HomeMy WebLinkAboutNC0026123_20180418_Compliance Evauluation Inspection ACROY COOPER Governor MICHAEL S.REGAN Secretary LINDA CULPEPPER Water Resources Interim Director Environmental Quality April 18,2018 City of Asheboro Attn:John N. Ogburn, Ill, City Manager P.O. Box 1106 Asheboro, NC 27204-1106 RECEIVED/DENR/DWR Subject: Compliance Evaluation Inspection APR 4 2018 Asheboro Wastewater Treatment Plant, NPDES Permit NC0026123 City of Asheboro Water Resoul ces Randolph County Permitting Section Dear Mr. Ogbum: Ron Boone of the Winston-Salem Regional Office of the NC Division of Water Resources (DWR or the Division)conducted a compliance evaluation inspection(CEI)of the Asheboro Wastewater Treatment Plant(WWTP), NPDES permit NC0026123, on March 29, 2018. The assistance and cooperation of Michael Wiseman, Operator in Responsible Charge, Michele Dawes, Technical Services Manager, Sarah Laughlin, Technical Services Specialist, Bernadine Wardlaw,Water Quality Lab Manager, and Michael Rhoney, Professional Engineer, during the inspection, was greatly appreciated. An inspection checklist is attached for your records and inspection findings are summarized below. Mr. Gary Perlmutter, of DWR's central office NPDES Unit in Raleigh, also attended the inspection for permitting purposes.The current permit was issued June 27,2012 and expired on September 30,2016.A new permit is in draft.The city must continue operating the plant in accordance with the permit that expired September 30, 2016, until a new permit is issued. Mr. Perlmutter addressed several issues that must be finalized before a final permit will be issued, including but not limited to ammonia, cyanide, metals, hardness, mercury, conductivity, and 1,4 Dioxane. Several compliance schedules will likely be needed in order to give the city time to comply with several of the new parameters/limits being considered. General Information The WWTP is located at 1032 Bonkemeyer Drive in Randleman,Randolph County,NC.The permit authorizes the City to operate this 9-million gallon per day(MGD)WWTP,which consists of the following units: • Influent pump station with two screw-lift pumps,two automatic bar screens, and grit removal system • Influent ultrasonic flow meter • Seven primary clarifiers;one 3 0 million gallon (MG)circular tank and six 1.0 MG rectangular tanks • Three 140-foot trickling filters • Four 27,024-cubic foot secondary clarifiers • Nitrification mixing/transfer pump basin • Two 2.0 MG nitnfication basins with a mixing basin, blowers, and Schreiber aeration systems • Magnesium hydroxide chemical addition system for pH and alkalinity adjustment • Three 70,333-cubic foot circular final clarifiers `Nothing Compares=, State of North Carolina I Environmental Quality 450 W Hanes Mill Road,Suite 300,Winston-Salem,North Carolina 27105 Phone.336-776-98001 FAX 336-776-9797 • Polymer chemical addition system • One Parkson Dynasand continuous flow tertiary filter • Chlorine contact chamber with sodium hypochlorite disinfection • Sodium bisulfite dechlorination • Effluent ultrasonic flow meter • Cascade aeration basin • Two 401,900 gallon anaerobic floating-top sludge digesters • Approximately 47,250 square-feet of drying beds • Sludge dewatering presses,thickener tanks, including a dissolved air floatation thickening tank, lime stabilization system, and a solids storage facility; and, • One 600 kilowatt(KW)standby power generator There is also a dumping station for septic haulers at the plant. This should be considered for inclusion in the plant descnption in the permit, but this is neither critical or required. The permit authorizes the City of Asheboro to discharge treated effluent from the plant via outfall 001 into Haskett Creek,this section of which is currently classified as Class C waters in the Cape Fear river basin. Site Review Mr.Wiseman provided Mr.Boone a tour of the entire facility Mr.Boone observed no violations,discrepancies, or areas of concern, and was impressed with the plant and the operators Several noteworthy items are listed below • Mr.Wiseman stated that all programmable logic controllers in the plant were recently replaced/upgraded. • Both influent and effluent flow devices also have staff gauges permanently mounted in the Parshall flumes for backup flow measurement in the event that the ultrasonic units fail • The effluent flow meter is calibrated at least quarterly by ISI out of Charlotte,NC;calibration records are maintained at the plant as required. The effluent flow rate displayed on the meter at the flume at 12.11 PM was 5.07 MGD, which very closely matched both the chart recorder and SCADA system recorder inside the plant control center • The 3.0 MG circular pnmary clarifier is NOT currently used for primary clarification because the additional treatment capacity is unnecessary to fully treat the plant's 3.5 MG average daily flow; rather the circular clarifier is used to store press filtrate from the sludge presses, which is then sent to the trickling filters and the rest of the treatment process. • The two 2 0 MG nitrification basins employ Schreiber diffused aeration systems,which provide 1,200 diffusers in each basin.The dissolved oxygen is maintained near 1 8 milligrams per liter(mg/I). • Sodium hypochlorite is injected at the overflow weirs of the final clarifiers to provide additional contact time and aid in reducing algal growth around the weirs and effluent channels. This provided the cleanest weirs and effluent channels that Mr. Boone has ever seen on final clanfiers. • Mr.Wiseman stated that the appropriate required replacement parts for all systems are kept on hand at the plant. • The one tertiary filter actually consists of 32 independent 2.5-micron particle sand filters. • The two anaerobic floating-top digesters are operated independently, the first thermophilically and the second mesophilically,to optimize the digestion process. • The plant's two 1.5-meter belt presses were very clean and well maintained. • The plant's drying beds are used to accept and dewater grease from local grease haulers • The plant's 600 KW generator can run the entire plant for 26 hours straight with a full tank of fuel. It is automatically started when commercial power fails. The operators exercise the generator at least monthly. The city has an emergency priority contract with Pugh Oil and they maintain the fuel tank level full,twice weekly.The generator is maintained by contractor and maintenance records are kept on file at the plant. • The city may wish to consider adding flow equalization facilities to the plant during the next plant upgrade. Documentation&Laboratory Review All documentation was reviewed including discharge monitoring reports, laboratory records, operation, maintenance, and repair records, operator visitation records, etc. All required records were readily available for inspection and all met minimum requirements Mr Wiseman and his operators,as well as Ms. Bernadine Wardlaw and the laboratory staff, have done an excellent job of documenting the operation and maintenance of the plant and laboratory operations,as required by the permit. The plant's laboratory holds DWR's lab certification number 86. The only sample the city sends out to commercial laboratones for analysis is mercury. Lab records are maintained on hand for at least 10 years Both influent and effluent sampling is flow proportional and samples are pumped from the respective sample locations to a refrigerator located inside the laboratory where they are stored at the proper preservation temperature. DMR values were compared to laboratory bench sheets for 2017. No transcnption errors were found. Since April 2013, the city has had only a single monthly average ammonia violation which occurred in January 2016. This violation was addressed with a separate Notice of Deficiency(NOD)from this office The Division greatly appreciates all the city's efforts to effectively and efficiently operate and maintain the Asheboro WWTP. Mr. Wiseman and Ms. Wardlaw, and their crews, should be proud and commended for their exemplary efforts. If you have any questions regarding the inspection or this letter, or if we may be of further assistance to you, please feel free to call Mr. Boone or me at(336)776-9800.Thank you for your attention to this matter. Sincerely, rri V. 4+, ght, PE gional upervisor Water Quality Regional Operations Division of Water Resources Attachments: 1. BIMS Inspection Report,Asheboro WWTP, NPDES Permit NC0026123 CC: WSRO—SWP with attachments Central Files with attachments ,NPDES Unit with attachments City of Asheboro Attn Michael Wiseman—ORC Asheboro WWTP P.O. Box 1106 Asheboro, NC 27204-1106 United States Environmental Protection Agency Form Approved EPA Washington,D C 20460 OMB No 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A National Data System Coding(i e, PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN I 2 IS I 3 I N00026123 I11 12 I 18/03/29 117 18 I I 19 Ls]I 201 21111111 1111111111111111111111111 11111111111 p6 Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA Reserved 671 I 70 I I 71 1 1 72 u 1 731 1 174 751 1 1 1 1 1 1 180 Section B Facility Data LJ Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 10 00AM 18/03/29 12/08/01 Asheboro WWTP Exit Time/Date Permit Expiration Date 1032 Bonkemeyer Dr 01 00 P M 18/03/29 16/09/30 Asheboro NC 27203 Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data /// Michael Ray Wiseman/ORC/336-672-0892/ Name,Address of Responsible Official/Title/Phone and Fax Number Contacted John N Ogburn,PO Box 1106 Asheboro NC 272041106/City Manager/336-626-1213/3366261218 No Section C Areas Evaluated During Inspection(Check only those areas evaluated) II Permit • Flow Measurement • Operations&Maintenance in Records/Reports II Self-Monitoring Program II Sludge Handling Disposal El Facility Site Review El Effluent/Receiving Waters II Laboratory Section D Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s)and Si• - - s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date Ron B40WSRO WQ//336-776-9690/ / IV/ ilratio :::.„,„„,1 Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date IAA— Y 1‘-::::1",„...-_,,,,e4- 4// /z'/ /k C EPA Form 3560-3(Rev 9-94)Previous editions are obsolete Page# 1 NPDES yr/mo/day Inspection Type 1 d 31 NC0026123 Il 21 18/03/29 117 18 Section D Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary) Please refer to the attached inspection summary letter Page# 2 JPermit• NC0026123 Owner-Facility AsheboroVVWfP Inspection Date 03/29/2018 Inspection Type Compliance Evaluation Pump Station -Influent Yes No NA NE Is the pump wet well free of bypass lines or structures'? • 000 Is the wet well free of excessive grease? • ❑ ❑ ❑ Are all pumps present'? • 000 Are all pumps operable'? • ❑ ❑ ❑ Are float controls operable'? U ❑ ❑ ❑ Is SCADA telemetry available and operational'? • 000 Is audible and visual alarm available and operational'? • 000 Comment None Flow Measurement- Influent Yes No NA NE #Is flow meter used for reporting'? 0 • 00 Is flow meter calibrated annually'? 1111:1 ❑ ❑ Is the flow meter operational'? , • 000 (If units are separated) Does the chart recorder match the flow meter'? 000 • Comment None Bar Screens Yes No NA NE Type of bar screen a Manual ❑ b Mechanical • Are the bars adequately screening debris'? • 000 Is the screen free of excessive debris'? 111000 Is disposal of screening in compliance'? • 000 Is the unit in good condition'? M ❑ ❑ ❑ Comment None Grit Removal Yes No NA NE Type of grit removal a Manual ❑ b Mechanical II Is the grit free of excessive organic matter? I ❑ ❑ ❑ Is the grit free of excessive odor'? 11000 #Is disposal of grit in compliance'? • 000 Page# 3 Permit NC0026123 Owner-Facility Asheboro VVWTP Inspection Date 03/29/201 B Inspection Type Compliance Evaluation Grit Removal Yes No NA NE Comment None Primary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater'? • ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier'? ❑ ❑ E ❑ Are weirs level? • 000 Is the site free of weir blockage? IMODD Is the site free of evidence of short-circuiting? • ❑ ❑ 0 Is scum removal adequate? MOOD Is the site free of excessive floating sludge'? 1 ❑ ❑ ❑ Is the drive unit operational'? MOOD Is the sludge blanket level acceptable'? ❑ ❑ ❑ • Is the sludge blanket level acceptable'? (Approximately 1/4 of the sidewall depth) ❑ ❑ ❑ • Comment None Trickling Filter Yes No NA NE Is the filter free of ponding? • ❑ ❑ ❑ Is the filter free of leaks at the center column of filter's distribution arms'? M ❑ ❑ ❑ Is the distribution of flow even from the distribution arms'? • 0 0 ❑ Is the filter free of uneven or discolored growth? • 000 Is the filter free of sloughing of excessive growth? • 000 Are the filter's distribution arms orifices free of clogging? U ❑ ❑ ❑ Is the filter free of excessive filter flies,worms or snails'? 111000 Comment None Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater'? • D00 Is the site free of excessive buildup of solids in center well of circular clarifier? ❑ ❑ • ❑ Are weirs level? U ❑ ❑ ❑ Is the site free of weir blockage'? • 000 Is the site free of evidence of short-circuiting'? • 000 Is scum removal adequate'? MOOD Is the site free of excessive floating sludge? • DOD Page# 4 1 Permit NC0026123 Owner-Facility Asheboro WWTP Inspection Date 03/29/2018 Inspection Type Compliance Evaluation Secondary Clarifier Yes No NA NE Is the drive unit operational'? MOOD Is the return rate acceptable(low turbulence)? E ❑ ❑ ❑ Is the overflow clear of excessive solids/pin floc'? h • 0010 Is the sludge blanket level acceptable'? (Approximately 1/4 of the sidewall depth) D00111 Comment There are also final clarifiers that receive activated sludge These clarifiers were also in excellent condition and Mr Boone had no concerns Aeration Basins Yes No NA NE Mode of operation Ext Air Type of aeration system Diffused Is the basin free of dead spots'? MOOD Are surface aerators and mixers operational'? U ❑ ❑ ❑ Are the diffusers operational'? • 000 Is the foam the proper color for the treatment process'? • 000 Does the foam cover less than 25%of the basin's surface'? 111000 Is the DO level acceptable'? • 000 Is the DO level acceptable?(1 0 to 3 0 mg/I) • 000 Comment None Pumps-RAS-WAS Yes No NA NE Are pumps in place'? ❑ ❑ U ❑ Are pumps operational'? ❑ ❑ U ❑ Are there adequate spare parts and supplies on site'? 00110 Comment RAS is conveyed via gravity only Filtration (High Rate Tertiary) Yes No NA NE Type of operation Down flow Is the filter media present'? MUDD Is the filter surface free of clogging'? MOOD Is the filter free of growth? MOOD Is the air scour operational'? • ❑ ❑ ❑ Is the scouring acceptable'? • 1100 Is the clear well free of excessive solids and filter media'? MOOD Page# 5 Permit: NC0026123 Owner-Facility Asheboro VVVVTP f Inspection Date 03/29/2015 Inspection Type Compliance Evaluation Filtration (High Rate Tertiary) Yes No NA NE Comment None Disinfection-Liquid Yes No NA NE Is there adequate reserve supply of disinfectant'? • El ❑ ❑ (Sodium Hypochlorite) Is pump feed system operational'? • ❑ El ❑ Is bulk storage tank containment area adequate'? (free of leaks/open drains) • ❑ ❑ p Is the level of chlorine residual acceptable'? • ❑ ❑ ❑ Is the contact chamber free of growth, or sludge buildup'? • ❑ 0 ❑ Is there chlorine residual prior to de-chlorination? • ❑ ❑ ❑ Comment None De-chlorination Yes No NA NE Type of system? Liquid Is the feed ratio proportional to chlorine amount(1 to 1)'? ❑ 0 ❑ Is storage appropriate for cylinders'? • ❑ ❑ ❑ #Is de-chlorination substance stored away from chlorine containers'? U ❑ ❑ ❑ Are the tablets the proper size and type'? ❑ ❑ • 0 Comment None Are tablet de-chlorinators operational'? p ❑ • ❑ Number of tubes in use'? Comment None Flow Measurement-Effluent Yes No NA NE #Is flow meter used for reporting'? • ❑ ❑ ❑ Is flow meter calibrated annually'? • 0 0 ❑ Is the flow meter operational'? • ❑ ❑ ❑ (If units are separated) Does the chart recorder match the flow meter'? • ❑ ❑ ❑ Comment Meter is calibrated quarterly by contractor Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained'? • ❑ ❑ ❑ Are the receiving water free of foam other than trace amounts and other debris'? • ❑ ❑ 0 If effluent (diffuser pipes are required) are they operating properly'? El ❑ I 0 Page# 6 J Permit- NC0026123 Owner-Facility Asheboro WINTP Inspection Date 03/29/2018 Inspection Type Compliance Evaluation Effluent Pipe Yes No NA NE Comment None Anaerobic Digester Yes No NA NE Type of operation Floating cover Is the capacity adequate'? • ❑ ❑ ❑ #Is gas stored on site'? U ❑ ❑ ❑ Is the digester(s)free of tilting covers'? • ❑ ❑ ❑ Is the gas burner operational'? • ❑ ❑ ❑ Is the digester heated'? U ❑ ❑ ❑ Is the temperature maintained constantly'? • ❑ 0 ❑ Is tankage available for properly waste sludge'? U ❑ ❑ ❑ Comment None Chemical Feed Yes No NA NE Is containment adequate'? • ❑ ❑ ❑ Is storage adequate'? • ❑ ❑ ❑ Are backup pumps available'? • 0 ❑ ❑ Is the site free of excessive leaking'? • ❑ ❑ ❑ Comment None Solids Handling Equipment Yes No NA NE Is the equipment operational'? • ❑ ❑ ❑ Is the chemical feed equipment operational'? U ❑ ❑ ❑ Is storage adequate'? U ❑ ❑ ❑ Is the site free of high level of solids in filtrate from filter presses or vacuum filters'? • ❑ ❑ ❑ Is the site free of sludge buildup on belts and/or rollers of filter press'? 11 ❑ ❑ ❑ Is the site free of excessive moisture in belt filter press sludge cake'? U ❑ ❑ ❑ The facility has an approved sludge management plan'? U ❑ ❑ ❑ Comment None Drying Beds Yes No NA NE Is there adequate drying bed space'? • ❑ ❑ ❑ Is the sludge distribution on drying beds appropriate'? • 0 0 ❑ Page# 7 Permit NC0026123 Owner-Facility Asheboro VVVVTP 1 Inspection Date 03/29/201 B Inspection Type Compliance Evaluation Drying Beds Yes No NA NE Are the drying beds free of vegetation'? • ❑ 0 0 #Is the site free of dry sludge remaining in beds'? E ❑ ❑ ❑ Is the site free of stockpiled sludge'? • 0 0 0 Is the filtrate from sludge drying beds returned to the front of the plant? • ❑ ❑ ❑ #Is the sludge disposed of through county landfill'? ❑ MI ❑ ❑ #Is the sludge land applied'? • ❑ ❑ 0 (Vacuum filters) Is polymer mixing adequate? • ❑ ❑ ❑ Comment Drying beds used for grease from local grease haulers only Sludge is digested, thickened, pressed, and land applied Standby Power Yes No NA NE Is automatically activated standby power available'? • ❑ ❑ ❑ Is the generator tested by interrupting primary power source'? • ❑ ❑ ❑ Is the generator tested under load'? • ❑ ❑ ❑ Was generator tested&operational during the inspection? ❑ M ❑ ❑ Do the generator(s) have adequate capacity to operate the entire wastewater site'? • ❑ ❑ ❑ Is there an emergency agreement with a fuel vendor for extended run on back-up power'? • ❑ ❑ ❑ Is the generator fuel level monitored'? • ❑ ❑ ❑ Comment None Permit Yes No NA NE (If the present permit expires in 6 months or less) Has the permittee submitted a new ❑ ❑ • ❑ application'? Is the facility as described in the permit'? • ❑ ❑ ❑ #Are there any special conditions for the permit'? ❑ • ❑ ❑ Is access to the plant site restricted to the general public'? • ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑ Comment None Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? N ❑ ❑ ❑ Is all required information readily available, complete and current'? • ❑ ❑ ❑ Are all records maintained for 3 years (lab reg required 5 years)? • ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? • ❑ ❑ ❑ Page# 8 ,i Permit NC0026123 Owner-Facility Asheboro VWVfP Inspection Date. 03/29/2018 Inspection Type Compliance Evaluation Record Keeping Yes No NA NE Is the chain-of-custody complete'? • 000 Dates,times and location of sampling • Name of individual performing the sampling • Results of analysis and calibration • Dates of analysis • Name of person performing analyses IN Transported COCs U Are DMRs complete do they include all permit parameters'? • 000 Has the facility submitted its annual compliance report to users and DWQ? • 000 (If the facility is=or>5 MGD permitted flow) Do they operate 24/7 with a certified operator 1111000 on each shift'? Is the ORC visitation log available and current'? 11000 Is the ORC certified at grade equal to or higher than the facility classification'? • 000 Is the backup operator certified at one grade less or greater than the facility classification'? • ❑ ❑ ❑ Is a copy of the current NPDES permit available on site'? • 000 Facility has copy of previous year's Annual Report on file for review? • 000 Comment None Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory'? • 000 Are all other parameters(excluding field parameters) performed by a certified lab'? • 000 #Is the facility using a contract lab'? M ❑ ❑ ❑ #Is proper temperature set for sample storage(kept at less than or equal to 6 0 degrees • 000 Celsius)? Incubator(Fecal Coliform) set to 44 5 degrees Celsius+/-0 2 degrees'? • 000 Incubator(BOD) set to 20 0 degrees Celsius+/- 1 0 degrees'? U ❑ ❑ ❑ Comment None Influent Sampling Yes No NA NE #Is composite sampling flow proportional'? • 000 Is sample collected above side streams'? M ❑ ❑ ❑ Is proper volume collected'? 11000 Is the tubing clean'? • ❑ ❑ ❑ Page# 9 Permit NC0026123 Owner-Facility Asheboro VVV TP ,1 Inspection Date 03/29/2018 Inspection Type Compliance Evaluation Influent Sampling Yes No NA NE #Is proper temperature set for sample storage(kept at less than or equal to 6 0 degrees • 000 Celsius)'? Is sampling performed according to the permit% • ❑ 0 ❑ Comment None Effluent Sampling Yes No NA NE Is composite sampling flow proportional'? • 000 Is sample collected below all treatment units'? • 000 Is proper volume collected'? • 000 Is the tubing clean'? I ❑ ❑ ❑ #Is proper temperature set for sample storage(kept at less than or equal to 6 0 degrees • 000 Celsius)? Is the facility sampling performed as required by the permit(frequency, sampling type M ❑ ❑ ❑ representative)? Comment None Upstream / Downstream Sampling Yes No NA NE Is the facility sampling performed as required by the permit(frequency, sampling type, and M ❑ ❑ ❑ sampling location)? Comment River basin association Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping'? • 000 Does the facility analyze process control parameters,for ex MLSS, MCRT, Settleable U ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable'? Comment None Page# 10