HomeMy WebLinkAboutNC0038997_Authorization to Construct_20021025Michael F Easley, Governor
State of North Carolina
William G Ross, Jr., Secretary
Department of Environment and Natural Resources
Alan W Klimek, P E , Director
Division of Water Quality
October 25, 2002
Mr. Jay Manner
Roaring Gap Club Inc
P 0. Bok 129
Roaring Gap, North Carolina 28668
Subject Authorization to Construct
ATC No. 038997AOI
NPDES Permit No NCO038997
Alleghany County
Dear Mr Manner
The Division of Water Quality's NPDES Unit has reviewed your request for an Authorization to Construct at
the Roaring Gap Club WWTP The Division finds the proposed improvements to be satisfactory and hereby
grants authorization for the following
• Ultraviolet disinfection unit rated for 40 gpm, uv dosage of 32,000 micro -watt sec/cm' and automatic
dialer.
This Authorization to Construct is issued in accordance with NPDES Permit No NC0038997, issued April
26, 1999, and shall be subject to revocation unless the wastewater treatment facilities are constructed in
accordance with the terms and conditions of the permit.
The Permttee shall notify the Water Quality Supervisor of the Winston Salem Regional Office, telephone
number 336/771-4600, at least forty-eight (48) hours prior to operation of the installed facilities, so that an
in -place inspection can be made Notification shall be made during the normal office hours of 8 00 a.m. uintil
5 00 p m , Monday through Friday
Engineer's Certification
Upon completion of construction and prior to operation of the modified facility, the Permittee shall provide
the Division with a certification (copy enclosed) from a professional engineer registered in North Carolina
certifying that the permitted facility has been installed in accordance with the NPDES Permit, this
Authorization to Construct, and the approved plans and specifications The Certification should be subrrm-tted
to NCDENR / DWQ, NPDES Unit, 1617 Mail Service Center, Raleigh, North Carolina 27699-1617
Requirements for Certified Operator
The Permittee shall employ a certified wastewater treatment plant operator to be in responsible charge (ORC)
of the wastewater treatment facilities The operator must hold a certificate of the type and grade at least
equivalent to or greater than the classification assigned to the wastewater treatment facilities by the
Certification Commission The Permittee must also employ a certified back-up operator of the appropriatte
type and grade to comply with the conditions of Title 15A, Chapter 8G, 0200 The ORC of the facility must
visit each Class I facility at least weekly and each Class II, III, and IV facility at least daily, excluding,,
weekends and holidays; and must properly manage and document daily operation and maintenance of the
facility and comply with all other conditions of Title I5A, Chapter 8G, .0200.
Additional Requirements
The Operational Agreement between the Permittee and the Environmental Management Commission is
incorporated herein by reference and is a condition of this Permit Noncompliance with the terms of the
1617 Mail Service Center, Raleigh, North Carolina 27699-1617 Telephone (919) 733-5083 FAX (919) 733-0719
An Equal Opportunity Affirmative Action Employer Internet http Hh2o enr state nc us/
Roaring Gap Club WWTP
NPDES Perrmt No NCO038997
ATC No. 038997A01
Page 2
Operational Agreement shall subject the Pernuttee to all sanctions provided by G S 143-215 6 for violation
of or failure to act in accordance with the terms and conditions of this Pernut
Failure to abide by the requirements contained in this Authorization to Construct may subject the Permittee
to an enforcement action by the Division of Water Quality in accordance with North Carolina General Statute
143-215 6A to 143-215.6C
The issuance of this Authorization to Construct does not preclude the Permittee from complying with any and
all statutes, rules, regulations, or ordinances which may be imposed by other government agencies (local,
state, and federal) which have jurisdiction
The Permittee shall maintain a copy of the approved plans and specifications on file for the life of the
facility One (1) copy of the approved plans and specifications is enclosed for your records
If you have any questions about this Authorization to Construct, please contact Teresa Rodriguez, at (919)
733-5083, extension 595
Sincerely,
Alan W Klimek, P E.
Director
Enclosures Project Plans (approved)
Engineer's Certification Form
cc Winston Salem Regional Office, Water Quality
Technical Assistance and Certification Unit
Central Files
NPDES Unit Files
Mr John F Phillips, P E — Diehl & Phillips
219 East Chatham St
Cary, NC 27511
ATC NOTES
ATC No.
038997A01
PERMIT NO
NCO038997
FACILITY
Roaring ap WWTP
COUNTY
Alle han
RECEIVING STREAM
UT to Mitchell River
BASIN
Yadkin -Pee Dee River
CLASS
B-Tr
FLOW
0.013 MGD
APPLICATION/PLANS PREPARED BY: Diehl & Phillips, P. A
219 East Chatham St
Cary, NC 27511
SCOPE: Installation of a UV disinfection system.
SUMMARY: Roaring Gap Club wants to change the disinfection system from chlorination to UV in
response to the new requirement to measure TRC to a level of 17 pg/I They will keep the existing tablet
chlorinator, dechlonnator and contact chamber as a backup during power failures.
SUBMISSIONS:
• Engineering drawings
PROJECT EQUIPMENT DESCRIPTION:
• Two lamp UV unit rated for 40 gpm, 32,000 micro -watt seconds/cm.
• Autodialer to be activated in the event of loss of intensity or lamp failure
RECOMMENDATIONS:
The proposed system meets the UV guidelines as specified by the Division. Approval of the AtC is
recommended Backup is provided with the existing chlorination-dechIon nation system and an autodialer
will call the maintenance staff when the lamps loose intensity or fail.
NPDES Unit contact: Teresa Rodriguez
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
DIVISION OF WATER QUALITY
August 7, 2002
M E M O R A N D U M
TO: Ms. Teresa Rodriguez
NPDES Unit
THROUGH: Steve Mauney - WSRO Acting Supervisor
FROM: George Smith - WSRO 146
SUBJECT: ATC Number 038997AO1
Roaring Gap Club
Alleghany County
AUG
N,, 'R - V,"ffR PIALI Y
- f CAT :1 "T !
This office reviewed the ultraviolet disinfection (UV) system for
reliability with the following comments:
It was noted that the tablet chlorinator and dechlorination units
to be abandoned in place by removing the tablets. Per 15A NCAC 2H
.0124, there must be a continued treatment and disinfection where
the interruption of such treatment would render the waters unsafe
for their best intended uses. Therefore, this office would
suggest an alternative back-up method to meet the minimum
reliability conditions. (i.e., back-up power, dual train, etc.)
The UV system does not appear to have an automatic cleaning
device to insure maximum radiation for proper disinfection. Also,
during the time the system is down for cleaning there must not be
an interruption in the disinfection process.
cc: WSRO
DIEHL & PHILLIPS, P.A.
CONSULTING ENGINEERS
219 East Chatham Street
Cary, North Carolina 27511
Telephone (919) 467-9972 • Fax (919) 467-5327
October 1, 2002
Ms Teresa Rodriguez
NPDES Unit-DWQ
NC DENR
1617 Mail Service Unit
Raleigh, NC 27699-1617
Re Roaring Gap Club
NPDES Permit NC 0038997
ATC Number 038997A01
Dear Ms Rodriguez:
WILLIAM C. DIEHL, P.E.
JOHN F. PHILLIPS, P.E.
ALAN R. KEITH, P.E.
We offer the following information in response to your review comments on the
referenced project.
The design has been modified to use the existing tablet chlorinator and dechlorinator as a
backup disinfection system in the event of a power outage. The switchover to the backup
disinfection system will be automatic during a power outage, due to the recirculation
pump station overflowing (no power for the pumps) to the backup system In the event
of a lamp failure or loss of intensity, the specified U.V. intensity monitor will cause the
autodialer to call the Club's maintenance staff. The staff will then either clean or replace
bulbs, or operate two valves to divert the effluent through the backup
chlorination/dechlorination system.
Enclosed are two sets of revised plans (specifications are on the plans) for your review
Please call if you have any further questions.
OCT e 2 2002
DENR - WAIER QUALITY
PONT SOUPCE [1�AJVCH
Yours Very Truly,
Diehl & Phillips, P.A.
�J- 7. f� �
John F. Phillips, P E
DIEHL & PHILLIPS, P.A.
CONSULTING ENGINEERS
219 East Chatham Street
Cary, North Carolina 27511
Telephone (919) 467-9972 • Fax (919) 467-5327
2"r2
DIEHL, P.E.
PHILLIPS, RE
Z KEITH, RE
June 25, 2002
UENR - WATER QUALITY
NPDES UNIT -DWQ POINT -SOURCE BRANCH
NCDENR-�-
1617 Mail Service Unit
Raleigh, NC 27699-1617 T
Re Addition of Ultra -Violet Disinfection Unit for Roaring Gap Club
NPDES Permit No. NC0038997 _ ; 20�
Dear Reviewer
,4 n1SC ARGE PEM , � y'"�`'+
Please find enclosed three sets of plans (with equipment specifications e�plar�s}-fetyt`
addition of a U V disinfection unit at the wastewater treatment system for the Roaring Gap Club
The U.V unit is being installed to replace the existing chlorination/dechlormation system This
change is being made in response to the Division's notification to Permrttees that beginning July
1, 2002, Permittees must measure TRC with an instrument capable of analysis in the 10 to 15-
microgram per liter range Rather than purchasing the equipment necessary for the low level
TRC measurement, the Club has decided to install ultra -violet disinfection.
As an authorized agent for the Club, I hereby request Authorization to Construct the
improvements indicated on the plans Although these improvements will not be operational by
July 1, the maintenance staff for the Club should have the system operational within 60 to 90
days of receipt of the ATC We request you allow the ORC to continue the current field testing
procedures until these improvements can be installed If it is necessary to request an SOC to
prevent enforcement actions and penalties, we can make such a request, however, we hope to
have the improvements installed in a shorter time period than that usually required to obtain an
SOC
Please advise if you require any further information
Cc Winston-Salem Regional Office, DWQ
Mr Jay Manner
Mr Hal Transou
Yours Very Truly,
Diehl & Phillips, P.A.
k �D -
John F. Phillips, P E.
2002
CISCPARGE PEH,'.
Roaring Gap Glub I N C .
P.O. BOX 129
ROARING GAP, N.C. 28668
(336) 363-2211
July 16, 2002
Mr. David A. Goodrich
Supervisor, NPDES Unit
DWQ NCDE1 TR
1617 Mail Service Unit
Raleigh, NC 27699-1617
Re Designation of Authorized Representative
Dear Mr Goodrich.
ly
200,02 D
DEP,R - WATER QUALITY
POINT SOURCE BRANCH
The Roaring Gap Club, Inc , hereby designates John F. Phillips, P E. of Diehl & Phillips, P.A to
act as our duly authorized representative for all matters pertaining to the ultraviolet disinfection
system addition to our treatment facility (ATC No 038997A01)
Please call if you have any questions in this matter
Yours Very Truly,
Ja ner, =anager
Roaring Gap Club, Inc.
o�0� WAT�9Q�
Michael F Easley, Governor
rWrlltam G Ross Jr ,Secretary
—i North Carolina Department of Environment and Natural Resources
o -c
Alan W Khmek, P E ,
August 19, 2002
John F. Phillips, P E.
219 East Chatham Street
Cary, North Carolina 27511
Subject Request for Additional Information
Roaring Gap Club
NPDES Permit NCO038997
ATC Number 038997A01
Dear Mr. Phillips:
The initial review of the plans and specifications for the proposed LTV system for Roaring Gap Club
Wastewater Treatment Plant has been completed. The Division issued guidelines for Ultraviolet
disinfection systems in November of 2001 The following are part of the requirements of the new
guidelines and need to be addressed before we proceed with the issuance of the Authorization to 'Construct -
IN Since the discharge is to a class B stream, standby power or a chlorination/dechlormation back up
system must be in place unless the perrmttee can demonstrate to the Director's satisfaction that, in the
event of a power outage or lamp/unit failure, no untreated water will reach waters of the state Please
provide information as to how this requirement is being met.
The system shall have an autodialer and audible/visual alarms or a way to alert the operator in
responsible charge in the event of a system failure or malfunction.
For specific information regarding the UV Guidelines go to our website at
http://h2o.enr.state.ne.us/NPDES/NPDESweb.html. Please respond to the questions and provide the
requested information prior to September 19, 2002 Thank you in advance for your efforts in responding
to this information request. This information will greatly aid the Division in its review of the plans and
specifications for the proposed project
If you have any questions, please call me at (919) 733-5093, extension 595.
Sincerely,
Teresa Rodriguez,
NPDES Unit