SECTIONS
NTS
ACCESS DRIVE SECTION NTS
3-INCH ABC STONE (COMPACTED
IN PLACE AND PROOF-ROLLED)
YARD SECTION
3-INCH #57 STONE
COMPACTED STRUCTURAL FILL WHERE
REQUIRED TO 98%
12-INCH ABC STONE (COMPACTED IN PLACE AND
PROOF-ROLLED). PLACE IN SEPARATE 2 EQUAL
6-INCH THICK LIFTS. INSTALL 6-INCH DEPTH
DURING INITIAL GRADING OPERATIONS, AND
INSTALL REMAINING 6-INCH DEPTH DURING FINE
GRADING OPERATIONS.
3-INCH ABC STONE (COMPACTED IN PLACE
AND PROOF-ROLLED) (SUBGRADE)
GRAVEL YARD
GATE
EDGE OF STONE
EDGE OF
GRADE/EDGE
OF ABC STONE
SHOULDER
FENCE
EDGE OF ABC DRIVE
SECTION C-C
1" = 10' HORIZ.
1" = 1' VERT.
3" #57 STONE ON TOP OF
3" ABC STONE ON TOP OF
3" ABC STONE SUBGRADE
GRASS
15'
FENCE
X
X
X
6' OUTSIDE FENCE
GRAVEL YARD
3" COMPACTED ABC
STONE (SUBGRADE)
1
30
1
6
3" COMPACTED ABC
STONE
3" #57 STONE
12" ABC STONE
ACCESS DRIVE
ABC STONE TO TRANSITION
FROM ACCESS DRIVE
ELEVATION TO GRAVEL YARD
FINISHED GRADE ELEVATION
COMPACTED
SUBGRADE
FINISHED GRADE (FG)
ELEVATION
PROFILE VIEW
PLAN VIEW
ACCESS DRIVE TRANSITION
ABC DRIVE TO GRAVEL YARD
NTS
ASPHALT PAVEMENT SECTION
3-INCH SURFACE COURSE ASPHALT
PAVEMENT (S9.5B). PLACE IN 2 EQUAL
1.5-INCH THICKNESS LIFTS.
8-INCH ABC STONE (COMPACTED IN
PLACE AND PROOF-ROLLED)
COMPACTED SUBGRADE TO 100%
FOR UPPER 8-INCHES AND 95%
BELOW UPPER 8-INCHES
COMPACTED SUBGRADE TO 98%
COMPACTED STRUCTURAL FILL WHERE
REQUIRED TO 98%
COMPACTED SUBGRADE TO 98%
SUBGRADE (SG)
APP.CK.BY
LOCATION
SCALE
DRAWN
DATE
CHK.
DWG. NO.
APP.
SCALE RATIO 1:1
MM JSS
NO.DATE REVISION
AS NOTED
RDC-73163 SHT OF 17
HARNETT COUNTY, NORTH CAROLINA
LINDEN 230kV SUBSTATION
801 JONES FRANKLIN RD, SUITE 300
RALEIGH, NC 27606
(919)851-6866
(919) 851-7024 FAX
LICENSE # F-0672
PROJECT NUMBER: 178451074
05-25-2018
CALL 1-800-632-4949
IT'S THE LAW !
BEFORE YOU DIG !
RSJ100% SUBMITTAL FOR PERMITTING
NOT FOR CONSTRUCTION
NTS
SHOULDER/PERIMETER
DRIVE/LAYDOWN AREA SECTION
COMPACTED STRUCTURAL FILL WHERE
REQUIRED TO 98%
6-INCH ABC STONE (COMPACTED IN
PLACE AND PROOF-ROLLED).
COMPACTED SUBGRADE TO 98%
160N NONWOVEN POLYPROPYLENE
GEOTEXTILE PRODUCT FROM MIRAFI OR
APPROVED EQUAL.
ABC STONE
20'
6'
6'
6'
GRASS
15'
NTS
4-INCH #4 WASHED STONE WITH LESS THAN 2.0% FINES PASSING
THE ASTM NO. 200 SIEVE, COORDINATE DELIVERY OF WASHED
STONE WITH DUKE ENERGY IN ORDER TO VERIFY STONE HAS
BEEN WASHED
STONE DITCH SECTION
6-INCH CLEAN WASHED SAND
SUBGRADE (UNCOMPACTED), SCARIFY THE SURFACE OF
THE SUBGRADE WITHIN STONE DITCH AREA TO FACILITATE
INFILTRATION
PROVIDE GRASS SEED AS AN EXPERIMENT TO TRY AND GET
GRASS TO GROW WITHIN STONE DITCH AREA, COORDINATE WITH
DUKE ENERGY
NOTES:
CLEAR AND EXCAVATE THE AREA OF THE STONE DITCH WHILE PROTECTING AND MAINTAINING
SUBGRADE INFILTRATION RATES FOLLOWING THESE STEPS:
1.EXCAVATE IN DRY SUBGRADE CONDITIONS AND AVOID EXCAVATING IMMEDIATELY AFTER
STORMS WITHOUT A SUFFICIENT DRYING PERIOD.
2.DO NOT ALLOW EQUIPMENT TO CROSS THE STONE DITCH AREA AFTER EXCAVATION HAS
BEGUN. OPERATE EXCAVATION EQUIPMENT FROM OUTSIDE THE STONE DITCH AREA OR
FROM UNEXCAVATED PORTIONS OF THE AREA USING AN EXCAVATION STAGING PLAN.
3.USE EQUIPMENT WITH TRACKS RATHER THAN TIRES TO MINIMIZE SOIL COMPACTION WHEN
EQUIPMENT ON THE SUBGRADE SURFACE IS UNAVOIDABLE.
4.DIG THE FINAL 9 TO 12 INCHES BY USING THE TEETH OF THE EXCAVATOR BUCKET TO
LOOSEN SOIL AND DO NOT SMEAR THE SUBGRADE SOIL SURFACE. FINAL GRADING OR
SMOOTHING OF THE SUBGRADE SHOULD BE DONE BY HAND IF POSSIBLE.
5.MINIMIZE THE TIME BETWEEN EXCAVATION AND PLACEMENT OF THE SAND AND STONE
AGGREGATE.
THE FINAL SUBGRADE SLOPE SHALL NOT EXCEED 0.5%. THE SLOPE OF THE SUBGRADE SHALL
BE CHECKED BEFORE PROCEEDING. WHERE POSSIBLE, EXCAVATE SOIL FROM THE SIDES OF
THE STONE DITCH AREA TO MINIMIZE SUBGRADE COMPACTION FROM EQUIPMENT. AFTER
VERIFYING THE SUBGRADE SLOPE, SCARIFY THE SOIL SUBGRADE SURFACE APPROXIMATE 2
INCH DEPTH TO MAINTAIN THE SOIL'S PRE-DISTURBANCE INFILTRATION RATE AND POSSIBLY
IMPROVE THE SOIL'S INFILTRATION RATE. SCARIFYING THE SUBGRADE MUST OCCUR WHILE
THE SOIL IS DRY. TO SCARIFY THE SUBGRADE, USE BACKHOE BUCKET'S TEETH TO RAKE THE
SURFACE OF THE SUBGRADE .
BOTTOM WIDTH
TOTAL WIDTH (STONE)
SIDE SLOPE
SEEDED SLOPES
(TYPICAL)
1
RSJJSS17-5-18 PER DEQ REVIEW COMMENTS, CHANGED STONE SECTION
REQUIREMENTS