HomeMy WebLinkAboutNC0043532_Compliance Evaluation Inspection_201708181
t'<d
Water Resources
ENVIRONMENTAL QUALITY
August 18, 2017
Ms Donna Davis, Utility Director
Stanly County
1000 North 1St Street, Suite 12
Albemarle, North Carolina 28001
SUBJECT Compliance Evaluation Inspection
West Stanly WWTP
NPDES Permit NCO043532
Stanly County, NC
Dear Ms Davis
Gt/AIZ-7v
PAT MCCRORY
Govemor
DONALD R VAN DER VAART
Secretary
S. JAY ZIMMERMAN
Director
RECEIVED/NCDEWWR
AUG 2 2 2017
Water Quality
Permitting Section
On August 10, 2016, Roberto Scheller of this Office conducted an inspection at the subject
facility This inspection was conducted as a Compliance Evaluation Inspection (CEI) to insure
compliance with permit requirements and conditions At the time of inspection facility appeared
to be well maintained and operated despite only one of three secondary clarifiers are in
operation We wish to thank you and operating staff for your assistance regarding the
inspection A copy of this inspection will be forwarded to the facility's Operator -in -Responsible -
Charge (ORC)
The enclosed report should be self-explanatory, however, should you have any questions,
please do not hesitate to contact myself of Roberto Scheller at (704) 235-2204 or
roberto scheller@ncdenr gov
Enclosure Inspection Report
cc ORC, Donald Zufall, email
Wastewater Branch
File
Sincerely,
r
W Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
dzufall@stanlycountync gov
State of North Carolina I Environmental Quality I Water Resources I Water Quality Regional Operations
Mooresville Regional Office) 610 East Center Avenue, Suite 3011 Mooresville, North Carolina 28115
704 663 1699
United States Environmental Protection Agency
Form Approved
EPA Washington, D C 20460
OMB No 2040-0057
Water Compliance Inspection Report
Approval expires B-31-98
Section A National Data System Coding (i e, PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 1 3 I NCO043532 111 12 17/08/10 17 18 C I 19 t G j 201
L_J
211
1 1 1I 1 1 1 1 11 1 1 1 I I I I I I I I I 1 1 I I I I I I I I I 11 I I I I I 166
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved ---
67 70 I, J 71 I JI 72 I N I 73 I I 174 75III 80
LJ it L_1 I I
Section B Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
10 06AM 17/08/10
10/02/01
West Stanly W WTP
Exit Time/Date
permit Expiration Date
24939-B Barbees Grove Rd
12 15P 17/08/10
14/01/31
Oakboro NC 28129
Name(s) of Onsite Representative(s)1Titles(s)/Phone and Fax Number(s)
Other Facility Data
Donald G Zufall/ORC/980-621-3449/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Donna Davis, 1000 N 1st St Albemarle NC 28001/Utilities
No
Director/704-986-369117049863711
Section C Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenance Records/Reports
Self-MQnitonng Program N Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
oberto cheller MRO WQ//252-946-6481/
Q
O
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W Corey Basinger MRO WQ//704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete �^y
Page#
NPDES yr/mo/day Inspection Type
31 NCO043532 I11 12 17/08/10 17 181 I
M
Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
1
Page# 2
Permit: NCO043532 Owner - Facility west Stanly WWTP
Inspection Date. 08/10/2017 Inspection Type Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires In 6 months or less) Has the permittee submitted anew
❑
❑
M
❑
application?
M
❑
❑
❑
Is the facility as described In the permit?
M
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
0
❑
Is access to the plant site restricted to the general public?
M
❑
❑
❑
Is the Inspector granted access to all areas for Inspection?
M
❑
❑
❑
Comment Permit Is in review for renewal Permit Is for the continued operation of a 0 90 MGD
wastewater treatment plant
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required Information readily available, complete and current?
M
❑
❑
❑
Are all records maintained for 3 years (lab reg required 5 years)?
M
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete?
M
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete do they include all permit parameters?
0
❑
❑
❑
Has the facility submitted Its annual compliance report to users and DWQ?
❑
❑
❑
M
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
M
❑
on each shift?
Is the ORC visitation log available and current?
M
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
0
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
M
❑
❑
❑
Is a copy of the current NPDES permit available on site?
M
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
❑
❑
Comment All records reviewed were current and well organized Records reviewed include Process
Control logs, ORC log, Daily Operations log, and Meter Calibration records It was noted
that a YSI 550A meter was being used to collect DO and Temperature measurements
Please note that tempeature of YSI meter should be checked aginst a NIST certified
therometer and recorded in calibration log
Page# 3
Permit NC0043532
Inspection Date 08/10/2017
Owner - Facility west Stanly WWTP
Inspection Type Compliance Evaluation
Type of bar screen
E
❑
Pump Station - Influent
Yes No NA NE
Is the pump wet well free of bypass lines or structures?
S
❑
❑
❑
Is the wet well free of excessive grease?
❑
❑
❑
0
Are all pumps present?
N
❑
❑
❑
Are all pumps operable?
N
❑
❑
❑
Are float controls operable?
E
❑
❑
❑
Is SCADA telemetry available and operational?
❑
❑
0
❑
Is audible and visual alarm available and operational?
N
❑
❑
❑
Comment
Bar Screens
Yes No NA NE
Type of bar screen
E
❑
❑
❑
a Manual
❑
❑
❑
❑
b Mechanical
E
❑
❑
❑
,Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
E
❑
❑
❑
Is disposal of screening in compliance?
E
❑
❑
❑
Is the unit In good condition?
❑
❑
❑
0
Comment Bar screen is scheduled for removal and replacement
Grit Removal
Yes No NA NE
Type of grit removal
E
❑
❑
❑
a Manual
❑
❑
❑
❑
b Mechanical
E
❑
❑
❑
Is the grit free of excessive organic matter?
❑
❑
N
❑
Is the grit free of excessive odor?
❑
❑
N
❑
# Is disposal of grit In compliance?
❑
❑
0
❑
Comment Grit removal schedule for removal and replacement It was noted that
grit removal not
operating at time of inspection
Chemical Feed
Yes No NA NE
Is containment adequate?
E
❑
❑
❑
Is storage adequate?
0
❑
❑
❑
Are backup pumps available?
0
❑
❑
❑
Is the site free of excessive leaking?
N
❑
❑
❑
Page# 4
t'
Permit NCO043532
Inspection Date 08/10/2017
Chemical Feed
Comment Chemical feed at pump station to reduce odor
Owner -Facility west Stanly WWrP
Inspection Type Compliance Evaluation
Influent Sampling
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees
Celsius)?
Is sampling performed according to the permit?
Yes No NA NE
Yes No NA NE
❑ E ❑ ❑
■ ❑ ❑ ❑
E ❑ ❑ ❑
N ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Comment Temperature of Influent sampler was recorded at 3 degrees Celsius at time of Inspection
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment Process control on MLSS was well documented
Aeration Basins
Mode of operation
Type of aeration system
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Is the DO level acceptable?(1 0 to 3 0 mg/1)
Yes No NA NE
N ❑ ❑ ❑
■ ❑ ❑ ❑
Yes No NA NE
Ext Air
Surface
■ ❑ ❑ ❑
N ❑ ❑ ❑
❑ ❑ N ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ N
N ❑ ❑ ❑
Comment MLSS had good color and appeared to have good settleabllty in secondary clarifier
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids In center well of circular clarifier?
0
❑
❑
❑
Are weirs level?
N
❑
❑
❑
Page# 5
I
Permit NCO043532 Owner - Facility west Stanly WWTP
Inspection Date 08/10/2017 Inspection Type Compliance Evaluation
Secondary Clarifier Yes No NA NE
Is the site free of weir blockage?
E
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
E
❑
❑
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately % of the sidewall depth)
❑
❑
❑
E
Comment Effluent from secondary clarifier was clear with few suspended solids
❑
Disinfection -Gas
Yes No NA NE
Are cylinders secured adequately?
0
❑
❑
❑
Are cylinders protected from direct sunlight?
0
❑
❑
❑
Is there adequate reserve supply of disinfectant? -
0
❑
❑
❑
Is the level of chlorine residual acceptable?
❑
❑
❑
0
Is the contact chamber free of growth, or sludge bui dup?
E
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
0
❑
❑
❑
Does the Stationary Source have more than 2500 lbs of Chlorine (CAS No 7782-50-5)?
❑
❑
E
❑
If yes, then Is there a Risk Management Plan on site?
❑
❑
N
❑
If yes, then what is the EPA twelve digit ID Number? (1000-____:-____)
If yes, then when was the RMP last updated?
Comment -
De -chlorination Yes No NA NE
Type of system ? Gas
Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ ❑ ❑
Is storage appropriate for cylinders? ❑ ❑ ❑
# Is de -chlorination substance stored away from cnIorine containers? ❑ ❑ ❑
Comment
Are the tablets the proper size and type? ❑ ❑ N ❑
Are tablet de-chlonnators operational? ❑ ❑ N ❑
Number of tubes in use?
Page# 6
Permit. NCO043532 Owner - Facility west Stanly WWTP
Inspection Date. 08/10/2017 Inspection Type Compliance Evaluation
De -chlorination Yes No NA NE
Comment
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
N
❑
❑
❑
Is sample collected below all treatment units?
# Is flow meter used for reporting?
❑
❑
❑
Is proper volume collected?
Is flow meter calibrated annually?
❑
❑
❑
Is the tubing clean?
Is the flow meter operational?
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees
0
❑
❑
❑
Celsius)?
❑
❑
0
❑
Is the facility sampling performed as required by the permit (frequency, sampling type
M
❑
❑
❑
representative)?
Comment At time of Inspection effluent sampler was noted at 3 deqrees Celsius At time of Inspection
effluent was clear with no visible suspended solids
Yes No NA NE
Is the equipment operational?
N
❑
❑
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
M
❑
❑
❑
Is flow meter calibrated annually?
❑
❑
❑
❑
Is the flow meter operational?
N
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
M
❑
❑
❑
Comment Flow mearurement consist of V -notch weir and ultra sonic flow meter with chart recorder
Flow meter was last calabrated on July 27, 2017 by Clearwater, Inc
Solids Handling Equipment
Yes No NA NE
Is the equipment operational?
N
❑
❑
❑
Is the chemical feed equipment operational?
❑
❑
0
❑
Is storage adequate?
0
❑
❑
❑
Is the site free of high level of solids In filtrate from filter presses or vacuum filters?
❑
❑
0
❑
Is the site free of sludge buildup on belts and/or rollers of filter press?
❑
❑
0
❑
Is the site free of excessive moisture In belt filter press sludge cake?
❑
❑
0
❑
The facility has an approved sludge management plan?
0
❑
❑
❑
Comment Facility has aerobic sludge digester with floating aerators and Is decanted to thicken sludge
Sludge Is removed for disposal at the Rock River UWV P
Page# 7