HomeMy WebLinkAboutWQ0003426_Final Permit_19950331State of North Carolina
Department of Environment,
Health and Natural Resources
Division of Environmental Management
James B. Hunt, Jr., Governor
Jonathan B. Howes, Secretary
A. Preston Howard, Jr., P.E., Director
March 31, 1995
Mr. Steven F. Adams
1511 Altamahaw-Union Ridge Road
Burlington, North Carolina 27217
LT.R?FA/•
� IL
ED FE Fl
Subject: Permit No. WQ0003426
Steven F. Adams
Single Family Wastewater
Spray Irrigation Facility
Alamance County
Dear Mr. Adams:
In accordance with your application received January 3, 1995, we are forwarding herewith Permit
No. WQ0003426 dated March 31, 1995, to Mr. Steven F. Adams for the construction operation of the
subject single family wastewater treatment and spray irrigation facilities. It is understood that the subject
wastewater treatment system is not constructed at this time. Please notice that upon completion of
construction of the subject system an engineers certification must be provided to the Division, in
accordance with this permit and State Regulations.
This permit shall be effective from the date of issuance until March 31, 2000, and shall be subject
to the conditions and limitations as specified therein. Please pay particular attention to the monitoring
requirements in this permit. Failure to establish an adequate system for collecting and maintaining the
required operational information will result in future compliance problems. Issuance of this permit hereby
voids Permit No. WQ0003426 issued June 29, 1990.
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the
right to request an adjudicatory hearing upon written request within thirty (30) days following receipt of
this permit. This request must be in the form of a written petition, conforming to Chapter 150B of the
North Carolina General Statutes, and filed with the Office of Administrative Hearings, P.O. Drawer
27447, Raleigh, NC 27611-7447. Unless such demands are made this permit shall be final and binding.
One set of approved plans and specifications was forwarded to you in the original issuance of this
permit. If you need additional information concerning this matter, please contact Mr. John Seymour at
(919) 733-5083 ext. 546.
Sincerely,
nz�QL
A. Prest Howard, Jr., P.E.
cc: Alamance County Health Department
Winston-Salem Regional Office, Water Quality Section
Facilities Assessment Unit
Simmons Engineering & Surveying, Inc.
P.O. Box 29535, Raleigh, North Carolina 27626-0535 Telephone 919-733-5083 FAX 919-733-9919
An Equal Opportunity Affirmative Action Employer 50% recycled/ 10% post -consumer paper
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT, HEALTH AND NATURAL RESOURCES
RALEIGH
SINGLE FAMILY SPRAY IRRIGATION PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as
amended, and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
Mr. Steven F. Adams
Alamance County
FOR THE
construction and operation of a 480 GPD spray irrigation wastewater treatment and disposal system
consisting of a 1,000 gallon baffled septic tank, a 420 ft2 subsurface sand filter (6 feet by 70 feet), a tablet
chlorinator with a 73 gallon chlorine contact chamber, two (2) 1,200 gallon storage/pump tanks with
appropriate pump (22 gpm), a spray irrigation area with five (5) sprinklers (with 3/16 inch nozzles) as
shown by the approved plans, and all associated piping, valves, controls, and appurtenances to serve the
Steven F. Adams Residence, with no discharge of wastes to the surface waters, pursuant to the renewal
application received January 3, 1995, the approved plans, in the original application received April 18,
1990, and in conformity with the project plan, specifications, and other supporting data subsequently filed
and approved by the Department of Environment, Health and Natural Resources and considered a part of
this permit.
This permit shall be effective from the date of issuance until March 31, 2000, and shall be subject
to the following specified conditions and limitations:
I. PERFORMANCE STANDARDS
1. Upon completion of construction and prior to operation of this permitted facility, a
certification must be received from a professional engineer certifying that the permitted
facility has been installed in accordance with this permit, the approved plans and
specifications, and other supporting materials. Mail the Certification to the Water Quality
Permits and Engineering Unit, P.O. Box 29535, Raleigh, NC 27626-0535. .
2. The Winston-Salem Regional Office, telephone number 910/ 771-4600 shall be notified at
least forty-eight (48) hours in advance of operation of the installed facilities so that an in -
place inspection can be made. Such notification to the regional supervisor shall be made
during the normal office hours from 8:00 a.m. until 5:00 p.m. on Monday through Friday,
excluding State Holidays.
3. The spray irrigation facilities shall be effectively maintained and operated at all times so that
there is no discharge to the surface waters, nor any contamination of ground waters which
will render them unsatisfactory for normal use. In the event that the facilities fail to
perform satisfactorily, including the creation of nuisance conditions or failure of the
irrigation area to adequately assimilate the wastewater, the Permittee shall tape immediate
corrective actions including those actions that may be required by the Division of
Environmental Management, such as the construction of additional or replacement
wastewater treatment and disposal facilities.
4. The issuance of this permit shall not relieve the Permittee of the responsibility for damages
to surface or groundwaters resulting from the operation of this facility.
5. The sand media of the subsurface sand filter must comply with the Division's sand
specifications. The engineer's certification will serve as evidence that these specifications
have been met.
6. A leakage test shall be performed on the septic tank and dosing tank to insure that any
exfiltration occurs at a rate which does not exceed twenty (20) gallons per twenty-four (24)
hours per 1,000 gallons of tank capacity. The engineer's certification will serve as proof of
compliance with this condition.
7. If excavation into bedrock is required for the installation of the septic tank or sand filter, the
pit shall be lined with a 10 mil synthetic liner.
8. The residuals generated from these treatment facilities must be disposed in accordance with
General Statute 143-215.1 and in a manner approved by the North Carolina Division of
Environmental Management.
9. Diversion or bypassing of the untreated wastewater from the treatment facilities is
prohibited.
10. The following buffers shall be maintained:
a) 400 feet between wetted area and any residence or places of public assembly under
separate ownership,
b) 150 feet between wetted area and property lines,
c) 100 feet between wetted area and wells,
d) 100 feet between wetted area and drainageways or surface water bodies,
e) 50 feet between wetted area and public right of ways,
f) 100 feet between treatmentfstorage units and any wells, and
g) 50 feet between treatment units and property lines.
Some of the buffers specified above may not have been included in previous permits for
this waste treatment and disposal system. These buffers are not intended to prohibit or
prevent modifications, which are required by the Division, to improve performance of the
existing treatment facility. These buffers do, however, apply to modifications of the
treatment and disposal facilities which are for the purpose of increasing the flow that is
tributary to the facility. These buffers do apply to any expansion or modification of the
spray irrigation areas and apply in instances in which the sale of property would cause any
of the buffers now complied with, for the treatment and disposal facilities, to be violated.
= The applicant is advised that any modifications to the existing facilities will require a permit
modification.
H. OPERATION ANDMAINTENANCE REQUIREMENTS
1. The facilities shall be properly maintained and operated at all times.
2. A suitable vegetative cover of the spray field shall be maintained.
3. Irrigation shall not be performed during inclement weather or when the ground is in a
condition that will cause runoff.
4. Adequate measures shall be taken to prevent wastewater runoff from the spray field.
5. The application rate shall not exceed 15.6 inches per year at an instantaneous application
rate not to exceed 0.2 inches per hour.
2
6. The facilities shall be effectively maintained and operated as a non -discharge system to
prevent the discharge of any wastewater resulting from the operation of this facility.
7. No type of wastewater other than that from the Steven F. Adams Residence shall be
sprayed onto the irrigation area.
8. In the event that the sprinkler heads fail to achieve the design diameter due to obstructions,
the obstructions shall be removed or the sprinkler heads shall be raised and supported to
such height that the design diameter is achieved.
9. No traffic or equipment shall be allowed on the disposal area except while installation
occurs or while normal maintenance is being performed.
10. The Permittee is responsible for the. operation and maintenance of the entire treatment and
disposal system including, but not limited to, the following items:
a. The septic tank shall be checked annually and pumped out as needed.
b. The tablet chlorinator shall be checked every week. Tablets shall be added so as to
provide proper chlorination.
c. The storage, pump, and alarm systems shall be inspected weekly. The scum layer shall
be removed at the same interval as the septic tank is cleaned out.
d. The spray system shall be inspected weekly to make certain of the sprayers proper
operation, that the vegetative growth allows a proper spray pattern, that the soil is
assimilating the disposed treated wastewater with no surface runoff, and that no
objectionable odors are being generated.
111. MONITORING AND REPORTING REQUIREMENTS
1. Any monitoring deemed necessary by the Division of Environmental Management to insure
surface and ground water protection will be established and an acceptable sampling
reporting schedule shall be followed.
2. The Permittee shall maintain records of all maintenance performed on the system and
irrigation area, as required in Condition H 10 for a minimum of five years. This
information shall be provided to the Division of Environmental Management upon request.
3. Noncompliance Notification:
The Permittee shall report by telephohe_to the Winston-Salem Regional Office, telephone
number 910/ 771-4600 as soon as possible, but in no case more than 24 hours or on the
next working day following the occurrence or first knowledge of the occurrence of any of
the following:
a. Any process unit failure, due to known or unknown reasons, that renders the facility
incapable of adequate wastewater treatment, such as mechanical or electrical failures of
pumps, spray heads, etc.; or
b. Any failure of a pumping station or treatment facility resulting in a by-pass directly to
receiving waters without treatment of all or any portion of the influent to such station or
facility.
Persons reporting such occurrences by telephone shall also file a written report in letter
form within 15 days following first knowledge of the occurrence. This report must outline
the actions taken or proposed to be taken to ensure that the problem does not recur.
IV. INSPECTIONS
1. Adequate inspection, maintenance, and cleaning shall be provided by the Permittee to
insure proper operation of the subject facilities.
2. Any duly authorized officer, employee, or representative of the Division of Environmental
Management may, upon presentation of credentials, enter and inspect any property,
premises or place on or related to the disposal site or facility at any reasonable time for the
purpose of determining compliance with this permit, may inspect or copy any records that
must be maintained under the terms and conditions of this permit, and may obtain samples
of groundwater, surface water, or leachate.
V . GENERAL CONDITIONS
1. This permit shall become voidable unless the facilities are constructed in accordance with
the conditions of this permit, the approved plans and specifications, and other supporting
data.
2. This permit is effective only with respect to the nature and volume of wastes described in
the application and other supporting data.
3. This permit is not transferable. In the event there is a desire for the facilities to change
ownership, or there is a name change of the Permittee, a formal permit request must be
submitted to the Division of Environmental Management accompanied by an application
fee, documentation from the parties involved, and other supporting materials as may be
appropriate. The approval of this request will be considered on its merits and may or may
not be approved.
4. Upon the availability of a municipal or regional sewerage collection system, the subject
wastewater treatment facilities shall be abandoned and all wastewater discharged into the
municipal or regional sewerage system.
5. The spray irrigation field shall be fenced with at least a two strand wire fence.
6. Failure to abide by the conditions and limitations contained in this permit may subject the
Permittee to an enforcement action by the Division of Environmental Management in
accordance with North Carolina General Statute 143-215.6(a) to 143-215.6(c).
7. The issuance of this permit does not preclude the Permittee from complying with any and
all statutes, rules, regulations, or ordinances which may be imposed by other government
agencies (local, state, and federal) which have jurisdiction.
8. This permit may be revoked if the Permittee fails to abide by the conditions of the
"Operation and Maintenance Agreement" previously signed by the Permittee.
9. A set of approved plans and specifications for the subject project must be retained by the
Permittee for the life of the project.
10. The Permittee, at least six (6) months prior to the expiration of this permit, shall request its
extension. Upon receipt of the request, the Commission will review the adequacy of the
facilities described therein, and if warranted, will extend the Permit for such period of time
and under such conditions and limitations as it may deem appropriate.
4
11. Issuance of this permit hereby voids Permit No. WQ0003426 issued June 29, 1990.
Permit issued this the 31st day of March, 2000
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
A. Preston oward, Jr., P. ., irector
Division o nvironmental Management
By Authority of the Environmental Management Commission
Permit Number WQ0003426
RATING SCALE FOR CLASSIFICATION OF WATER POLLUTION CONTROL SYSTEMS
Name of Facility: -5L:ye-.,, %�-CI... -r
Owner or Contact Person: S' ip LIP ", '�&CV� r-.
Mailing Address: /J-// 4 /Ti '1-'"7 uz - .ta'�5
T^
County: c Tefephone:�9'/6)
Present Cfasslfleatlon: New Facility '- ^Existing Faciilty
NPDES Per. c� . NC00 Nondisc. Per. No.WC rLr��4�1 LHealth Dept.Per No.
Rated by: — Tefephono: Y' 4�
Reviewed b�: _ __ r.. „Health Dept. Telephone:
Regional Office Telephone:
Central Office Telephone:
ORC: Grade: Telephone:
Check Classification(s): Subst--' _9 Spray Irrigation Land Application
Wastewater Classification: (Circle Ono f 11 III IV Total Paints:
w : ►1 ' :�s. :,► � : � .: 1 � � ►il:if, .!; ru �►1 u■ .r■ : :.a 1►11�. :1 •. I► � ." ll:: �Ci� • 1 � •
���. s : � a .. 1 1: . LE s►1 sue: 1■I i : �i. � . ii... 4S• ! JI.. �a� !`71-�. ��a . ylti. �►: � JI. :•r.
:.► :: Il 1 Il: • .. 1 A i ::. 'm u1-11 WIM-1 I a W.1 11111-
SUBSURFACE CLASSIFICATION
(check all units that apply)
1. septic tanks
2. pump tanks
3. siphon or pump -dosing systems
4. sand filters
5. • grease trapAnterceptor
6� ,.oil/water separators
7. gravNy subsurface treatment and disposal:
B. pressure subsurface treatment and disposal
SPRAY IRRiGgTICN CLASSIFICATION
(check all units that apply)
1. preliminary treatment (definition no. 32 )
2._ iagoons
3 aseptic tanks
4.^ � pump tanks
5. pumps
S.=sand litters
7. grease traprinterceptor
e. oil/water separators
9 Ldisinfection
10. chemical addition for nutrienYalgae control
11.__;,=:,spray irrigation of wastewater
In addition to the above classifications, pretreatment of wastewater in excess of these components shall
be rated using the point rating system and will require an operator with an appropriate dual certification.
LANd APPLICATIONIRESIDUALS CLASSIFICATION (Applies only to permit holder)
1. Land application of biosolids, residuals or contaminated soils on a designated site.
WASTEWATER TREATMENT T FACILITY CLASSIFICATION
The following systems shaft be assigned a Class I classification, unless flow is of a significant quantity or the technology is unusually
complex, to require consideration by the Commission on a case -by -case basis. (Check d Appropriate)
1. al/water Separator Systems consisting only of physical separation, pumps and disposal;
2. Septic Tank/Sand Fifter Systems consisting only of septic tanks, dosing apparatus, pumps,sand fillers, disinfection
and direct discharge;
3. Lagoon Systerus consisting only of preliminary treatment, lagoons, pumps, disinfection, neoessary chemical treatment for
algae or nutrient control, and direct discharge;
4. Closed -loop Recycle Systems;
5. Groundwater Remediation Systems consisting only of oilfwater separators, pumps, air -stripping, carbon adsorption, disinfection
and disposd;
fi. Aquacuhure operations with discharge to surface waters;
7ti___,_Water Plant sludge handling and back -wash water treatment;
8. Seafood processing consisting of screening and disposal.
9. Single-family discharging systems, with the exception of Aerobic Treatment Units, will be classified if permitted after July 1,
1993 or if upon inspection by the Division, It Is found that the system Is not being adaquslely operated or maintained. Such
systems will be notified of the classification or reclassification by the Commission, in writing.
� � Y
/ 1 �
=tea
6 � _ ��`••i/l ` T'' �Vr� r Rom' ,�• ��(� r1 .
'_ ram_• ,, ��' D~ ����4���� - �. ,
JET`: - \ �'�it— �1 f/D - {,/Fp� .r.r'',� �, �I l t ••.� % 'io 1{ T
I
J \ Nq1 C � � `� • O � J• �' 1
y I t �� ���• � O tc.
' ` 'D t _ 11 f/ /V--J/ j� ..� ���L'e'11 y5 f 7•'� �_% !
1
Permit No. WQ0003426
March 31, 1995
Lgaolaoj
1, , as a duly registered Professional Engineer in the State of North
Carolina, having been authorized to observe (periodically, weekly, full tune) the construction of the
project,
Project Name
Location
for the
Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation
of the construction such that the construction was observed to be built within substantial compliance and
intent of this permit, the approved plans and specifications, and other supporting materials.
Signature Registration No.
Date
0