HomeMy WebLinkAboutWQ0010736_Final Permit_19950609State of North Carolina
Department of Environment,
Health and Natural Resources
Division of Environmental Management
James B. Hunt, Jr., Governor
Jonathan B. Howes, Secretary
A. Preston Howard, Jr., P.E., Director
June 9, 1995
Helen Wimberley, Owner
1513 Walnut Street
Cary, North Carolina 27511
Dear Ms. Wimberley:
4 • •
r �T
C)EHNR
Subject: Permit No. WQ0010736
Wimberley Farms, Lot ##1
Single Family Wastewater
Spray Irrigation Facility
Wake County
In accordance with your application received March 10, 1995, we are forwarding herewith Permit
No. WQ0010736, dated June 9, 1995, to Ms. Helen Wimberley for the construction and operation of the
subject single family wastewater treatment and spray irrigation facilities.
Please be advised of Condition No. V 3 which states that this permit is not transferable. In the
event there is a desire for the facilities to change ownership, or there is a name change of the Permittee, a
formal permit request must be submitted to the Division of Environmental Management accompanied by an
application fee, documentation from the parties involved, and other supporting materials as may be
appropriate. The approval of this request will be considered on its merits and may or may not be
approved.
This permit shall be effective from the date of issuance until May 31, 2000, and shall be subject to
the conditions and limitations as specified therein. Please pay particular attention to the monitoring
requirements in this permit. Failure to establish an adequate system for collecting and maintaining the
required operational information will result in future compliance problems.
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the
right to request an adjudicatory hearing upon written request within thirty (30) days following receipt of
this permit. This request must be in the form of a written petition, conforming to Chapter 150B of the
North Carolina General Statutes, and filed with the Office of Administrative Hearings, P.O. Drawer
27447, Raleigh, NC 27611-7447. Unless such demands are made this permit shall be final and binding.
One set of approved plans and specifications is being forwarded to you. If you need additional
information concerning this matter, please contact NU,0'.ithe1 D::;A len at (919) 733-5083 ext. 547.
Sincerely,
A. Press Howard, J ., P.E.
cc: Wake County Health Department
Raleigh Regional Office, Water Quality Section
Environmental Design Group, P.A.
Training and Certification Unit
Facilities Assessment Unit
P.O. Box 29535, Raleigh, North Carolina 27626-0535 Telephone 919-733-5083 FAX 919-733-9919
An Equal opportunity Affirmative Action Employer 50% recycled/ 10% post -consumer paper
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT, HEALTH AND NATURAL RESOURCES
RALEIGH
SINGLE FAMILY SPRAY IRRIGATION PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as
amended, and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
Ms. Helen Wimberley
Wake County
FOR THE
construction and operation of a 480 GPD spray irrigation wastewater treatment and disposal system
consisting of a 1,000 gallon septic tank, a 1,000 gallon dosing tank, a 144 ft2 surface sand filter with a
cover, a tablet chlorinator, a 3,000 gallon storage/pump tank, and a 17,632 ft2 spray irrigation area to
serve the Wimberley Residence (Wimberley Farms, Lot #1), with no discharge of wastes to the surface
waters, pursuant to the application received March 10, 1995, and in conformity with the project plan,
specifications, and other supporting data subsequently filed and approved by the Department of
Environment, Health and Natural Resources and considered a part of this permit.
This permit shall be effective from the date of issuance until May 31, 2000, and shall be subject to
the following specified conditions and limitations:
I.
PERFORMANCE—STANDAR
Upon completion of construction and prior to operation of this permitted facility, a
certification must be received from a professional engineer certifying that the permitted
facility has been installed in accordance with this permit, the approved plans and
specifications, and other supporting materials. Mail the Certification to the Water Quality
Permits and Engineering Unit, P.O. Box 29535, Raleigh, NC 27626-0535.
2. The Raleigh Regional Office, telephone number (919) 571-4700, shall be notified at least
forty-eight (48) hours in advance of operation of the installed facilities so that an in-place
inspection can be made. Such notification to the regional supervisor shall be made during
the normal office hours from 8:00 a.m. until 5:00 p.m. on Monday through Friday,
excluding State Holidays.
3. The spray irrigation facilities shall be effectively maintained and operated at all times so that
there is no discharge to the surface waters, nor any contamination of ground waters which
will render them unsatisfactory for normal use. In the event that the facilities fail to
perform satisfactorily, including the creation of nuisance conditions or failure of the
irrigation area to adequately assimilate the wastewater, the Permittee shall take immediate
corrective actions including those actions that may be required by the Division of
Environmental Management, such as the construction of additional or replacement
wastewater treatment and disposal facilities.
4. The issuance of this permit shall not relieve the Permittee of the responsibility for damages
to surface or groundwaters resulting from the operation of this facility.
5. The sand media of the surface sand filter must comply with the Division's sand
specifications. The engineer's certification will serve as evidence that these specifications
have been met.
6. A leakage test shall be performed on the septic tank and dosing tank to insure that any
exfiltration occurs at a rate which does not exceed twenty (20) gallons per twenty-four (24)
hours per 1,000 gallons of tank capacity. The engineer's certification will serve as proof of
compliance with this condition.
7. If excavation into bedrock is required for the installation of the septic tank or sand filter, the
pit shall be lined with a 10 mil synthetic liner.
8. A sanitary tee shall be installed on the influent pipe of the septic tank. The engineer's
certification will serve as evidence that these specifications have been met.
9. The residuals generated from these treatment facilities must be disposed in accordance with
General Statute 143-215.1 and in a manner approved by the North Carolina Division of
Environmental Management.
10. Diversion or bypassing of the untreated wastewater from the treatment facilities is
prohibited. '
11. The following buffers shall be maintained:
a) 400 feet between wetted area and any residence or places of public assembly under
separate ownership,
b) 150 feet between wetted area and property lines,
c) 100 feet between wetted area and wells,
d) 100 feet between wetted area and drainageways or surface water bodies,
e) 50 feet between wetted area and public right of ways,
f) 100 feet between treatmenttstorage units and any wells, and
g) 50 feet between treatment units and property lines.
II. OPERATION AND MAINTENANCE REQUIREMENT
1. The facilities shall be properly maintained and operated at all times.
2. Upon classification of the facility by the Certification Commission, the Permittee shall
employ a certified wastewater treatment plant operator to be in responsible charge (ORC) of
the wastewater treatment facilities. The operator must hold a certificate of the type and
grade at least equivalent to or greater than the classification assigned, to the wastewater
treatment facilities by the Certification Commission. The Permittee must also employ a
certified back-up operator of the appropriate type and grade to comply with the conditions
of Title 15A, Chapter 8A, .0202. The ORC of the facility must visit each Class I facility at
least weekly and each Class H, III, and IV facility at least daily, excluding weekends and
holidays, and must properly manage and document daily operation and maintenance of the
facility and must comply with all other conditions of Title 15A, Chapter 8A, .0202. Once
the facility is classified, the Permittee must submit a letter to the Certification Commission
which designates the operator in responsible charge within thirty days after the wastewater
treatment facilities are 50% complete.
3. A suitable vegetative cover shall be maintained.
4. Irrigation shall not be performed during inclement weather or when the ground is in a
condition that will cause runoff.
2
5 . Adequate measures shall be taken to prevent wastewater runoff from the spray field.
6. The application rate shall not exceed 15.9 inches per year at an instantaneous application
rate not to exceed 0.2 inches per hour.
7. The facilities shall be effectively maintained and operated as a non -discharge system to
prevent the discharge of any wastewater resulting from the operation of this facility.
8. No type of wastewater other than that from the Wimberley Residence (Wimberley Farms,
Lot #1) shall be sprayed onto the irrigation area.
9. In the event that the sprinkler heads fail to achieve the design diameter of 60 feet due to
obstructions, the obstructions shall be removed or the sprinkler heads shall be raised and
supported to such height that the design diameter is achieved.
10. No traffic or equipment shall be allowed on the disposal area except while installation
occurs or while normal maintenance is being performed.
11. The Permittee is responsible for the operation and maintenance of the entire treatment and
disposal system including, but not limited to, the following items:
a. The septic tank shall be checked annually and pumped out as needed.
b. The tablet chlorinator shall be checked every week. Tablets shall be added so as to
provide proper chlorination.
c. The storage, pump, and alarm systems shall be inspected weekly. The scum layer shall
be removed at the same interval as the septic tank is cleaned out.
d. The spray system shall be inspected weekly to make certain of the sprayers proper
operation, that the vegetative growth allows a proper spray pattern, that the soil is
assimilating the disposed treated wastewater with no surface runoff, and that no
objectionable odors are being generated.
III. MONITORING AND REPORTING REQUIREMENTS
Any monitoring deemed necessary by the Division of Environmental Management to insure
surface and ground water protection will be established and an acceptable sampling
reporting schedule shall be followed.
2. The Permittee shall maintain records of all maintenance performed on the system and
irrigation area, as required in Condition II 10 for a minimum of five years. This
information shall be provided to the Division of Environmental Management upon request.
3. Noncompliance Notification:
The Permittee shall report by telephone to the Raleigh Regional Office, telephone number
(919) 571-4700, as soon as possible, but in no case more than 24 hours or on the next
working day following the occurrence or first knowledge of the occurrence of any of the
following:
a. Any process unit failure, due to known or unknown reasons, that renders the facility
incapable of adequate wastewater treatment, such as mechanical or electrical failures of
pumps, spray heads, etc.; or
b. Any failure of a pumping station or treatment facility resulting in a by-pass directly to
receiving waters without treatment of all or any portion of the influent to such station or
facility.
Persons reporting such occurrences by telephone shall also file a written report in letter
form within 15 days following first knowledge of the occurrence. This report must outline
the actions taken or proposed to be taken to ensure that the problem does not recur.
IV. INSPECTIONS
1. Adequate inspection, maintenance, and cleaning shall be provided by the Permittee to
insure proper operation of the subject facilities.
2. Any duly authorized officer, employee, or representative of the Division of Environmental
Management may, upon presentation of credentials, enter and inspect any property,
premises or place on or related to the disposal site or facility at any reasonable time for the
purpose of determining compliance with this permit, may inspect or copy any records that
must be maintained under the terms and conditions of this permit, and may obtain samples
of groundwater, surface water, or leachate.
V. GENERAL CONDITIONS
This permit shall become voidable unless the facilities are constructed in accordance with
the conditions of this permit, the approved plans and specifications, and other supporting
data.
2. This permit is effective only with respect to the nature and volume of wastes described in
the application and other supporting data.
3. This permit is not transferable. In the event there is a desire for the facilities to change
ownership, or there is a name change of the Permittee, a formal permit request must be
submitted to the Division of Environmental Management accompanied by an application
fee, documentation from the parties involved, and other supporting materials as may be
appropriate. The approval of this request will be considered on its merits and may or may
not be approved.
4. Upon the availability of a municipal or regional sewerage collection system, the subject
wastewater treatment facilities shall be abandoned and all wastewater discharged into the
municipal or regional sewerage system.
5. The spray irrigation field shall be fenced with at least a two strand wire fence.
6. Failure to abide by the conditions and limitations contained in this permit may subject the
Permittee to an enforcement action by the Division of Environmental Management in
accordance with North Carolina General Statute 143-215.6(a) to 143-215.6(c).
7. The issuance of this permit does not preclude the Permittee from complying with any and
all statutes, rules, regulations, or ordinances which may be imposed by other government
agencies (local, state, and federal) which have jurisdiction.
8. This permit may be revoked if the Permittee fails to abide by the conditions of the
"Operation and Maintenance Agreement" previously signed by the Permittee.
9. A set of approved plans and specifications for the subject project must be retained by the
Permittee for the life of the project.
4
10. The Permittee, at least six (6) months prior to the expiration of this permit, shall request its
extension. Upon receipt of the request, the Commission will review the adequacy of the
facilities described therein, and if warranted, will extend the Permit for such period of time
and under such conditions and limitations as it may deem appropriate.
Permit issued this the nineth day of June, 1995
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
' l
A. Presto oward, Jr., P.P.', Director
Division ofEnvironmental Management
By Authority of the Environmental Management Commission
Permit Number WQ0010736
Permit No. WQ0010736
June 9, 1995
I, , as a duly registered Professional Engineer in the State of North
Carolina, having been authorized to observe (periodically, weekly, full time) the construction of the
project, , for the
Project Name Location
Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation
of the construction such that the construction was observed to be built within substantial compliance and
intent of this permit, the approved plans and specifications, and other supporting materials.
Signature
Date
0
Registration No.
NPDES FACILITY AND PERMIT DATA 06/08/95 12:36:29
UPDATE OPTION TRXID 5NU KEY NCG170114
PERSONAL DATA FACILITY APPLYING FOR PERMIT
FACILITY NAME> STONECUTTER MILLS CORP. COUNTY> RUTHERFORD
ADDRESS: MAILING [REQUIRED) LOCATION (REQUIRED)
STREET: 300 DALLAS ST STREET: OXFORD STREET
CITY: SPINDALE ST NC ZIP 28160 CITY: SPINDALE ST
TELEPHONE 704 286 2341 DATE FEE PAID: 02/23/95 AMOUNT:
STATE CONTACT) EVANS PERSON IN CHARGE KIM WARNER
1=PROPOSED,2=EXIST,3=CLOSED 1 1=MRJOR,2=MINOR 2 1=MUN,2=NON-MUN
LAT: 3521530 LONG: 08155550 N=NEW,M=MODIFICATION,R=REISSUE> N
DATE APP RCVD 02/23/95 WASTELOAD REQS ! /
DATE STAFF REP REQS 03/23/95 WRSTELOAD RCVD
DATE STAFF REP RCVD 04/10/95 SCH TO ISSUE
DATE TO P NOTICE / / DATE DRAFT PREPARED 06/07/95
DATE OT AG COM REQS / / DATE DENIED ! !
DATE OT AG COM RCVD / / HATE RETURNED
REGION
01
NC ZIP 28160
400.00
2
DATE TO EPA ! ! DATE ISSUED ! / ASSIGN/CHANGE PERMIT
DATE FROM EPA t / EXPIRATION DATE / !
FEE CODE C 0 ) 1=C>IOMGD),2=()1MGD),3=(>0.1MGD),4=(<0,1MGD),5=SF,6=(GP25,64,79),
7=(GP49,73)B=CGP76)9=(GP13,34,30,52)0=CNOFEE) DIS/C 73 CONBILL C )
COMMENTS:
MESSAGE:* DATA MODIFIED SUCCESSFULLY*«
OPERATION AND MAINTENANCE AGREEMENT FOR THE
DIVISION OF ENVIRONMENTAL MANAGEMENT
Name: Pl e-1CN S WIM bar
Address: 3 .5{,-ee-f
City: State: AJ ZIP: __. -75"� I
Single Family Residence Wastewater Treatment System
Final Disposal by Spray Irrigation
Permit No.
a County
I agree to operate and maintain the wastewater treatment system as follows:
1. The Permittee is responsible for the operation and maintenance of the entire treatment and
disposal system including, but not Limited to, the following items:
a. The septic tank shall be checked every six (6) months and pumped out as required.
b. The tablet chlorinator shall be checked every week until the actual usage rate is established
and thence on a monthly basis. Tablets shall be added so as to provide proper chlorination.
c. The storage system, pump system, and alarm system shall be inspected monthly. The
scum layer shall be removed at the same interval as the septic tank is cleaned out.
d. The spray system shall be inspected monthly to make certain of the sprayers proper
operation, that the vegetative growth allows proper spray patterns, that the soil is absorbing
the disposed treated wastewater with no surface runoff, and that no objectionable odors are
being generated. -
2. Failure of the Permittee to properly operate this system is subject to a penalty up to $10,000 per
day.
3. Failure to meet permit conditions or violation of the State's surface or groundwater regulations
will require cessation of occupancy of the residence.
I understand that failure to comply with these conditions along with the permit conditions may result in
voiding the permit.
Signature:
Notary Seal
a� W�?ApY
Notary Signature:
S+oA,e-- o�
�p�nk,co o-�
Date: `7 -
��r N (a'a
1
Date: 3- f„^ q
' `�=�-� --� � �' .- F zoo i - i• �,f - __ _
ChD
�`�'��• t —i ti r W ; 1 jam. 6_G Tr` L y Fo- r- l�i.'� •:'j l -.jr
_ _ W'-c'f`Ci L+G� L�►L �' � a. � L� ;�: m i . . � ' ,`, � ��. f �1
� � ��— _ 4j.--- 4.JQ o0l�73-/ • ;- - ;.�- � Friendstrip'�,�'y . '
i h(Qoo /074-v
j — Wa oo I v 74-1
77
- - �' ` . _. - - ' _.` - _ _ _- - .... �=.y�,YC- Farrar r� J ' •�� , '\'`- _ _
loll fes- 1/� _ _ — • ••! _ l ..
SIN; — 'w� �' _ r , ` +\`_ �� _~ _ - r - - .a= �•^
-70
Lana
.r ' - meg' -.� ` + • �-.`.• `r .•2 � �_ ++ � ^ - - ! �• � f � -�/ ' .. ..- ~'
.14
• � Jf�' - , '� �Y �_ � ,t. �, tel{/' �
• _ - - l �— � 1ST � ~ . � � _ / ■ � � �� ��z�
RATING SCALE'FOR CLASSIFICATION OF WATER POLLUTION CONTROL SYSTEMS
game of Facility: Gt1 n ' 4--d:�'T
C er or Contact Person.- Mme.- �LG� L in..bcrlcv
K ng -Address::-f_. /3 L"t :5rrz f _.._...... tea, _/VG
County: Telephone:
Present Classifjcation: New Facility`Existing Facility
•NPDLS -Per.- No- NC00 Nondisc. Per. No.WQc+a1oZ3/ Health Dept.Per No.
Rated by: T'12�4 4z:) rLG5 _ Telephone: ,67/ *70 - Dater -9S
Reviewed by: Health Dept. Telephone:
Regional Office Telephone:
Central Office Telephone:
OP,C: Grade: Telephone:
Check Classirication(s): Subsurface v-"� Spray Irrigation Land Application
Wastewater Classification: (Circle One) I 'il - Ill IV Total Points:
f►9: alt :♦ .\Ila• �•. �►1 ■ ,�.:: a \N+ : • ► 1 � 1: � :. ►s
SL83SURFACE CLAS- IF1CATON
(check all
units that apply)
1.
septic tanks
2.
pump lanls
3-
siphon or pump dosing systems
4.
sand fillers
5. —grease
Irap/interceptor
E
oil/water separalors
7.
gravity subsurface treatment and disposaf:
8.
pressure subsurface treatment and disposal:
--------------------------------
S PPAIRRiGAmNCLASsFcATYYJ
(check all units that apply)
1. preiiminary treatment (definition no. 32 }
2. lagoons
3. septic tanks
4, pump tanks
5. ✓ pumps
6. ✓ sand fillers
7. grease Irao/inlerceptor
e. oil/water separators
9.�disinlection
10, chemical addition for nulrient/algae control
11. \!spray irn'galicn'ol wastewater
In addition to the - above classifications, pretreatment of wastewater in excess of these components .shale
be rated using the point rating system end will require an operator with an appropriate dual certification..
LANG APPLICATION/RESIDUALS CLASSIFICATION (Applies only to permit holder) 7.
1. Land application of Fosolids, residuals or conlaninaled soils on a desfgnaled site.
---------------------------
WASTEWA TERTRFATMEM FACILITY CIASSlFICATiCN
The following systems shall be assigned a Class I classilicalion, Ud!!!;g the flow is of a significant quantity or the technology is unusually
complex, to require consideration by the Commission on a case-by-mse basis: (Check if Appropriate)
1. OiVwater Separalor Systems consisting only of physical separation, pumps and disposal;
2• Septic Tank/Sand Filler Systems consisting only of septic tanks, dosing apparatus, pumps,sand fillers, disWe-clion
and direct discharge;
3. Lagoon Systems consisting only of preliminary treatment, lagoons, pumps, disinfection, necessary chemical treatment for
algae or nutrient control, and direct discharge;
4. Closed-loop Recycle Systems;
5. Groundwater Remediation Systems consisting only of oil/waler separators,- pumps, air -stripping, carbon adsorption, disinfeCion
and dispo zl: 7
&. Aquaculture operations wilh discharge to surface waters;
7. Wa!er Plant sludge handling and back -wash wa!er treatment;
9. _Seaf-c-d processing consisting of screening and disposal.
5 _Single_fami!y discharging systems, with the eaceplion of Aerobic Treatment units, will oe classified if perrnin;�, a!!er July 1,
7493 or ii upon inspection by the Division, it is Lound that the system is not being adequately operated or main) nod. su=1i
systems wall be notified of the classification or reclassification by tho Commission, in writing.
70
r�