Subject: NPDES Compliance Inspection Report
Wallace Regional WWTP
NPDES Permit No. NC0003450
Duplin County
A Compliance Evaluation inspection of the Wallace Regional WWTP was conducted by Helen Perez from this office
on August 25, 2016. This inspection was to verify that the facility is operating in compliance with the conditions
and limitations specified in NPDES Permit No. NC0003450. The findings and comments noted during this
inspection are provided in the enclosed copy of the "Water Compliance Inspection Report".
Notice that there is an ongoing problem with the vortex grit removal system. Short-term
plans should be made to conduct repairs or modifications to the system to avoid further
operational/maintenance problems or negative effects to the plant's treatment efficiency.
If you have any questions concerning this report, you may contact the inspector at the letterhead contact or via
email at helen.perez@ncdenr.gov.
ncerely,
Morel ch z -King, Assistant Regional Supervisor
Water Qua ' egional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
Enclosure
Cc: Wilmington Regional Office —Yellow Inspection File
Central Files, Water Quality Section
127 Cardinal Drive Extension, Wilmington, North Carolina 28405
Phone: 910-796-7215\ Internet: www.ncdenr.gov
An Fnual Onnnrtunitv \ Affirmative Action Emolover — Made in cart by recvcled oaoer
' United States Environmental Protection Agency
Form Approved.
EPA Washington, D.0 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires B-31-98
Section A: National Data System Coding (Le , PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 15 I 3 I NC0003450 I11 121 16/06/25 I17 18 LC] I 19 1 G I 201 I
211111 1 1 1 1 1 111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111 1 l l 1 1 166
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA -----------------Reserved------------
67I L 70I, I 71 J 72 LNJ 73l_LJ74 751 I I I I I 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number) I
10.00AM 16/08/25
13/02/01
Wallace Regional WWTP
851 Old Wilmington Rd
Exit Time/Date
Permit Expiration Date
Wallace NC 28466
11:25AM 16/08/25
17/01/31
Name(s) of Onsite Representative(s)rritles(s)/Phone and Fax Number(s)
Other Facility Data
Brent McCoy Dean/ORC/910-285-5927/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Gerald F James,PO Box 849 Wallace NC 284660849/Public Works
Yes
Director/910-285-2812/9102855135
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
0 Permit Flow Measurement Operations & Maintenance Records/Reports
0 Self -Monitoring Program Sludge Handling Disposal Facility Site Review Compliance Schedules
0 Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Helen Perez WIRO WQ//910-796-7387/
,�YA RF
Signature of Management Q A Reviewer Agency/Off/Phon and Numbers Date
Morella Sanchez -King WIRO WQ//910-796-7218/ N // lip
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type (Cont) 1
31 NCo003450 111 121 96/08/25 117 18 ICI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
A compliance inspection was conducted on 8/25/16. The facility was clean and well maintained. A
review of records included log books, lab records, CDCs, field parameter bench sheets and
calibrations. All records were organized and complete. The vortex grit removal system continues to
cause operational problems for the staff as indicated in the report section. The Town of Wallace and
operations staff should address this Issue in a timely manner. The facility is still receiving pump and
haul waste from the Pender Industrial Park (Acme Smoked Fish). They receive 3 loads a day and it is
stored in one of the facility's sludge thickeners before it is added to the SBRs. This wastewater has not
caused any operation issues to date The ORC indicated that the Pender County WWTP should be
on-line soon to handle the waste.
Page#
Permit: NC0003450 Owner -Facility: Wallace Regional WWTP
Inspection Date: 08/25/2016 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
M
❑
❑
❑
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
M
❑
Is access to the plant site restricted to the general public?
M
❑
❑
❑
Is the inspector granted access to all areas for inspection?
❑
❑
❑
Comment: No comment.
Compliance Schedules Yes No NA NE
Is there a compliance schedule for this facility? ❑ M ❑ ❑
Is the facility compliant with the permit and conditions for the review period? ❑ M ❑ ❑
Comment: There were two BOD limit violations and four ammonia limit violations that had penalty
assessments since the last inspection on 03/04/2015.
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
M
❑
❑
❑
Is all required information readily available, complete and current?
M
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
❑
❑
❑
0
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported CDCs
Are DMRs complete: do they include all permit parameters?
M
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
0
❑
❑
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
M
❑
❑
❑
on each shift?
Is the ORC visitation log available and current? -
0
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
■
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
0
❑
❑
❑
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Page# 3
0
Permit: NC0003450 Owner - Facility: Wallace Regional VWVrP
Inspection Date: 08/25/2016 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Facility has copy of previous year's Annual Report on file for review? M ❑ ❑ ❑
Comment: No comment
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Comment: Envirochem is the facility's contract lab.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Yes No NA NE
M ❑ ❑ ❑
M ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ ■
❑ ❑ ■ ❑
❑ ❑ ■ ❑
Yes No NA NE
M ❑ ❑ ❑
M ❑ ❑ ❑
M ❑ ❑ ❑
❑ ❑ ❑ ■
■ ❑ ❑ ❑
M ❑ ❑ ❑
M ❑ ❑ ❑
Comment: The generator was not tested during the inspection but last test was performed on Tuesda
08/23/16 for 30 minutes according to the facility's log book.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable M ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: MLSS and MLVS parameters are analvzed in the lab. MLSS levels are maintained between
2100-2500. The facility is currently using a Thermo Scientific pH meter and bench sheets
and calibrations were kept and maintained.
Pump Station - Influent Yes No NA NE
Is the pump wet well free of bypass lines or structures? ❑ ❑ ❑
Is the wet well free of excessive grease? ❑ ❑ ❑ 0
Page# 4
Permit: NC0003450
Owner -Facility: Wallace Regional WVVfP
Type of bar screen
Inspection Date: 08/25/2016 -
Inspection Type: Compliance Evaluation
a.Manual
❑
Pump Station - Influent
Yes No NA NE
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
N
❑
❑
❑
Are float controls operable?
M
❑
❑
❑
Is SCADA telemetry available and operational?
❑
❑
❑
S
Is audible and visual alarm available and operational?
❑
❑
❑
■
Comment: SCADA is available but not evaluated.
Bar Screens
Yes No NA NE
Type of bar screen
a.Manual
❑
b.Mechanical
0
Are the bars adequately screening debris?
■
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment: The spiral mechanical screen appears to operate adequately and screenings are dumped
Into a dumpster located on the influent concrete pad.
Grit Removal
Yes No NA NE
Type of grit removal
a.Manual
❑
b.Mechanical
0
Is the grit free of excessive organic matter?
❑
❑
❑
M
Is the grit free of excessive odor?
0
❑
❑
❑
# Is disposal of grit in compliance?
N
❑
❑
❑
Comment: The facilitv's staff continues to have operational issues with the vortex grit removal system
The backwash water and the grit withdrawal pump cannot remove all of the settled grit in the
bottom chamber which causes the chamber paddles to bind . When it rains, grit
acculmulates faster due to stormwater. They continue to use the services of Triple S's
vacuum truck to remove the solids every 2 weeks to a month. This is expensive and time
consuming. The town should address this ongoing problem.
Flow Measurement - Influent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
1 -MIN.7►/_MMM
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 5
Permit: NC0003450 Owner -Facility: Wallace Regional WWTP
Inspection Date: 08/25/2016 Inspection Type: Compliance Evaluation
Flow Measurement - Influent Yes No NA NE
(If units are separated) Does the chart recorder match the flow meter? ❑ ❑ N ❑
Comment: The flow meter was calibrated on 5-19-16 by Glover Instruments and Controls
Influent Sampling
Yes No NA NE
# Is composite sampling flow proportional?
N
❑
❑
❑
Is sample collected above side streams?
i
❑
❑
❑
Is proper volume collected?
❑
❑
❑_
■
Is the tubing clean?
The operator understands and can explain the process?
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees
N
❑
❑
❑
Celsius)?
0
❑
❑
❑
Is sampling performed according to the permit?
®
❑
❑
❑
Comment: No Comment
Sequencing Batch Reactors
Yes No NA NE
Type of operation:
Duplex
depending on utility costs.
Is the reactor effluent free of solids?
N ❑
❑
❑
Does minimum fill time correspond to the peak hour flow rate of the facility?
❑ ❑
❑
N
Is aeration and mixing cycled on and off during fill?
❑
❑
❑
The operator understands and can explain the process?
❑
❑
❑
Comment: The ORC has a good understandinq of the SBR operation. Currently the plant runs two of
the three batch reactors efficiently,
but the third reactor might be put on-line this winter
depending on utility costs.
Aerobic Digester
Yes No NA NE
Is the capacity adequate?
M
❑
❑
❑
Is the mixing adequate?
M
❑
❑
❑
Is the site free of excessive foaming In the tank?
0
❑
❑
❑
# Is the odor acceptable?
0
❑
❑
❑
# Is tankage available for properly waste sludge?
0
❑
❑
❑
Comment: Solids from the sludge thickener is disposed of off site by subsurface infection by Triple S
Pump Station - Effluent Yes No NA NE
Is the pump wet well free of bypass lines or structures? 0 ❑ ❑ ❑
Are all pumps present? 0 ❑ ❑ ❑
Page# 6
Permit: NC0003450
Inspection Date: 08/25/2016
Owner -Facility: Wallace Regional WWrP
Inspection Type: Compliance Evaluation
Type of operation:
Cross flow
❑
Pump Station - Effluent
Yes No NA NE
Are all pumps operable?
0
❑
❑
❑
Are float -controls operable?
❑
❑
❑
0
Is SCADA telemetry available and operational?
❑
❑
❑
S
Is audible and visual alarm available and operational?
❑
❑
❑
0
Comment: Decanted effluent is stored in an 2 3 MG above ground aerated tank before it is processed
through the tertiary drum filters.
Filtration (High Rate Tertiary)
Yes No NA NE
Type of operation:
Cross flow
❑
❑
Is the filter media present?
0 ❑
❑
❑
Is the filter surface free of clogging?
❑ ❑
❑
0
Is the filter free of growth?
0 ❑
❑
❑
Is the air scour operational?
❑ ❑
❑
■
Is the scouring acceptable?
❑ ❑
❑
0
Is the clear well free of excessive solids and filter media?
0 ❑ •
❑
❑
Comment: Algae has built up in the effluent storage tank and sometimes causes problems as it passes
through to the tertiary disk filter system. The weight of the algae
puts a strain on the drive
belt of the disk filters and sometimes makes it inoperable. Facility
is planning on removinq
algae in the effluent storage tank manuallV.
Disinfection,- UV
Are extra UV bulbs available on site?
Are UV bulbs clean?
Is UV intensity adequate?
Is transmittance at or above designed level?
Is there a backup system on site?
Is effluent clear and free of solids?
Comment: No comment.
Yes No NA NE
M ❑ 1:11:1
M ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ M
❑ ❑ ■ ❑
■ ❑ ❑ ❑
Flow Measurement - Effluent
Yes No NA NE
# Is flow meter used for reporting?
M
❑
❑
❑
Is flow meter calibrated annually?
M
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
M
❑
Comment: The effluent flow meter was calibrated on 5-19-16 by
Glover Instruments and Controls.
Page# 7
Permit: NC0003450 Owner - Facility: Wallace Regional WWTP
Inspection Date: 08/25/2016 Inspection Type: Compliance Evaluation
Flow Measurement- Effluent Yes No NA NE
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Yes No NA NE
M ❑ ❑ ❑
M ❑ ❑ ❑
❑ ❑ ❑ ■
■ ❑ ❑ ❑
® ❑ ❑ ❑
M ❑ ❑ ❑
Comment. The effluent sampler is located at the effluent discharge point approximately 1 mile away
from the VWVfF but very secured. The sampler has a lock on the control panel the tubing
connection and the sampler door. In addition there's a lock on the gate of the fenced area
and a lock on the gate at the beginning of the dirt road that leads to site
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and 0 ❑ ❑ ❑
sampling location)?
Comment: No comment.
Effluent Pipe
Yes No
NA NE
Is right of way to the outfall properly maintained?
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
0
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
0
❑
Comment: No comment
Page# 8