plant Manager
Dupont -Fayetteville Works
E I DuPont de Nemours and Company
22828 NC Highway 87 West
Fayetteville NC 283067332
Division of Water Quality
Coleen H. Sullins
Director
June 15, 2010
SUBJECT: June 4, 2010 Compliance Evaluation Inspection
E I DuPont de Nemours and Company
Dupont Fayetteville Works
Permit No: NC0003573
Bladen County
Dear Ms. Wrigley:
Dee Freeman
Secretary
Enclosed please find a copy of the Compliance Evaluation Inspection form from the inspection conducted on
June 4, 2010. The Compliance Evaluation Inspection was conducted by Mark Brantley, Environmental Chemist,
of the Fayetteville Regional Office. The cooperation of Mr. Jamie Lewis, Facility ORC, was greatly appreciated.
The facility was found to be in Compliance with permit NC0003573. As a reminder, preservation of the Waters of
the State can only be achieved through consistent NPDES Permit compliance.
Comments
• Facility was clean and neat in appearance at the time of the inspection.
• The November 2009 DMR and laboratory records were reviewed and appeared to be in order.
Some rust was noted on both clarifiers. Please consider painting these structures as soon as possible
because taking preventive maintenance steps now may avoid costly repairs in the future.
Please refer to the enclosed inspection report for additional observations and comments. If you or your staff have
any questions, please call me at 910-433-3327.
Sincerely,
BrantleyMark
Environmental Chemist
Surface Water Protection Section
Fayetteville Regional Office
cc: Jamie Ray Lewis, ORC
Central Files
Fayetteville Files, ;kmb;
North Carolina Division of Water Quality/Aquifer Protection Section 225 Green St./ Suite 714 Fayetteville, NC 28301 Phone (910) 433-3300
FAX (910) 486-0707 Internet: h2o.enr.state.nc.us Customer Service 1-877-623-6748
NorthCarolina
Naturally
An Equal Opportunity/Affirmative Action Employer - 50% Recycled/10% Post Consumer Paper
DEQ-CFW 00060875
United States Environmental Protection Agency
Form Approved.
Washington, D.C. 20460
EPA
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/molday Inspection Type Inspector Fac Type
1 I NI 2 15I 31 N00003573 Ill 121 10/06/04 117 18I CI 19I gI 20II)
Remarks
21111111111111111111111111111111111111111IIIIIII16
Inspection Work Days Facility Self -Monitoring Evaluation Rating 61 QA --------------------------- Reserved ----------------------
67) 169 70 13 I 711 NJ 72 I N I 73' I' 74 751 I I I I I I 180
L
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
09:30 AM 10/06/04
07/07/01
Dupont Fayetteville Works
Exit Time/Date
Permit Expiration Date
22828 NC Highway 87 West
Fayetteville NC 283067332
12.30 PM 10/06/04
11/10/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Jamie Ray Lewis/ORC/910-678-1143/
Name, Address of Responsible Official/Title/Phone and Fax Number
Michael Johnson,22828 NC Highway 87 West Fayetteville NC Contacted
283067332//910-678-1155/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenance . Records/Reports
Self -Monitoring Program N Sludge Handling Disposal Facility Site Review
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Mark Brantley FRO WQ//910-433-3300 Ext.727/
,00;;�W G /5- -/v
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
// )j — / U
Belinda S Henson FRO WQ//910-433-3300 Ext.726/ t¢ ' i `7
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page # 1
DEQ-CFW 00060876
NPDES yr/molday Inspection Type 1
3I. NC0003573 I11 12I 10/06/04 I17 18ICI
Section D: Summary of (Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Facility was clean and neat in appearance at the time of the inspection.
The November 2009 DMR and laboratory records were reviewed and appeared to be in order.
Some rust was noted on both clarifiers. Please consider painting these structures as soon as possible
because taking preventive maintenance steps now may avoid costly repairs in the future.
Page # 2
DEQ-CFW 00060877
Permit: NC0003573
Inspection Date: 06/04/2010
Owner - Facility: Dupont Fayetteville Works
Inspection Type: Compliance Evaluation
Operations & Maintenance
Yes
No
NA
NE
Is the plant generally clean with acceptable housekeeping?
■
n
❑
n
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge ■
n
n
n
Judge, and other that are applicable?
Comment:
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new application?
n
n
■
n
Is the facility as described in the permit?
■
n
n
n
# Are there any special conditions for the permit?
o
o
■
In
Is access to the plant site restricted to the general public?
■
n
n
n
Is the inspector granted access to all areas for inspection?
■
n
n
n
Comment:
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
■
n
n
n
Is all required information readily available, complete and current?
■
n
n
n
Are all records maintained for 3 years (lab. reg. required 5 years)?
■
n
n
n
Are analytical results consistent with data reported on DMRs?
■
n
n
n
Is the chain -of -custody complete?
■
n
n
n
Dates, times and location of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
■
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
■
n
n
n
Has the facility submitted its annual compliance report to users and DWQ?
n
n
n
■
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift?
■
n
n
n
Is the ORC visitation log available and current?
■
n
n
n
Is the ORC certified at grade equal to or higher than the facility classification?
■
n
n
n
Is the backup operator certified at one grade less or greater than the facility classification?
■
n
n
n
Is a copy of the current NPDES permit available on site?
■
n
n
n
Page # 3
DEQ-CFW 00060878
` t Permit: NC0003573 Owner - Facility: Dupont Fayetteville Works
Inspection Date: 06/04/2010 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Facility has copy of previous year's Annual Report on file for review? n n ❑ ■
Comment:
Flow Measurement - Effluent
Yes
NO
NA
Nt
# Is flow meter used for reporting?
■
n
n
n
Is flow meter calibrated annually?
■
n
n
n
Is the flow meter operational?
■
n
n
n
(If units are separated) Does the chart recorder match the flow meter?
n
n
n
■
Comment: Flow meter was last calibrated by ISI Instrumentation Services on 2-19-10.
Solids Handling Equipment
Yes
No
NA
NE
Is the equipment operational?
■
n
n
n
Is the chemical feed equipment operational?
■
n
n
n
Is storage adequate?
■
n
n
n
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
n
n
Cl
■
Is the site free of sludge buildup on belts and/or rollers of filter press?
❑
n
n
M
Is the site free of excessive moisture in belt filter press sludge cake?
n
❑
n
■
The facility has an approved sludge management plan?
n
n
n
■
Comment: DAF unit and associated equipment was not in operation at the time of the
inspection. Sludge is disposed of at the Sampson County landfill.
Chemical Feed
Yes
No
NA
NE
Is containment adequate?
■
n
n
n
Is storage adequate?
■
n
n
n
Are backup pumps available?
■
n
n
n
Is the site free of excessive leaking?
■
n
n
n
Comment:
qualization Basins
Yes
No
NA
NE
Is the basin aerated?
■
n
n
n
Is the basin free of bypass lines or structures to the natural environment?
■
n
n
n
Is the basin free of excessive grease?
■
n
n
n
Are all pumps present?
■
n
n
n
Are all pumps operable?
■
n
n
n
Page # 4
DEQ-CFW 00060879
Permit: NC0003573 Owner - Facility: Dupont Fayetteville Works E
Inspection Date: 06/04/2010 Inspection Type: Compliance Evaluation
n
Equalization Basins
Yes
No
NA
NE
Are float controls operable?
D
D
■
D
Are audible and visual alarms operable?
■
D
D
D
# Is basin size/volume adequate?
■
❑
❑
❑
Comment:
Secondary Clarifier
Yes
No
NA
NE
Is the clarifier free of black and odorous wastewater?
■
D
D
D
Is the site free of .excessive buildup of solids in center well of circular clarifier?
■
D
D
D
Are weirs level?
■
D
D
D
Is the site free of weir blockage?
■
D
D
D
Is the site free of evidence of short-circuiting?
■
D
D
D
Is scum removal adequate?
■
D
D
D
Is the site free of excessive floating sludge?
■
D
D
D
Is the drive unit operational?
■
D
D
D
Is the return rate acceptable (low turbulence)?
■
❑
D
D
Is the overflow clear of excessive solids/pin floc?
■
❑
D
D
Is the sludge blanket level acceptable? (Approximately '/< of the sidewall depth)
■
n
n
D
Comment:
Aeration Basins
Yes
No
NA
NE
Mode of operation
Ext. Air
Type of aeration system
Diffused
Is the basin free of dead spots?
■
D
D
Cl
Are surface aerators and mixers operational?
❑
D
■
D
Are the diffusers operational?
■
D
D
D
Is the foam the proper color for the treatment process?
■
D
D
D
Does the foam cover less than 25% of the basin's surface?
■
Q
D
Is the DO level acceptable?
■
❑
0
Is the DO level acceptable?(1.0 to 3.0 mg/1)
■
D
D
D
Comment:
Influent Sampling
Yes
No
NA
NE
# Is composite sampling flow proportional?
D
D
■
D
Page # 5
DEQ-CFW 00060880
' r Permit: NC0003573 Owner - Facility: Dupont Fayetteville Works
Inspection Date: 06/04/2010 Inspection Type: Compliance Evaluation
Influent Sampling
Yes
No
NA
NE
Is sample collected above side streams?
■
n
n
n
Is proper volume collected?
■
n
n
n
Is the tubing clean?
■
n
Q
n
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)?
■
n
n
n
Is sampling performed according to the permit?
■
n
n
n
Comment:
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
■
n
n
n
Is sample collected below all treatment units?
■
n
n
n
Is proper volume collected?
■
❑
Q
n
Is the tubing clean?
■
n
n
n
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)?
■
n
n
n
Is the facility sampling performed as required by the permit (frequency, sampling type representative)?
■
n
n
n
Comment:
Upstream / Downstream Sampling
Yes
No
NA
NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and sampling location)? n n n 0
Comment: Facility is a member of the Middle Cape Fear River Basin Association.
Page # 6
DEQ-CFW 00060881