HomeMy WebLinkAboutNC0004812_NOV Response_20180430F�ar�
Apt -030,2018
W. Corey Basinger
Regional Supervisor
Mooresville Regional Office
610 E. Central Ave., Suite 301
Mooresville NC 28115
Subject: Notice of Violation
Compliance Evaluation Inspection
NOV-2018-PC-0124
Pharr Yarns WWTP
NPDES Permit No. NC0004812
Gaston County
Dear W. Corey Basinger,
This in response to the aforementioned Notice of Violation.
The flow meter is past due for calibration.
RECEIVED/NCDENR/DWR
MAY 0 8 2098
WOROS
MOORESVILLE REGIONAL OFFICE
We are endeavoring to find someone with required hard ware, remote control,
to calibrate this meter. It is over twenty years old and since our WWTP is going to be
decommissioned in December we feel it wouldn't be a prudent use of dollars to replace
this unit.
ORC staff must indicate maintenance work done in the facility.
This has been stressed to the operator. The ORC will now check to make sure
all maintenance records are kept correctly.
Secondary clarifier in need of maintenance, short circuiting.
The clarifier was taken off line and flow diverted to the other secondary clarifier.
We are waiting for a contractor to weld steel plates over the openings to remedy this.
Excessive amount of foam in the treatment units, with foam in the effluent sampling
location.
Foam is a constant in our treatment process as we treat dye house waste.
Although foam was noticed in the effluent sampling location no foam was observed
on the receiving stream. The WWTP is equipped to feed de-foamer to prevent foam
from entering the receiving stream.
Pharr Yarns, LLC • 100 Main Street • PO Box 1939 • McAdenville North Carolina 28101-1939 • Phone 704.824.3551
F0,
LRADIHONAIUkF INNOVATIO
The Sampler tubing was dirty and in need of replacement.
New tubing was purchased the day after the inspection and put on the sampler.
A 90 to 120 day schedule, or sooner, to replace tubing has been implemented.
In closing we at Pharr take our responsibility to the environment very seriously
and endeavor to do the right thing daily. If more information is needed or questions arise
feel free to contact me at 704-823-2397 or george.altice@pharryarns.com
Respectfully,
Geo ge Altice
Engineering Director
Pharr
Pharr Yarns, LLC • 100 Main Street • PO Box 1939 • McAdenville North Carolina 28101-1939 • Phone 704.824.3551
Jamie Davis
:rom: James Davis <j1davis012@gmai1.com>
Sent: Tuesday, May 01, 2018 10:07 AM
To: Jamie Davis
Subject: Thermometer Calibration
.aa or .AkJ i. Jr +ypnw rro.fp of Ihr u,Fje(4 JkrnwxeWr fw alf nlygttM rn,mbn�
� w�nrew f , uv rlLuLlamlr iuSjat vmp. t N!%'(rhnngaNrp Wry, mfmu NL%i Wrgr
If -*I- -NISI Nw wt W,. mime..w Jleen
Jamie Davis
'rom: James Davis <jldavis012@gmail.com>
Sent: Tuesday, May 01, 2018 10:40 AM
To: Jamie Davis
3
Jamie Davis
From: James Davis <jldavis012@gmail.com>
Sent: Tuesday, May 01, 2018 10:12 AM
To: Jamie Davis