HomeMy WebLinkAboutNC0050105_Compliance Evaluation Inspection_20160614 PAT MCCRORY Governor DONALD R. VAN DER VAART Secretary Water Resources S. JAY ZIMMERMAN ENVIRONMENTAL QUALITY Director June 14, 2016 Mick J Noland PWC/Fayetteville PO Box 1089 Fayetteville, NC 28302 SUBJECT: 6/3/2016 Compliance Evaluation Inspection PWC/Fayetteville Rockfish Creek WWTP Permit No: NC0050105 Cumberland County Dear Mr Noland: Enclosed please find a copy of the Compliance Evaluation Inspection form from the inspection conducted on 6/3/2016. The Compliance Evaluation Inspection was conducted by Mark Brantley, Environmental Program Consultant, of the Fayetteville Regional Office. The facility was found to be in Compliance with permit NC0050105. The cooperation of Mr. Scott McCoy, facility ORC,was greatly appreciated. As a reminder, preservation of the Waters of the State can only be achieved through consistent NPDES Permit compliance. Comments • Facility was clean and neat in appearance at the time of the inspection. This facility is also well maintained and operated by a very knowledgeable operations staff. • Maintenance records,work orders, and ORC logs are maintained through an electronic work order system. • Only the field parameter section of the Laboratory was inspected due to construction/remodeling activities that were being performed at the Cross Creek Laboratory. The Cross Creek Laboratory was inspected by the Laboratory Certification Branch in July 2015. • The relocation of the effluent sample equipment was discussed during the inspection. The Fayetteville Regional Office understands that the sample pump and refrigerator may be moved to a more convenient location but the sample point will remain the same (at the bottom of the cascade). Fayetteville Regional Office 225 Green Street,Suite 714,Fayetteville,North Carolina 28301-5095 Main Phone: 910-433-3300 1 Internet: http:/hvww.ncdenr.gov An Equal Opportunity 1 Affirmative Action Employer—Made in part by Recycled Paper Mr. Noland Page 2 June 14, 2016 Please refer to the enclosed inspection report for additional observations and comments. If you or your staff have any questions, please call me at 910-433-3327. Sincerely, Mark Brantley Environmental Program Consultant Division of Water Resources Water Quality Regional.Operations Section cc: Michael Scott McCoy,ORC Central Files FiieL2ldt5 a; United states Envirormentel Protection Agency Form Approved. EPA vvesi'inoton.D.C.20460 OMB No.2040-0057 Water Compliance Inspection Report Approval expires831-98 Section A:National Data System Coding(I.e.,PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN I 2 3 NC0050105 111 121 ¶6/08/03 117 181,.1 19 I c I 201 I 2111111111 1111111 11 11 1 11 1111 1 1 11111 1111111 111L 1 r Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 OA Reserved 671 1 701IJ, I 71 I I 72 ILJ u I 731 1 174 7511 1 1 1 1 1 1 180 Section B:FacilityFacilityData Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 09:30AM 18/06/03 13/01/01 Roddnh Creek WWTP Edi Time/Date Penna Expiration Date 2538 Tracey Hall Rd 12:00PM 18/08/03 18/10/31 Fayetteville NC 28308 Names)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data I// Michael Scott McCoy/ORC/910-223-4757/ Name,Address of Responsible Offidarltle/Phone and Fax Number Contacted Mick J Noland,PO Box 1089 Fayetteville NC 2830210891/910.223-4733/ No Section C:Areas Evaluated During Inspection(Check only those areas evaluated) a Permit • Flow Measurement II Operations&Maintenance II Records/Reports •Self-Monitoring Program •Sludge Handling Disposal • Facility Site Review • Effluent/Receiving Waters Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s)and Signatures)of Inspector(s) Agency/Office/Phone and Fax Numbers Date Mad( Brantley FRO WO//910-433-3300 Fxt727/ "'a 4,44. ‘. Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date itWIa Fje6� D !SE FSO WW/910-433-3300 Ext72( 4 '15 - 1 EPA Form 3580.3(Rev 9-94)Previous editions are obsolete. Page% 1 NPDES yr/me/day Inspection Type (Cont) 1 3I NC0050105 111 121 16/06/03 117 18 [2j Section D:Summary of Finding/Comments(Math additional sheets of narrative and checklists as necessary) Comments Facility was clean and neat in appearance at the time of the inspection. This facility is also well maintained and operated by a very knowledgeable operations staff. Maintenance records,work orders, and ORC logs are maintained through an electronic work order system. Only the field parameter section of the Laboratory was inspected due to construction/remodeling activities that were being performed at the Cross Creek Laboratory.The Cross Creek Laboratory was inspected by the Laboratory Certification Branch in July 2015. The relocation of the effluent sample equipment was discussed during the inspection. The Fayetteville Regional Office understands that the sample pump and refrigerator may be moved to a more convenient location but the sample point will remain the same(at the bottom of the cascade). Page* 2 Permit NC0050105 Owner_Faculty: Roddlsh Creels NNyTP Inspection Date: 08/03/2018 Inspection Type: Compliance Evaluation Operations& Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? • ❑ 0 0 Does the facility analyze process control parameters,for ex: MLSS, MCRT, Settleable • ❑ 0 0 Solids,pH, DO,Sludge Judge,and other that are applicable? Comment: Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new • ❑ 0 0 application? Is the facility as described in the permit? • ❑ 0 0 #Are there any special conditions for the permit? 0 0 • El Is acrogc to the plant site restricted to the general public? • 0 0 0 Is the inspector granted access to all areas for inspection? • 0 0 0 Comment: Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? • 0 0 0 Is all required information readily available,complete and current? • 0 0 0 Are all records maintained for 3 years(lab.reg. required 5 years)? • 0 0 0 Are analytical results consistent with data reported on DMRs? 0 0 0 U Is the chain-of-custody complete? • 0 0 0 Dates,times and location of sampling • Name of individual performing the sampling • . Results of analysis and calibration Dates of analysis • Name of person performing analyses • Transported COCs • Are DMRs complete:do they include all permit parameters? • 0 0 0 Has the facility submitted its annual compliance report to users and DWQ? • 0 0 0 (If the facility is=or>5 MGD permitted flow)Do they operate 2417 with a certified operator • 0 0 0 on each shift'? Is the ORC visitation log available and current? U 0 0 0 Is the ORC certified at grade equal to or higher than the facility dassification? • 0 0 0 Is the backup operator certified at one grade less or greater than the facility dassitcation? • 0 0 0 Is a copy of the current NPDES permit available on site? • 0 0 0 Page# 3 Permit NC0050105 Owner-Facility: Rockfish Creek WNW Inspection Date: 06/03/2016 inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Facility has copy of previous year's Annual Report on file for review? • 0 ❑ 0 Comment: Effluent Pipe Yes No NA NE Is right of way to the outfall property maintained? • 0 0 0 Are the receiving water free of foam other than trace amounts and other debris? • 0 0 0 If effluent (diffuser pipes are required) are they operating properly? 0 0 • 0 Comment: Flow Measurement-Effluent Yes No NA NE #Is flow meter used for reporting? • 0 0 0 Is flow meter calibrated annually? • 0 0 0 Is the flow meter operational? • 0 0 0 (If units are separated)Does the chart recorder match the flow meter? 0 0 • 0 Comment: Aerobic Digester Yes No NA NE Is the capacity adequate? • 0 0 0 Is the mbdng adequate? • 0 0 0 Is the site free of excessive foaming in the tank? • 0 0 0 #Is the odor acceptable? • 0 0 0 #Is tankage available for properly waste sludge? • 0 0 0 Comment: Solids Handling Equipment Yes No NA NE Is the equipment operational? • 0 0 0 Is the chemical feed equipment operational? • 0 0 0 Is storage adequate? • 0 0 0 Is the site free of high level of solids in filtrate from filter presses or vacuum filters? • 0 0 0 Is the site free of sludge buildup on belts and/or rollers of filter press? • 0 0 0 Is the site free of excessive moisture in belt filter press sludge cake? 0 0 0 10 The facility has an approved sludge management plan? • 0 0 0 Comment: Page# 4 Permit NC0050105 Owner-Facility: Rockfish Creek WWTP Inspection Date: 06/03/2016 Inspection Type: Compliance Evaluation Chemical Feed Yes No NA NE Is containment adequate? • ❑ 0 0 Is storage adequate? • 0 0 0 Are backup pumps available? • 0 0 0 Is the site free of excessive leaking? • 0 0 0 Comment: Pump Station -Influent Yea No NA NE Is the pump wet well free of bypass lines or structures? • 0 0 0 Is the wet well free of excessive grease? • 0 0 0 Are all pumps present? • 0 0 0 Are all pumps operable? • 0 0 0 Are float controls operable? 0 0 10 0 Is SCADA telemetry available and operational? • 0 0 0 Is audible and visual alarm available and operational? 0 0 II 0 Comment: Bar Screens Yes No NA NE Type of bar screen a.Manual ❑ b.Mechanical • Are the bars adequately screening debris? • 0 0 0 Is the screen free of excessive debris? • 0 0 0 Is disposal of screening in compliance? U 0 0 0 Is the unit in good condition? • 0 0 0 Comment: Facility is reviewing plans to replace the current bar screens with a newer unit that is more efficient and easier to maintain. Grit Removal Yes No NA NE Type of grit removal a.Manual 0 b.Mechanical • Is the grit free of excessive organic matter? • 0 0 0 Is the grit free of excessive odor? • 0 0 0 Page! 5 Permit NC0050105 Owner-Facility: Rockfish Creek VAMP Inspection Date: 06103/2016 inspection Typo: Compliance Evaluation Grit Removal Yes No NA NE #Is disposal of grit in compliance? • 0 0 0 Comment: Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? • 0 0 0 Is the site free of excessive buildup of solids in center well of circular clarifier? • 0 0 0 Are weirs level? • 0 0 0 Is the site free of weir blockage? U 0 0 0 Is the site free of evidence of short-circuiting? • 0 0 0 Is scum removal adequate? • 0 0 0 Is the site free of excessive floating sludge? • ❑ 0 0 Is the drive unit operational? • 0 0 0 Is the return rate acceptable(low turbulence)? • 0 ❑ 0 Is the overflow clear of excessive solids/pin floc? • 0 0 0 Is the sludge blanket level acceptable?(Approximately Y.of the sidewall depth) • 0 0 0 Comment: Aeration Basins Yes No NA NE Mode of operation Ext Air Type of aeration system Diffused Is the basin free of dead spots? 110 ❑ ❑ Are surface aerators and mixers operational? 0 ❑ • 0 Are the diffusers operational? .10 ❑ ❑ Is the foam the proper color for the treatment process? U 0 0 0 Does the foam cover less than 25%of the basin's surface? • 0 0 ❑ Is the DO level acceptable?. U Cl 0 0 Is the DO level acceptable?(1.0 to 3.0 mg/I) • ❑ 0 0 Comment: Filtration (HIab Rate Tertiarvl Yes No NA NE Type of operation: Is the filter media present? U 0 0 ❑ Is the filter surface free of dogging? U 0 0 0 Page# 6 • • Permit NC0080105 Owner-Facility: Rockfish Creek WM? Inspection Date: 08/03/2018 Inspection Type: Compliance Evaluation Filtration (Hiah Rate Tertiary' Yes No NA NE Is the filter free of growth? • 0 0 0 Is the air scour operational? • 0 0 0 Is the scouring acceptable? • 0 0 0 Is the clear well free of excessive solids and fitter media? • 0 0 0 Comment: • De-chlorination Yes No NA NE Type of system? Is the feed ratio proportional to chlorine amount(1 to 1)? • 0 0 0 Is storage appropriate for cylinders? • 1:100 #Is dechlorination substance stored away from chlorine containers? • 0 0 0 Comment: Are the tablets the proper size and type? 0 0 • 0 Are tablet de-chlorinators operational? 0 0 • 0 Number of tubes in use? Comment: Standby Power Yes No NA NE Is automatically activated standby power available? • 0 0 0 Is the generator tested by interrupting primary power source? • 0 0 0 Is the generator tested under load? • 0 0 0 Was generator tested&operational during the inspection? 0 0 0 • Do the generator(s)have adequate capacity to operate the entire wastewater site? • 0 ❑ 0 Is there an emergency agreement with a fuel vendor for extended run on back-up power? • 0 0 0 Is the generator fuel level monitored? • 0 0 0 Comment: Disinfection-Liquid Yes No NA NE Is there adequate reserve supply of disinfectant? • 0 0 0 (Sodium Hypochlorite)Is pump feed system operational? • 0 0 0 is bulk storage tank containment area adequate?(free of leaks/open drains) • 0 0 0 Is the level of chlorine residual acceptable? • 0 0 0 Is the contact chamber free of growth,or sludge buildup? • 0 0 0 Page/ 7 • Permit NC0050106 Owner-Polity: Rad(fieh Creek W WTP Inspection Date: 06/03/2016 inspection Type: Compliance Evaluation Disinfection-Liquid Yes No NA NE Is there chlorine residual prior to de-chlorination? • ❑ ❑ 0 Comment: Influent Sampling Yes No NA NE #Is composite sampling flow proportional? • 0 0 ❑ Is sample collected above side streams? • 0 0 0 Is proper volume collected? • ❑ ❑ 0 Is the tubing dean? • 000 #Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees • 000 Celsius)? Is sampling performed according to the permit? • 0 0 0 Comment: Effluent Sampling Yes No NA NE Is composite sampling flow proportional? • 000 Is sample collected below all treatment units? • ❑ ❑ ❑ Is proper volume collected? • 000 Is the tubing clean? • 0 ❑ ❑ #Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees • 000 Celsius)? Is the facility sampling performed as required by the permit(frequency,sampling type • ❑ .❑ ❑ representative)? Comment: Upstream/Downstream Sampling Yes No NA NE Is the facility sampling performed as required by the permit(frequency,sampling type,and 00 • 0 sampling location)? Comment: Facility is a member of the Middle Care Fear River Basin Association. Page# 8 INFLUENT ADF=12.4 MGD ,sssssssssssssss' INFLUENT PUMP STATION FBW PTE ML NPW SH SB FCE WAS ADF MGD FE M G LEGEND BARSCREENS CAPE FEAR RIVER FILTER BACKWASH PRIMARY TREATMENT EFF MIXED LIQUOR NONPOTABLE WATER SODIUM HYPOCHLORITE SODIUM BISULFITE FINAL CLARIFIER EFF WASTE ACTIVATED SLUDGE AVERAGE DAILY FLOW MILLION GALLONS PER DAY FILTER EFFLUENT MAGMETER GRINDER FLOW SPLITTER BOX STIRRED VORTEX GRIT COLLECTORS PTE 0=2.75 MGD TO AERATION BASINS 1, 2 AND 3 PTE 0=2.07 MGD BASINS 4 AND 5 BLOWER BUILDING CASCADE AERATOR PTE PTE PTE PTE AIR CHLORINE CONTACT TANKS RAS AERATION BASIN NO. 5 AERATION BASIN NO. 4 AERA11ON BASIN NO. 3 AERATION BASIN NO. 2 AERATION BASIN NO. 1 RAS Q=1.03 MGD TO AERATION BASINS 1, 2 AND 3 RAS Q=1.38 MGD TO AERATION BASINS 4 AND 5 Q=6.2 MGD SB NO. 1 NO. 2 NO. 3 FUTURE NO. 4 SB ML FILTER EFFLUENT CHANNEL RAS SH FBW Q=.8 MGD FILTERS NO. 1 NO. 2 NO. 3 NO. 4 G) RAS PUMPS FINAL CLARIFIER NO. 2 FINAL CLARIFIER NO. 1 RAS/WAS PUMPING STATION SCUM PUMP FCE WAS PUMPS SCUM PUMP D--Ce c FCE FILTER INFLUENT SH CHANNEL FCE Q=12.4 MGD ML Q=6.2 MGD i i FUTURE FINAL CLARIFIER • De4 RAS PUMPS —Col— H He _ FCE SH NO. 5 NO. 6 FILTER BYPASS CHANNEL SH f FINAL CLARIFIER NO. 3 H EFF PARSHALL FLUME- 41 NPW PUMP STATION FE Q=12.3 MGD NPW PUMP WET WELL CHLORINATION BUILDING �DECHLORINATION BUILDING TO NPW ® SYSTEM Q=.9 MGD SB STANDBY POWER GENERATOR 2000 KW ROCKFISH CREEP RECLAMATION F WAS Q=.12 MGD3 SCUM s SCUM s AEROBIC DIGESTERS 5 TANKS 1.16 MG EACH NO..5 DdJ NO. 4 D4 NO. 3 D4 NO. 2 x B NO. 1 DECANT TO PLANT DRAIN % B AERATED SLUDGE STORAGE TANKS 3 TANKS .7 MG EACH NO. 3 NO. 2 NO. 1 GRAVITY BELT THICKENERS 2-3 METER GBTS POLYMER — GB-2 x X SLUDGE PUMPS 4 600 GPM EACH THICKENED SLUDGE TANKS GB-1 SP-4 SP-3 IQ THICKENED SLUDGE PUMPS SOLIDS HANDLING BUILDING TSP-2 TSP-1 SP-2 DC SP-1 BIOSOLIDS TO. LAND APPLICATION ROCKFISH CREI RECLAMATION