JAMES A. MCFARLAND, JR. PRESIDENT
MOVIES ONE, LLC
POST OFFICE Box 2277
WILMINGTON, NORTH CAROLINA 28402
Subject: Permit No. WQ0029952
Hampstead Lands WWTF
Wastewater Treatment and
Reclaimed Water Utilization System
Pender County
Dear Mr. McFarland:
In accordance with your permit application received March 7, 2006, and subsequent additional
information received April 4, 2006, April 25, 2006 and May 16, 2006, we are forwarding herewith Permit
Number. WQ0029952 dated June 19, 2006, to Hampstead 504 LLC and Movies One, LLC for the
construction and operation of the subject wastewater treatment and reclaimed water utilization system.
This permit shall be effective from the date of issuance until May 31, 2011, and shall be subject to
the conditions and limitations as specified therein. Please pay particular attention to the monitoring
requirements in this permit. Failure to establish an adequate system for collecting and maintaining the
required operational information will result in future compliance problems.
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the
right to request an adjudicatory hearing upon written request within thirty (30) days following receipt of
this permit. This request must be in the form of a written petition, conforming to Chapter 150B of the
North Carolina General Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service
Center, Raleigh, NC 27699-6714. Unless such demands are made this permit shall be final and binding.
One set of approved plans and specifications is being forwarded to you. If you need additional
information concerning this matter, please contact Nathaniel Thornbu at(919)715-6160.
Sincere ,
r
1Alan W. Klimek, P.E.
CC'. Pender County Health Department
Wilmington Regional Office, Aquifer Protection Section
Hampstead 504 LLC — 91-11 Queens Blvd. #1B, Rego Park, NY 11374
W. Gus Simmons, PE — Cavanaugh & Associates, PA
Douglas N. Haggett, PE — Haggett Engineering Associates, Inc.
Technical Assistance and Certification Unit
Aquifer Protection Central Files
LAU Files
Noon hCarolina
Aaturally
Aquifer Protection Section 1636 Maii Service Center Raleigh, NC 27699-1636 Phone (919) 733-3221 Customer Service
http:/Amvv.ncwaterquality.arg 2728 Capital Boulevard Raleigh, NC 27604 Fax (919) 715-0588 1-877-623-6748
Fax (919) 715-6048
An Equal Opportunity/Affirmative Action Employer— 50% Recycled/10%Post Consumer Paper
L.,
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
RALEIGH
WASTEWATER TREATMENT AND RECLAIMED WATER UTILIZATION PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as
amended, and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
Hampstead 504 LLC & Movies One, LLC
Pender County
FOR THE
construction and operation of an 84,600 gallon per day (GPD) wastewater treatment and reclaimed water
utilization system consisting of:
a manually cleaned bar screen with I inch spacings; a flow splitter box; one (1) 25,070 gallon aerated
flow equalization basin with two (2) 100 gallon per minute (GPM) pumps, audible/visual high water
alarms and one (1) 70 cubic feet per minute (CFM) blower; two (2) 50,470 gallon aeration basins with
two (2) 104 GPM anoxic recycle pumps and three (3) 245 CFM main plant blowers; two (2) 5,200 gallon
anoxic basins with mixers; two (2) 8,350 gallon clarifiers with two (2) 104 GPM waste/return sludge
pumps; two (2) tertiary filters with a total surface area of 69 square feet (ft) and an air scour blower unit;
a 5,632 gallon clearwell with two (2) 517 GPM backwash pumps; a 5,744 gallon mudwell with two (2) 90
GPM wasting pumps; two (2) 15,000 gallon aerated sludge holding basins with two (2) 104 GPM decant
pumps; two (2) tablet chlorinators; a 2,606 gallon chlorine contact basin; an effluent flow meter; a
turbidimeter; a permanent auxiliary power generator; an effluent pump station with two (2) 69 GPM
pumps and audible/visual high water alarms; a five-day upset pond pump station with two (2) 69 GPM
pumps and audible/visual high water alarms; a synthetically lined 428,000 gallon 5 -day upset pond with a
pump station containing two (2) 16 GPM return pumps and audible/visual high water alarms; a 1.27
million gallon synthetically lined wet weather storage pond providing approximately 15 days worth of
storage with a irrigation pump station with two (2) 100 GPM dosing pumps, audible/visual high water
alarms and a 1,200 gallon dose filter flush tank; a 10.6 acre irrigation area consisting of twelve (12)
irrigation zones and a rain sensor; and all piping, valves and appurtenances
to serve 705 bedrooms on 235 residential lots at Hampstead Lands with no discharge of wastes to the
surface waters, pursuant to the application received March 7, 2006 and subsequent additional information
received by the Division, and in conformity with the project plan, specifications, and other supporting
data subsequently filed and approved by the Department of Environment and Natural Resources and
considered a part of this permit.
This permit shall be effective from the date of issuance until May 31, 2011, and shall be subject to
the following specified conditions and limitations:
1. PERFORIMANCE STANDARDS
I. This wastewater treatment and irrigation disposal system shall only treat the wastewater
generated by the approved 235 residential lots. If the Permittee chooses to connect additional
wastewater generators (i.e,, residences, neighboring school, etc.), the Permittee shall submit a
permit modification to increase the wastewater treatment plant capacity and reevaluate the
existing irrigation system to handle the increased flow.
2. Upon completion of construction and prior to operation of this permitted facility, a certification
must be received from a professional engineer certifying that the permitted facility has been
installed in accordance with this permit, the approved plans and specifications, and other
supporting materials. If this project is to be completed in phases and partially certified, you shall
retain the responsibility to track further construction approved under the same permit, and shall
provide a final certificate of completion once the entire project has been completed. Mail the
Certification to the Land Application Unit, 1636 Mail Service Center, Raleigh, NC 27699-1636.
The Wilmington Regional Office, telephone number (910) 796-7215, shall be notified at least
forty-eight (48) hours in advance of operation of the installed facilities so that an in-place
inspection can be made. Such notification to the regional supervisor shall be made during the
normal office hours from 8:00 a.m. until 5:00 p.m. on Monday through Friday, excluding State
Holidays.
4. The reclaimed water utilization facilities shall be effectively maintained and operated at all times
so that there is no discharge to the surface waters, nor any contamination of ground waters, which
will render them unsatisfactory for normal use. In the event that the facilities fail to perform
satisfactorily, including the creation of nuisance conditions or failure of the irrigation area to
adequately assimilate the wastewater, the Permittee shall take immediate corrective actions
including those actions that may be required by the Division of Water Quality (Division), such as
the construction of additional or replacement wastewater treatment and disposal facilities.
5. The issuance of this permit shall not relieve the Permittee of the responsibility for damages to
surface water or ground water resulting from the operation of this facility.
6. The residuals generated from these treatment facilities must be disposed in accordance with
General Statute 143-215.1 and in a manner approved by the Division.
7. Diversion or bypassing of the untreated wastewater from the treatment facilities is prohibited.
8. The following buffers shall be maintained:
a. 100 feet between wetted areas and water supply wells,
b. 100 feet between wetted areas and waters classified as SA,
c. 25 feet between wetted areas and surface waters not classified as SA,
d. 100 feet between wastewater treatment units and wells,
e. 50 feet between reclaimed water storage/irrigation ponds and property lines, and
f. 50 feet between wastewater treatment units and property lines.
9. Public access to the irrigation sites shall be controlled during active site use. Such controls may
include the posting of signs showing the activities being conducted at each site.
10. The disposal system shall be connected to a rain or moisture sensor that shall indicate when
wastewater application is not appropriate in accordance with Condition II(4) of this permit.
11. A usable green area shall be maintained for wastewater disposal. The green area shall have the
capability of accommodating the average daily flow of the facility being served without
exceeding the loading rates of the green area. A "green area", as defined in 15A NCAC 2H .0404
(g)(7), is an area suitable for waste disposal, either in its natural state or which has been modified
by planting a vegetative cover of grasses or low growing shrubbery.
2
12. The following shall be requirements for the reclaimed water distribution, storage, and utilization
facilities:
a. All reclaimed water valves, storage facilities, and outlets shall be tagged or labeled to warn
the public or employees that the water is not intended for drinking. Where appropriate, such
warning shall inform the public or employees to avoid contact with the water.
b. All reclaimed water piping, valves, outlets, and other appurtenances shall be color -coded,
taped, or otherwise marked to identify the source of the water as being reclaimed water.
i. All reclaimed water piping and appurtenances shall be either colored purple (i.e., Panton
522) and embossed or integrally stamped or marked "CAUTION: RECLAIMED
WATER — DO NOT DRINK" or be installed with a purple (i.e., Pantone 522)
identification tape or polyethylene vinyl wrap. The warning shall be stamped on opposite
sides of the pipe and repeated every three feet or less.
ii. Identification tape shall be at least three inches wide and have white or black lettering on
purple (i.e., Pantone 522) field stating "CAUTION: RECLAIMED WATER — DO NOT
DRINK." Identification tape shall be installed on top of reclaimed water pipelines,
fastened at least every 10 feet to each pipe length and run continuously the entire length
of the pipe.
c. All reclaimed water valves and outlets shall be of a type, or secured in a manner, that permits
operation by authorized personnel only.
d. Above -ground hose bibs (i.e., spigots or other hand -operated connections) shall not be
present. Hose bibs shall be located in locked below -grade vaults that shall be clearly labeled
as being of non -potable quality. As an alternative to the use of locked below -grade vaults
with standard hose bibs services, hose bibs, which can only be operated by a special tool or
connected to a special hose connection, may be placed in non -lockable underground services
boxes clearly labeled as non -potable water.
II. OPERATION AND MAINTENANCE REQUIREMENTS
1. The facilities shall be properly maintained and operated at all times.
2. Upon classification of the wastewater treatment and irrigation facilities by the Water Pollution
Control System Operators Certification Commission (WPCSOCC), the Permittee shall designate
and employ a certified operator to be in responsible charge (ORC) and one or more certified
operator(s) to be back-up ORC(s) of the facilities in accordance with 15A NCAC 8G .0201. The
ORC shall visit the facilities in accordance with 15A NCAC 8G .0204 or as specified in this
permit and shall comply with all other conditions specified in these rules.
A suitable, year-round vegetative cover of Coastal Bermuda Grass shall be maintained on the
irrigation areas.
4. Irrigation shall not be performed during inclement weather or when the ground is in a condition
that will cause runoff.
5. Adequate measures shall be taken to prevent wastewater runoff from the irrigation field.
b. The facilities shall be effectively maintained and operated as a non -discharge system to prevent
the discharge of any wastewater resulting from the operation of this facility.
7. The application rate for each permitted irrigation area shall not exceed the following:
Irrigation Zone .
Area
(acres)
Dominant Soil
Series
Instantaneous
Loading Rate
(inches/hour)
Annual Loading
Rate (inches/year)
1
0.91
Leon
0.6
148.72
2
0.76
Kureb
0.6
148-72,
3
0.79
Baymeade
0.6
148.72
4
0.82
Baymeade
0.6
148.72
5
0.75
Baymeade
0.6
148.72
6
1.00
Kureb
0.6
148.72
7
0.98
Leon
0.6
72.28
8
091
Leon
0.6
72.28
9
0.88
Leon
0.6
72.28
10
0.82
Kureb
0.6
72.28
11
1.03
Kureb
0.6
72.28
12
0.95
Kureb
0.6
72.28
Total
10.60
8. An automatically activated standby power source shall be on site and operational at all times. If a
generator is employed as an alternate power supply, it shall be tested weekly by interrupting the
primary power source.
9. No type of wastewater other than that from the Hampstead Lands WWTF shall be irrigated onto
the irrigation area.
10. Freeboard in the wet weather storage and 5 -day upset ponds shall not be less than, two (2) feet at
any time.
11. A waste -level gauge to monitor waste levels in the storage and upset ponds shall be installed prior
to operation. This gauge shall have readily visible permanent markings indicating the maximum
liquid level at the top of the temporary liquid storage volume, minimum liquid level at the bottom
of the temporary liquid storage volume, and top of the dam elevations. Caution must be taken not
to damage the integrity of the liner when installing the gauge.
12. A protective vegetative cover shall be established and maintained on all earthen basin
embankments (outside toe of embankment to maximum pumping elevation), berms, pipe runs,
erosion control areas, and surface water diversions. Trees, shrubs, and other woody vegetation
shall not be allowed to grow on the earthen basin dikes or embankments. Earthen basin
embankment areas shall be kept mowed or otherwise controlled and accessible.
13. All wastewater shall be routed to the five-day holding pond should the limit for fecal coliform
(daily maximum concentration of 25 per 100 ml) or turbidity (instantaneous maximum of 10
NTU) be exceeded, until such time that the problems associated with the treatment capability of
the wastewater treatment plant have been corrected. The wastewater in the five-day holding pond
shall be pumped back to the treatment plant for re -treatment or treated in the five-day pond prior
to discharge to the storage pond.
14. The chlorine used in the disinfection facility shall be of the kind and type specified in the
Division approved plans and specifications.
4
15. Grass clippings generated by mowing the vegetative cover of Coastal Bermuda shall be removed
from the irrigation site. Grass clipping removal shall be done by bagging or another suitable
method approved by the Division.
16. Waste shall not be applied or discharged onto or below the land surface when the vertical
separation between the waste and the seasonal high water table is less than one (1) foot.
III. MONITORING AND REPORTING REQUIREMENTS
1. Any monitoring (including groundwater, surface water, soil or plant tissue analyses) deemed
necessary by the Division to insure surface and ground water protection will be established and
an acceptable sampling reporting schedule shall be followed.
2. Influent flow shall be continuously monitored and daily flow values shall be reported on Form
NDMR.
The Permittee shall install an appropriate flow measurement device consistent with approved
engineering and scientific practices to ensure the accuracy and reliability of influent flow
measurement. Flow measurement devices selected shall be capable of measuring flows with a
maximum deviation of less than 10 percent from true flow, accurately calibrated at a minimum of
once per year, and maintained to ensure that the accuracy of the measurements is consistent with
the accepted capability of that type of device. The Permittee shall keep records of flow
measurement device calibration on file for a period of at least three years. At a minimum, data to
be included in this documentation shall be:
a. Date of flow measurement device calibration
b. Name of person performing calibration
c. Percent from true flow
3. As an indicator of proper operation and maintenance, the facility shall produce an effluent in
compliance with the following limitations:
Parameter
Flow
Monthly Average"
84,600 GPD
Daily (Instantaneous) Maximum
BODS (5 -day, 20°C)
10 mg/1
15 mg/1
NH3 as N
4 mg/1
6 mg/l
TSS
5 mg/l
10 mg/l
Fecal Coliform
14 per 100 ml b
25 per 100 ml
Nitrate (N0O
10 mg/1
Turbidity
10 NTU
The effluent pH shall not be less than 6.0 standard units nor greater than 9.0 standard units.
Monthly averages for all but fecal coliform shall be the arithmetic mean of all samples
collected during the reporting period.
b
Monthly average for fecal coliform shall be the geometric mean of all samples collected
during the reporting period.
Daily maximum shall be the maximum value of all samples collected during the reporting
period.
5
The Permittee shall monitor the effluent from the subject facilities at a point prior to irrigation for
the following parameters:
Parameter .
Sampling Point
Sampling Frequency
Type of Sample
Flow
Influent or Effluent
Continuous
Recording
Turbidity
Effluent
Continuous
Recording
BOD$ (5 -day, 20°C)
Effluent
*2/Month
Composite
NH3 as N
Effluent
*2/Month
Composite
TSS
Effluent
*2/Month
Composite
Fecal Coliform
Effluent
*2/Month
Grab
NO3
Effluent
*2/Month
Composite
Total Nitrogen
Effluent
*2/Month
Composite
Total Phosphorus
Effluent
*2/1\4onth
Composite
Settleable Matter
Effluent
Daily
Grab
Residual Chlorine
Effluent
Daily
Grab
TDS
Effluent
Triannually
Grab
TOC
Effluent
*Triannually
Grab
Chloride
Effluent
*Triannually
Grab
pH
Effluent
Triannually
Grab
21Month sampling frequency only during the months of April through October. During the
remainder of the year, these parameters shall be monitored monthly.
** Triannually sampling shall be conducted during March, July, and November.
If Groundwater sampling indicates or predicts problems with the compliance with Groundwater
Standards, this permit will be modified to include additional and/or more restrictive limitations.
4. The Permittee shall maintain adequate records tracking the amount of wastewater disposed.
These records shall include, but are not necessarily limited to the following information:
a. Date and time of irrigation,
b. Volume of wastewater irrigated,
c. Zone irrigated,
d. Length of time zone is irrigated,
e. Continuous weekly, monthly, and year-to-date hydraulic (inches/acre) loadings for each zone,
f. Weather conditions, and
g. Maintenance of cover crops.
5. Freeboard in the wet weather storage and 5 -day upset ponds shall be recorded weekly.
6. Three (3) copies of all monitoring data [as specified in Conditions III(2) and 111(3)] on Form
NDMR-1 and three (3) copies of all operation and disposal records [as specified in Conditions
I11(4) and 111(5)] on Form NDAR-1 shall be submitted monthly on or before the last day of the
following month. All information shall be submitted to the following address:
NC Division of Water Quality
Information Processing Unit
1617 Mail Service Center
Raleigh, North Carolina 27699-1617
7. A record shall be maintained of all residuals removed from this facility. This record shall include
the name of the hauler, permit authorizing the disposal or a letter from a municipality agreeing to
accept the residuals, date the residuals were hauled, and volume of residuals removed.
A maintenance log shall be maintained at this facility including but not limited to the following
items:
a. Daily sampling results of dissolved oxygen in the aeration basin and at the clarifier weir.
b. Visual observations of the plant and plant site.
c. Record of preventative maintenance (changing of filters, adjusting belt tensions, alarm
testing, diffuser inspections and cleanings, etc.).
d. Date of calibration of flow measurement device.
e. Date and results of power interruption testing on alternate power supply.
9. Noncompliance Notification:
The Permittee shall report by telephone to the Wilmington Regional Office, telephone number
(910) 796-7215, as soon as possible, but in no case more than 24 hours or on the next working
day following the occurrence or first knowledge of the occurrence of any of the following:
a. Any occurrence at the wastewater treatment facility which results in the treatment of
significant amounts of wastes which are abnormal in quantity or characteristic, such as the
dumping of the contents of a sludge digester; the known passage of a slug of hazardous
substance through the facility; or any other unusual circumstances.
b. Any process unit failure, due to known or unknown reasons, that render the facility incapable
of adequate wastewater treatment such as mechanical or electrical failures of pumps, aerators,
compressors, etc.
c. Any failure of a pumping station, sewer line, or treatment facility resulting in a by-pass
directly to receiving waters without treatment of all or any portion of the influent to such
station or facility.
d. Any time that self-monitoring information indicates that the facility has gone out of
compliance with its permit limitations.
Occurrences outside normal business hours may also be reported to the Division's
Emergency Response personnel at telephone number (800) 662-7956, (800) 858-0368, or
(919) 733-3300. Persons reporting such occurrences by telephone shall also file a written
report in letter form within five (5) days following first knowledge of the occurrence. This
report must outline the actions taken or proposed to be taken to ensure that the problem does
not recur.
GROUNDWATER REQUIREMENTS
Prior to beginning waste disposal operations, four (4) monitor wells (MW -1, MW -2, MW -3 and
MW -4) shall be installed to monitor groundwater quality. The wells shall be constructed such
that the water level in the well is never above or below the screened (open) portion of the well at
any time during the year. The general location and name for each well is marked on Figure 1.
Each monitoring well shall be located at the review boundary, constructed in accordance with this
permit, and approved by the Wilmington Regional Office.
2. All wells that are constructed for purposes of groundwater monitoring shall be constructed in
accordance with 15A NCAC 2C .0108 (Standards of Construction for Wells Other than Water
Supply) and any other state and local laws and regulations pertaining to well construction.
3. The Wilmington Regional Office, telephone number (910) 796-7215, shall be notified at ]east
forty-eight (48) hours prior to the construction of any monitoring well so that an inspection can be
made of the monitoring well location. Such notification to the regional Aquifer Protection
supervisor shall be made during the normal office hours from 8:00 a.m. until 5:00 p.m. on
Monday through Friday, excluding state holidays.
4. Within sixty (60) days of completion of all monitoring wells, the permittee shall submit two
original copies of a scaled topographic map (scale no greater than I":100') signed and sealed by a
professional engineer or a state licensed land surveyor that indicates all of the following
information:
a. The location and identity of each monitoring well,
b. The location of the waste disposal system,
c. The location of all property boundaries,
d. The latitude and longitude of the established horizontal control monument,
e. The relative elevation of the top of the well casing (which shall be known as the "measuring
point"), and
f. The depth of water below the measuring point at the time the measuring point is established.
The survey shall be conducted using approved practices outlined in North Carolina General
Statutes Chapter 89C and the North Carolina Administrative Code Title 21, Chapter 56. The
surveyor shall establish a horizontal control monument on the property of the waste disposal
system and determine the latitude and longitude of this horizontal control monument to a
horizontal positional accuracy of +/- 10 feet, All other features listed in a, through c. above shall
be surveyed relative to this horizontal control monument. The positional accuracy of features
listed in a. through e. above shall have a ratio of precision not to exceed an error of closure of I
foot per 10,000 feet of perimeter of the survey. Any features located by the radial method will be
located from a minimum of two points, Horizontal control monument shall be installed in such a
manner and made of such materials that the monument will not be destroyed due to activities that
may take place on the property. The map shall also be surveyed using the North American
Datum of 1983 coordinate system and shall indicate the datum on the map. All bearings or
azimuths shall be based on either the true or NAD 83 grid meridian. If a Global Positioning
System (GPS) is used to determine the latitude and longitude of the horizontal control monument,
a GPS receiver that has the capability to perform differential GPS shall be used and all data
collected by the GPS receiver will be differentially corrected.
The maps and any supporting documentation shall be sent to the N.C. Division of Water Quality,
Aquifer Protection. Section., Land Application Unit, 1636 Mail Service Center, Raleigh, N,C,
27699-1636.
Upon completion of all well construction activities, a certification must be received from a
professional engineer certifying that the monitoring wells are located and constructed in
accordance with the Well Construction Standards (15A NCAC 2C) and this permit. This
certification should be submitted with copies of the Well Completion Form (GW -1) for each well.
Mail this certification and the associated GW -1 forms to the Aquifer Protection Section, Land
Application Unit, 1636 Mail Service Center, Raleigh, N.C. 27699-1636.
For the initial sampling of the well as specified in Condition IV(1) of this permit, the permittee
shall submit a copy of the GW -1 Form (Well Completion Form) with the Compliance Monitoring
Form (GW -59) for that well, Compliance Monitoring Forms that do not include copies of the
GW -1 form will be returned to the permittee without being processed. Failure to submit these
forms as required by this permit may result in the initiation of enforcement activities pursuant to
NC General Statutes 143-215.6.
7. Monitor wells MW -1, MW -2, MW -3 and MW -4 shall be sampled initially after construction (and
prior to waste disposal operations) and thereafter every March, July and November for the
following parameters:
Water Level
Chloride
. Total Organic Carbon (TOC)
Nitrate (NO3-N)
Fecal Coliforms
Total Ammonia Nitrogen (NH3-N)
PH
Total Dissolved Solids (TDS)
Total Phosphorus
8. The measurement of water levels must be made prior to sampling for the remaining parameters.
The depth to water in each well shall be measured from the surveyed point on the top of the
casing.
9. The measuring points (top of well casing) of all monitoring wells shall be surveyed to provide the
relative elevation of the measuring point for each monitoring well.
10. If TOC concentrations greater than 10 mg/l are detected in any downgradient monitoring well,
additional sampling and analysis must be conducted to identify the individual constituents
comprising this TOC concentration. If the TQC concentration as measured in the background
monitor well exceeds 10 mg/l, this concentration will be taken to represent the naturally occurring
TOC concentration. Any exceedances of this naturally occurring TOC concentration in the
downgradient wells shall be subject to the additional sampling and analysis as described above.
11. The results of the sampling and analysis must be received on Form GW -59 (Groundwater Quality
Monitoring: Compliance Report Form) by the Division. of Water Quality, Information Processing
Unit, 1617 Mail Service Center, Raleigh, North Carolina 27699-1617 on or before the last
working day of the month following the sampling month.
12. The five-day upset pond and wet weather storage pond shall have either a liner of natural material
at least one (1) foot in thickness and having a hydraulic conductivity of no greater than 1 x 10-6
centimeters per second when compacted, or a synthetic liner of sufficient thickness to exhibit
structural integrity and an effective hydraulic conductivity no greater than that of the natural
material liner, according to 15A NCAC 2H .0219(f).
13. The COMPLIANCE BOUNDARY and REVIEW BOUNDARY for the waste disposal area(s) is
specified by regulations in 15A NCAC 2H, Waste Not Discharged to Surface Waters, specifically
.0219(k)(1)(C)(i)(III). The Compliance Boundary and the Review Boundary for groundwater
shall be established at the property boundary. An exceedance of Groundwater Quality Standards
at or beyond the Compliance Boundary is subject to remediation action according to 15A NCAC
2L .0106(d)(2).
V. INSPECTIONS
Adequate inspection, maintenance, and cleaning shall be provided by the Permittee to insure
proper operation of the subject facilities.
2. The Permittee or his designee shall inspect the wastewater treatment and disposal facilities to
prevent malfunctions and deterioration, operator errors and discharges which may cause or lead to
the release of wastes to the environment, a threat to human health, or a nuisance. The Permittee
shall keep an inspection log or summary including at least the date and time of inspection,
observations made, and any maintenance, repairs, or corrective actions taken by the Permittee.
This log of inspections shall be maintained by the Permittee for a period of three years from the
date of the inspection and shall be made available upon request to the Division or other permitting
authority.
3. Any duly authorized officer, employee, or representative of the Division may, upon presentation
of credentials, enter and inspect any property, premises or place on or related -to the disposal site
or facility at any reasonable time for the purpose of determining compliance with this permit;
may inspect or copy any records that must be maintained under the terms and conditions of this
permit, and may obtain samples of groundwater, surface water, or leachate.
VI. GENERAL CONDITIONS
This permit shall become voidable unless the facilities are constructed in accordance with the
conditions of this permit, the approved plans and specifications, and other supporting data.
2. This permit is effective only with respect to the nature and volume of wastes described in the
application and other supporting data.
The Operational Agreement between the Permittee and the Environmental Management
Commission is incorporated herein by reference and shall be a condition of this permit.
Noncompliance with the terms of the Operational Agreement shall subject the Permittee to all
sanctions provided by North Carolina General Statutes § 143-215.6A to § 143.215.6C for violation
of or failure to act in accordance with the terms and conditions of this permit.
4. This permit is not transferable. In the event there is a desire for the facilities to change
ownership, or there is a name change of the Permittee, a formal permit request must be submitted
to the Division accompanied by an application fee, documentation from the parties involved, and
other supporting materials as may be appropriate. The approval of this request will be considered
on its merits and may or may not be approved.
5. Failure to abide by the conditions and limitations contained in this permit may subject the
Permittee to an enforcement action by the Division in accordance with North Carolina General
Statute 143-215.6A to 143-215.6C.
6. The issuance of this permit does not exempt the Permittee from complying with any and all
statutes, rules, regulations, or ordinances which may be imposed by other government agencies
(local, state, and federal) which have jurisdiction, including but not limited to applicable river
buffer rules in 15A NCAC 213.0200, erosion and sedimentation control requirements in 15A
NCAC Chapter 4 and under the Division's General Permit NCG010000, and any requirements
pertaining to wetlands under 15A NCAC 2B .0200 and 2H.0500.
7. The Permittee shall retain a set of approved plans and specifications for the subject facility for the
life of the project.
10
8. The Permittee shall pay the annual administering and compliance fee within thirty days of being
billed by the Division. Failure to pay the fee accordingly may cause the Division to initiate action
to revoke this permit as specified by 15 NCAC 2H .0205 (c)(4).
9. The Permittee, at least six (6) months prior to the expiration of this permit, shall request its
extension. Upon receipt of the request, the Commission will review the adequacy of the facilities
described therein, and if warranted, will extend the permit for such period of time and under such
conditions and limitations as it may deem appropriate.
Permit issued this the 19`x' day of June 2006
NORTH
AL MANAGEMENT COMMISSION
Alan W. Klimek, PL, Director
Division of Water Quality
By Authority of the Environmental Management Commission
Permit Number WQ0029952
11
Permit No. WQ0029952
June 19, 2006
ENGINEER'S CERTIFICATION
Partial Final
I, , as a duly registered Professional Engineer in the State
of North Carolina, having been authorized to observe (periodically, weekly, full time) the construction of
the project,
Project Name
Location and County
for the Permittee hereby state that, to the best of my abilities, due care and diligence was used in the
-observation of the construction such that the construction was observed to be built within substantial
compliance and intent of this permit, the approved plans and specifications, and other supporting
materials.
Signature
Date
12
Registration No.
r. �- � r.� .• ``�Y` � I 1 � f j~\t� ' /I -------------
- - - - - -
--__-_--_-------
_ ' v • •WEtUlN65^ ����/ ��' 1 l + f I i � � �' t t i � ' / /� �'�� ~tet I 1l t �
/ I 1
.+
151 -DAY• 1 • �" �1. •'a'. �
IRRIGATION II
• j , 1 v . �P /` ! / r 7 _ ! I ! I r r-•----"-, t `\ 1 t �/ ` ! 1+ \ t L
POND\•. " �. .�` / /�
LI.- O
�,�,1 �`<-' ` , � - • " 1 1 -_, r � /•� � _-� _'- '- + I _ /' � J i '� r `~ �� �+ � +� /� � -1
10ii4' �
r .. ����1\.,1R. \ �• `':� 1 I--'7 �-. `- �Yc`^4-"- i _ r- r�s.,�.ria#� `�.... + t�� ,.r` I NfR ! ' t-
..1:�` 5\" �..'W��'`F _r --i+' ate' •"-.4 t�� �-=�� � � t� \ 7 Fey
« . " .
CQ
J � r I s•�'=.- ! , - "F` '--�'- �-,j-*-*-3r -• � _ _ _I+ � J � �.h fr �`_7 _ �--_------"- Qui �
SOR 21 PVC PIPE Mw -1 Y`':�,t I��r //' ��� �t v� •� ! _••� Ihr�-�`+-�.:"'T`" -J%�'« VIII 7 r `{w;{ I L � IIf4- i _
» t 93Fi' TO ZONE 8 �� --� �` + �J .�,"j. \ • �•.. f I !
WETLaNDs•• -�'-1 t \ �i•j � / ,f' �. . r-:�• � .;r;«yi, 1�`. `:'1.:.:.:��~_ `.� fr �"'• r !
,♦ ` :• \ J i V� i , • Tom' `� - «� , • _ r
+�+ ♦ i r. i rr ' � ' ,-.ams`• -e t• A �.' �• ,I✓ f y/ /' r El. _ _ . [J
�.i F
-�. 1r~ 4 1 1 I 1 1 ! y'. •l. .« j.• l_ �.' �' i� /` /' ri •I
. 1!+ 11ti - � � .Yr ` 1� 11 i i j%`« � «' 'ti . , " al " 15, . a .\ � _- _• i i 1. {•1' •I IIYi i
'.' . ". r\ / S I� ♦ 3 I•" I , 4 I• C a5 ", .' 4l �.� / /` 11 j � �+PlI, 1 \ ��yj
• « a i • \I 5 � ♦ k C_ ^ . 1 1 � I 1 / ., �. • « . , t - " Y 1< . � / Il I !' f I•I � +S. 1� W {f f
! � i I I I .r+' r + �I •I- .4«'-1' .1 � / I 1 +•"�"J f. 1\ U]
.`r -.`r.
•"�--,t -~� ♦ ylI I ,� li` '•��_r., _�..+-7��•� j,�`�"•1.• 'r l« :I..•�II.^ "S'. J .[ + i Ir• .I :!{}'� \ q �{ �Qi
••�� •+.,../''\ f r=' I I i ,{ \ O c O 1 11�' rF
' • a v .'�.•..Cen� �-h I .\ I I « • �l,�, !/ , t\. '. - « 5, I• ,. \ ' . .. ... I ^ r �� , `I. l if n \ ♦ 4•r•1 }
,f % I ..1 \ 1 a%.. / 1 _ "•I `\.. I r r � �.` i 1:' I1, \ +♦ T�� � ,}� m
\ `` \ t �•. .\,/ 1 \• 1 I�. �. .�`"•'•IS ."•I�* .`tl `. r- • - �.��r --- I �•�•L I�" I! \\ `t \\\ t vl 7
r . . ' 1 ' . � . . � . . "`✓ . ll ------- -! � � 1 � f ��• � Y t ' 1 wirrp Ew
,ASI I f I /• - :ti♦ 1 I i yl• 1': YC1Y. C. �.".4"SI •. ".p a!•�i �l'-I• !I fl 1\j 1 t\ {i'rS.. 1\ �r v xW
\ Ts \ f /' '�. 5 41 I I Il"ra .•" «�r. �'"• ` .`f ' 1. �1 `�•I i I `\ t tj r- M U
'• , ff ' r j' ♦ t r I I " . " q Ly - - ' ..... " . .. ` .•" :,.. ------
NO
-
SCAT, AREA NO. k i .- r 1t 1 tt I y «�•+•• •'• •i-.'yt'' t • •. • _ '.. 1 '� I
`�•� ??' . " . . . I . I • ' 1 P I 1 . I raj
y 24I3,Q7 5-S.F. I �r _ • + 1 1 ! 1 '1; _ '+ • + 4 T + 1 , /' � � " � C7
2Tr I I I _ V _,�.. 'v'r+... 1 "�+•• •� ' t. C "a'• jj •7• \ --- r"•'"' IIr I 1 v w
/ �` � I I ,y..- .". {�-- �", \, 1 S ,\ , ` j ` -.-� "•+-.' JL4__• �I I` % l I � 1-
3 L 1 + t, +,_fir._ �k 1 \ ;•S.,vl '.w I.rW. is ." 'ti'. •'. �'•. .•.� .`.'.' v .i ".
II I yy T
\, �~T `1 \, J L' F••``r�`." v'a•y .1.-» I. P � « .•. r1. .'rAV.... ,�'�', ••�• ILI`� I I! V1
1 ��-•� Mw -2 Y -- - -- t j - .`\ - i`:"} _ : •+1. :4: :; ` ', ±"4/ -�' '� - v �y�. ,` i 't` Ir Z
.... :', ::' •//• Y1 4 f 1 `' O
-j . ••II. . .�. .• I. �'. .I' ,"«-"J♦ .-• �. ."1 '. • �r.• •� •, .r dl/ ',,�il,l \.� I+ 4� n
i `�� 4 `\ a -I� MW -4 :n4• I• T I`. L " { "I. 4." . { 1 «"� • v �(�'-"a'•%_`,`- p-,�-ill 4 11 !1 �5
•/'�1 `rs i' ti oiwe J ��- �i,+! 'I-�I• •I 'L•" •qf• j� - J, •• �•l •«r -.=.f, .��-. I. -IL
4]
f � �� `l ! I t y .I . '" .`�'. i. y.• .R .4 .l. 1 � 1 -•t "« 1 JI11' +� 1 '�� 7 � O
---��----��� �! 1 , I 't I- - .�` � \ \ / � �. «,. Y!«}.-•'�"' •l'"-.1 . . ,1 r«. " �"« •'i •''. .-�1r -.W b' ; ' ♦1` `. .c���'.15j."�. 5♦ ♦ ``' t `♦
292 / i I �� I rr .L' 1. ."« »7 - f - .Il-. 1. .I .!« I»• .I• .-. t�" .i.",� .•.yi`�Y ••� ` , , o!
291 ! �, `,p 1, ��. � ; ,/ , ,�. .` ; :. y.«..4-.':�' ."a':."1 ".:�' .-.�:• ;.• •�- •-`r••.-�_• . � . � . '_ , ,.,�" \`_�-_.tt ,t _o
293 r --•S- I` + 1 .•i.'._.i . v
-.-. . .t' ♦`. .� ra I l�'".1 A` Vt \
♦\ 1 ' + i + Y I « •I • y 1 tc -`�• 1 «1t t'' 4 7-.
�` __.�__ I _ %'4 �_l I I `, + � 5 + [[ .1' Lv. ,.r "mow - `♦. I'- L` •r•4. v f�l'. .�. �•`1..-. �. 1__»_ .',♦�. `..��a. �." �' L `h;-�l 11 \\;♦'s♦I i i i i i 1 �
-r �� `� � r � , 1 , x `A`»'.�. . moi' . `• •J' ai « .i. � _ 'tV.•. •'' '.'.-"' .��\�%�y \ \` tVt �-•
�� , � 290 + I �.� \ ♦ I 1 1 1 i`L'.-.1.....-. ,� ` `♦`` k r•+•.i .".1 .-I. .! •�.• -. �,•+�,�•. � i'•.� ft,�«. - .'S,. ..�� `�♦ \`\I� I i i i ,
1 r i } 11 I i..-. I f. 1• i« t,' l J" . ♦\♦�
�� 't c i € ciO 6 i� o o �l „� �S t \ E @ tl I I - •' :'�`�` ```�♦ ��`.".:.ya" F �a. «"If_'" " a .':tL.- �.':�.i\=~� •N \ +'�s,• •. ������ ��`..�
. rr�-+� V 11 J+n un �, xcv ` sr 1 , m I j av � 1 1 [ lY�Ia a l . ` � ♦1 ♦ L�fI. 1 « I « 1 a J I . ` »I I L ' . 1 5 • S f a ? ' • . � ., `` � �♦♦ �'1�
'\ \ x� �" zn m ar 1 5 1 m,1 1 j I 1"`• �,`»`, .--- f 1 rJ 1•'-11•«•.It •". ;.. '.IV-.-. ,4.«."a`r.+. SII�� a1L. .,.'.IL7 l �'. Y.�. . •N�•• ,•A .'1♦�: U
! ',• I _ •'\ ♦ � k nv av av my my m m mr a,i 1 i I = S .� I 1 f \. a S. t . ` 1 4'f�Tta � . 1.+. . 1,' tR� `� \ .',�..« « . ♦. . DN "� � N
7 E f>y/, 289 + I ,♦ 1 I I 1 t•`♦« "� •'••• « i r I I \•v .t .1« .1,• •:+' .•.�`.+. .I "i 11 1` d • a .1 .-1!f '�'�'�' �..� -L '4 `. r
r 1 .\ \♦ \ €€ \ 4 5 1 6 I k 1r1 :.•. . + r , i y -. yy I I' t•a +y « 4�i .( 1 \ \.. ` ��. �V\-. -.•:� W
28a•r`"�,� ___- 1 \\ i }� \ D ` I tt I 01 I I i I 1«" -\ .. �.•�.�-•I tl l It�•�- r\.' 4 "«It• '+'!~� ",•• ,2H1. 7�. k~C 'a 4 .'•.��Y�`+If-���.,I �Cv N
L_ I
2B7 7jr � '\ " ,t � rt , + 1 � >� - .1'� 11 I r , •�. �. .t t ., � � I � « .� -tr . s. �...� 1 Ir , �-�� �.. \.�
" + l f 1 ll 1 I 1 1 ` 1 I Y.� +... _ "• f � a. L�
0 it a C2 III
LLQ=
a - 'W-� : • \' +\ \ -� /° 9 I ell- 1. 41 k ♦ `, \5 r- ^-� r.^ _ .,_- � �.r _ PROPERTY LINE Q UJ Q ca ti
L�-� _ r1 I • '`...,yc�ax 1 ,\ '` // i j I 1 ! I \ } _1 y__ :r^ Xp� J �3s - - -I t� FY m
r S . \ \ 1 ` \ % I I � I I 1 ` .•p... - •- f - �t_____S ��--ov a • . MAXIMUM SLOPE POWER POLE C� .1 = b e•7
♦ ,; . . - . ' . « « . ' \ \ \ 1 I S I I 1 i l �' . \ . W. 1. \ 4 1 t J DESIGN FLOW - H9a720 CPB z 0 f -
I II Iw'3 I 1 1 ,.' \ t 1 A ,. r w GUY WIRE V C
EA N i , .t , , t t �/ , L . ,. . WETTED AREA +. 456,196 S.F. a �• I"
. �\ 1 ,. - . • . «. a . - . • . , \ t i
TTI r + l 1 J I , 5 : j" • oe[ OVERHEAD ELECTRIC m
2 7.2 2 r t ., I . 1 t 1 tt .0 •. - • t� , • , •'�• - • SOIL AREAS w y YWyJ I=•• Z
' 1 1, , • .� a , �• 'f \ tt �1 y E u UNDERGROUND ELECTRIC Z ' YM
.'\ / «.•«•.'.".'.',". '�-., 1 I I I 4 I f tt..l. .1 K 1 1 \ } - AREA I: R F6UND IRON PIN 0 2 Z
- _ . , a.j.,•�., - • . Y ` Syl I P� I I I f \ y • , 1. " ., • :1 t \ f .� "�' , '-' ,� APPLICATION RATE - 3.865 INCHES/WEZI< p frj y Q 0
x U_
. .-t.�' r ��., �," y,\ t,�I I S 1 t Zl•.� IV 1 -lt'. �. a FUM RATE NES CPM R.O. w. MARKER Z r tl
r ! I I I \ t. + • f j ' •�"'+ •, NUMBER OF ZONES fi N!J o C7
• • - • • . • •� / ;.. ` .•\ 1 S I I 1 t'•' „ ' I ' . " j + t t « ' _' + •'\y • HEAD COUNT - 132 a . SURFACE INLET L7 2
FIRE
.-� 1 77 ' I I / I { I E11+ ` 1 ,. Vit•.-". .`l t, 1ttt>•` Sia �\•+ `a \.« a AREA 2: Ow MAN HOLEANT J
1 I + ` +. • . ' . .\ APPLICATION RATE - 1.162 INCHES/WEEK
} 4 t
• ' • "�• 1 ' 1 » • II I tt �' al I I •i -+ tl • « �` . FLOW RATE - 88.2 GPM , Ob CLEAN OUT C7
I f I ! V \ • « • • • - J • .�- NUMBER OF ZONES - 6 �-. s LDW PRESSURE SEWFR Q
_ ' . •` ! �' . . "\ 1 / I 1� t , 3 ` y ^ 1` .4• . + .� •I - .} • " C HEAD COUNT - 120 =
4 �',' .\ I , , t \ , } - •-'� I- L WsiLl�IDS,. . .•. WATER LINE
+ • , • , . . , • p+\ _ -,L 15 lt'�. ,t, • . 1 " . ' I " .
t. , 4 ' 1, ' « . c COVER CROP - COASTAL BERMUDA
y `\ ' C \ ♦ • . - IRRIGATION ZONE LINE
LY Y� ��" 4+_ 1 C • ,• n ELEVATION OF HIGHEST NOZZLE 88.5' MSL
• • +1 , �+ - .\. rte- l 1� 1 5 '� , \ • - • �, - � • t • • ` • �♦ « a •\• EXISTING CONTOURS L
•
• ' • �• , s It , s%'« ' ••- « • • .,\ I 1t ` l \
i•l ' . «. aJ` P. •. Y♦•. \- �,•i • 3� SENNENGER 40 SERIES SPRINKLER o ZCV ZONE CONTROL VALVE
_
' ) ,' ♦. c Tv TONE ISOLATION VALVE
I `� I 1 + I I I 1 4 L i " • \ " _C , • • `• MODEL 4012-1-3/4' M w/ /l0 NOZZLE oPR PRESSURE REGULATOR
��r! •4' CHAMLiNK'FENCE • ' • • • I + 4 4 / r
\S.�_..-..,1'f • . • �«' \ LOW ANGLE 12•
• CKV CHECK VALVE
. \ . 1 z 5 S 5 , ,• +• . " . " . , \ \Y tr a,c « FLOW .4.41 GPM O 40 P51
` ,.^ '\". ♦. .N ARVB AIR REL- SE/VACUUM BREAK VALVE
J CATI DIAMETER - 79 FEET tl 4D PS . cA
'APPIlCAON• AREA. ` • .{�� \ . 1 1 t t '♦ t, •. ♦. -� SPACING - 40' a 40'
• - ,j3 • ,D8D"LF?j 1' { + ' % ` a ❑ AF AUTOMATED FILTER v+��uvu °Irprs
1 . ,' , �,N"
• •' , - • ` • • " « -, ` t . \ ` I, 1 55 `♦`♦ HEIGHT - 1.5 FEET APPLICATION RATE - 0.265 INCHES/HOUR, MAX. ® MW MONITORING WELL � - • `t/s�,4
' wETIJfN ♦ yry_, t 4 , 5 '` , V \ �] SPRAY IRRIGATION SIGN
. • .r, ♦q l 1 , '�', '•1 S , 1 ♦ ♦ ♦ t LOW ANGLE SPRINKLER AT LOW PRESSURE = K& _
' . , . . • l♦ ♦ , t " , , t `♦ 1 TO MINIM3ZE WAND DRIFT
• - _ ..`.".'.�.'• ." •'.' -. .: : :`:`i ` - 1 t5 t 1 tl tt ` \� ` ` FINALDESIC7iE 'rr Nta`
` t ♦♦ GRAPHIC 8CA!]3
- tS' l , t1 + ` \ar r��� NOT RELEA 4 w rllrllt,t'
. : s - . - . +� �� ����� _j t `♦ \ \ ` FOR Su r- ORANNNG:
.� --- '•• .> `♦ f amu''- - �u+�' 1 '" �, \ `♦ CONSTRUCTION ims w!M C. 10.2
"`\-.`-Q2006 HAGGETT ENGINEERING ASSOCIATES, INC.
Flal
WQ0029952 — Hampstead Lands WWTF
17451 Hwy 17
Hampstead, NC 28443
Latitude: 34' 24' 08" Longitude: -77'40' 35"
7 m'
ti
Ae
Col -
Rand I&NOy ConVany 0 2025 TANA, ht. Rel. 01,12005
Topsail
1, Beach
WQ0029952 — Hampstead Lands WWTF
17451 Hwy 17
Hampstead, NC 28443
Latitude: 34° 24' 08" Longitude: -77° 40' 35"
STATE OF NORTH CAROLINA
COUNTY OF
Pender
Permit No_ wQo029952
OPERATIONAL AGREEMENT
This AGREEMENT made pursuant to G.S. 143-215.1 (dl) and entered into this day of
by and between the North Carolina Environmental Management
Con=ssion, an agency of the State of North Carolina, hereinafter known as the COMMISSION; and
Hampstead 504 LLC & Movies One LLC , a corporation/general partnership registered/licensed to do
business in the State of North Carolina, hereinafter known as the DEVELOPER.
WITNESSETH:
The DEVELOPER is the owner of the certain lands lying in Pender County, upon
which it is erecting and will erect dwelling units and other improvements, said development to be known
as Hampstead Commons
(hereinafter the Development).
2. The DEVELOPER desires, to construct a wastewater collection system with pumps, wastewater treatment
works, and/or disposal facilities (hereinafter Disposal System) to provide sanitary sewage disposal to serve
the Development on said lands.
3. The DEVELOPER has applied to the COMMISSION for the issuance of a permit pursuant to G.S. 143-
215.1 to construct, maintain, and operate the Disposal System.
4. The DEVELOPER has created or shall create unit ownership in said dwellings units, other improvements
and lands through filing of a Declaration of Unit Ownership (hereinafter Declaration), pursuant to Chapter
47C of the North Carolina General Statutes.
5. The DEVELOPER has caused to be formed or will cause to be formed at the time of filing of the
Declaration. the (Unit Owners' Association) _ _ _ (hereinafter
Association), a non-profit corporation organized and existing under and by the virtue of the laws of the
State of North Carolina, for the purpose, among others, of handling the property, affairs and business of
the Development; of operating, maintaining, re -constructing and repairing the common elements of the
lands and improvements subject to unit ownership, including the Disposal System; and of collecting dues
and assessments to provide funds for such operation, maintenance, re -construction and repair.
6. The COMMISSION desires to assure that the Disposal System of the Development is properly
constructed, maintained and operated in accordance with law and permit provisions in order to protect the
quality of the waters of the State and the public interest therein.
NOW, THEREFORE, in consideration of the promises and the benefits to be derived by each of the parties
hereto, the COMMISSION and DEVELOPER do hereby mutually agree as follows:
1. The DEVELOPER shall construct the Disposal System in accordance with the permit and plans and
specifications hereafter issued and approved by the COMMISSION, and shall thereafter properly operate
and maintain such systems and facilities in accordance with applicable permit provisions and law.
2. The DEVELOPER shall not transfer ownership .and/or control of the Disposal System to the Association
until construction has been completed in accordance with the permit and approved plans, and the staff of
the Division of Water Quality has inspected and approved of the facilities. In order to change the name of
the permit holder, the DEVELOPER must request that the permit be reissued to the Association. The
request must include a copy of the Association Bylaws and Declaration.
3. The DEVELOPER shall not transfer, convey, assign or otherwise relinquish or release its responsibility
for the operation and maintenance of its Disposal System until a permit has been reissued to the
DEVELOPER's successor.
FORM: DEV 09/05 Page 1 of 2
4. The DEVELOPER shall provide in the Declaration and Association Bylaws that the Disposal System and
appurtenances thereto are pain of the common elements and shall thereafter be properly maintained and
operated in conformity with law and the provisions of the pen -nit for construction, operation, repair, and
maintenance of the system and facilities. The Declaration and Bylaws shall identify the entire wastewater
treatment, collection and disposal system as a common element, which will receive the highest priority for
expenditures by the Association except for Federal, State, and local taxes and insurance.
5. The DEVELOPER shall provide in the Declaration and Association Bylaws that the Disposal System will
be maintained out of the common expenses. In order to assure that there shall be funds readily available to
repair, maintain or construct the Disposal System, beyond the routine operation and maintenance
expenses, the Declaration and Association Bylaws shall provide that a fund be created out of the common
expenses. Such fund shall be separate from the routine maintenance funds allocated for the facility and
shall be part of the yearly budget.
6. In the event the common expense allocation and separate fund are not adequate for the construction,
repair, and maintenance of the Disposal System, the Declaration and Association Bylaws shall provide for
special assessments to cover such necessary costs. There shall be no limit on the amount of such
assessments, and the Declaration and Bylaws shall provide that such special assessments can be made as
necessary at any time.
7. If a wastewater collection system and wastewater treatment and/or disposal facility provided by any city,
town, village, county, water and sewer authorities, or other unit of government shall hereinafter become
available to serve the Development, the DEVELOPER shall take such action as is necessary to cause the
existing and future wastewater of the Development to be accepted and discharged into said governmental
system, and shall convey or transfer as much of the Disposal System and such necessary easements as the
governmental unit may require as condition of accepting the Development's wastewater.
8. Recognizing that it would be contrary to the public interest and to the public health, safety and welfare for
the Association to enter into voluntary dissolution without having made adequate provision for the
continued proper maintenance, repair and operation of its Disposal System, the DEVELOPER shall
provide in the Association Bylaws that the Association shall not enter into voluntary dissolution without
first having transferred its said system and facilities to some person, corporation or other entity acceptable
to and approved by the COMMISSION by the issuance of a permit.
9. The agreements set forth in numbered paragraphs I, 2, 3, 4, 5, 6, 7, and 8 above shall be conditions of any
permit issued by the COMMISSION to the DEVELOPER for the construction, maintenance, repair and
operation of the Disposal System.
10. A copy of this agreement shall be filed at the Register of Deeds in the County(ies) where the Declaration
is filed and in the offices of the Secretary of State of North Carolina with the Articles of Incorporation of
the Association.
IN WITNESS WHEREOF, this agreement was executed in duplicate originals by the duly authorized
representative of the parties hereto on the day and year written as indicated by each of the parties named below:
FOR THE IRO L Hampstead 504 LLC & Movies one JtiC
MAN N C SION Name o LOPER
,Alan W. Klimek, P.E., Director (Si Lure)
Division of Water Quality
Jim McFarland, President
Print Name and Title
Zi Y L6, 41- 3 -0 &
(Date) (Date)
FORM: DEV 09/05 Page 2 of 2