HomeMy WebLinkAboutNC0061425_Site Visit_20160411Mr. Jadd Brewer Water Quality Utilities, Inc. P.O. Box 1167 Banner Elk, NC 28604-1167 SUBJECT: Dear Mr. Brewer: April 11, 2016 Compliance Evaluation Inspection Willow Valley WWTP NPDES Permit # NCO061425 Watauga County PAT NICCRORY i,nbP. nor DONALD R. VAN DER VAART Seuclar S. JAY ZIMMERMAN Urreclor RECENEDINCDE0]D\1VR APR 13 2016 Water Quality ecion Permitting A Compliance Evaluation Inspection was performed on the facility by George Smith, along with April Norton on March 23, 2016. Mr. Brandon Hughes, ORC, Grade II; Mr. Jadd Brewer, Back-up ORC, Grade III; were present for the inspection. The inspection is comprised of an overall evaluation of the facilities equipment, capability to meet effluent limits, and compliance with the NPDES permit. Permit Your new NPDES permit became effective October 1, 2012 and expires September 30, 2017. This office received a copy of the letter dated February 17, 2016 requesting the facility be changed from composite to grab sampling, since the permitted flow is 0.03 MGD. Records & Reports The operator and plant log are printed on a form showing visitation times and plant conditions. The log will be examined more thoroughly during the next year inspection for visitation times, observations, and process control. The chain of custody forms and calibrations records are in good order. Calibrations for field tests were documented for pH, Temperature and Dissolved Oxygen. Facility Site Review The plant is adjacent to a golf course tee box. A new fence is being installed. A gravel base has been placed around the treatment units. The manual 'A inch barscreen is acceptable. The equalization basin blower motor was being repaired There are two in -ground aeration basins. The basin on the right side is not used. The course bubble diffusers are delivering a good rolling action. The mixed liquor appeared light brown color with less than 10% of the surface of the basin covered with tan foam. Also, lime is added to the plant. a At the time of the inspection there was a lot of laundry detergent entering the plant. Mr. Brewer indicated that there are no adverse impacts. The clarifier effluent was clear. The Trojan 2000 UV disinfection unit is working. The indicator lights on the UV were not illuminated. The previous inspection showed that three of the four lights were illuminated. Flow Measurement Continuous flow measurement at the plant is performed using a 22 '/2 ° V -notch weir with an ultrasonic device mounted before the effluent weir. The flow measuring device was calibrated by B.W. Allen on October 8, 2015. Laboratory Water Quality Lab, Inc. #544 is certified, and performed the following field tests: Dissolved Oxygen, pH, and temperature. The pH meter is calibrated with a two-point buffer of 4 & 10, and check with a pH 7 buffer. A calibration log was kept for pH and dissolved oxygen. Temperature is traceable to NIST. Effluent/Receiving Waters The effluent, which discharges to Laurel Fork, Class C Trout waters, was clear and had no color, solids, or odor. The stream is not impacted from this discharge. Operations & Maintenance The Class II facility was maintained by the following contingent: Mr. Brandon Hughes, ORC, Grade II and Mr. Jadd Brewer, Back-up ORC, Grade I1I. Self -Monitoring Program The effluent is sampled using a time composite method at 100 mL/hour. The NPDES requirement for flow proportion sampling will not be addressed at this time. The NPDES Unit is reviewing the request to change the permit from flow proportional sample to grab sample. A review of the monthly self-monitoring reports from August 2015 through January -2016 showed no limit violations. The compliance inspection is considered satisfactory. Mr. Hughes does a very good job maintaining the facility. If you have any questions, please contact George Smith or me at (336) 776-9800. Sincerely, .,44,,,E Sherri V Knight, PE, Regional Supervisor Water Quality Regional Operations Section Division of Water Resources, NCDEQ cc: NPDES°Unit`Joe=Corporon WSRO Files United Stales Environmental Protection Agency Form Approved. EPA Washington, D C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A. National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN I - 2 15 I 3 I NCO061425 I11 12 16/03/23 17 18 I, I 19 I ! j 20I 211111 1 1 1 1 1 1 II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I f6 Inspection Work Days Facility Self -Monitoring Evaluation Rating 61 QA -Reserved — N I 731 LJJ4 75 80 I 72 IJ 67 70 [LJ z j 71 [-JL Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 09 28AM 16/03/23 13/02/01 Willow Valley Resort WWTP Bairds Creek Rd Exit Time/Date Permit Expiration Date Boone NC 28607 09 40AM 16/03/23 17/09/30 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Brandon K Hughes/ORC/828-260-5213/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Jadd W Brewer, //828-898-6277/ No Section C. Areas Evaluated During Inspection (Check only those areas evaluated) Permit ® Flow Measurement ® Operations & Maintenance ® Records/Reports Self -Monitoring Program Facility Site Review Effluent/Receiving Waters Section D Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date George S Smith WSRO WQH336-776-9700/ Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date t Zr.4ice. /�z !G�=Jc EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# Permit: NCO061425 Owner - Facility: Willow Valley Resort WWTP Inspection Date: 03/23/2016 Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? ! ❑ ❑ ❑ Does the facility analyze process control parameters, for ex- MLSS, MCRT, Settleable ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ M ❑ application? ❑ ❑ ❑ ❑ Is the facility as described in the permit? M ❑ ❑ ❑ # Are there any special conditions for the permit? M ❑ ❑ ❑ Is access to the plant site restricted to the general public? ■ ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? O ❑ ❑ ❑ Comment. Temporary means od disinfection required Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? ❑ ❑ ❑ ❑ Is all required information readily available, complete and current? ❑ ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? ® ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? ® ❑ ❑ ❑ Is the chain -of -custody complete? ® ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? M ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ M ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ 0 ❑ on each shift? Is the ORC visitation log available and current? M ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility, classification? M ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? 0 ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? 0 ❑ ❑ ❑ Page# 3 Permit: NCO061425 Owner -Facility: willow Valley Resort WWTP Inspection Date: 03/23/2016 Inspection Type: Compliance Evaluation, Record Keeping Yes No NA NE Facility has copy of previous year's Annual Report on file for review? ❑ ❑ S ❑ Comment: Flow Measurement - Effluent # Is flow meter used for reporting? Is flow meter calibrated annually? Is the flow meter operational? (If units are separated) Does the chart recorder match the flow meter? Comment: Equalization Basins Is the basin aerated? Is the basin free of bypass lines or structures to the natural environment? Is the basin free of excessive grease? Are all pumps present? Are all pumps operable? Are float controls operable? Are audible and visual alarms operable? # Is basin size/volume adequate? Comment. Aeration Basins Mode of operation Type of aeration system Is the basin free of dead spots? Are surface aerators and mixers operational? Are the diffusers operational? Is the foam the proper color for the treatment process? Does the foam cover less than 25% of the basin's surface? Is the DO level acceptable? Is the DO level acceptable?(1.0 to 3.0 mg/1) Comment: Yes No NA NE ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ ❑ Yes No NA NE ® ❑ ❑ ❑ ■ ❑ ❑ ❑ ® ❑ ❑ ❑ ® ❑ ❑ ❑ M ❑ ❑ ❑ M ❑ ❑ ❑ M ❑ ❑ ❑ ❑ ❑ ® ❑ Yes No NA NE Ext. Air Diffused ■ ❑ ❑ ❑ ❑ ❑ N ❑ ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ N ❑ ❑ ❑ E ❑ ❑ ❑ ❑ ❑ ❑ ■ Page# 4 �l Permit: NC0061425 Owner - Facility: Inspection Date: 03/23/2016 Inspection Type: Willow Valley Resort WWTP Compliance Evaluation Are extra UV bulbs available on site? ❑ ❑ Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? ■ ❑ ❑ ❑ Is the site free of excessive buildup of solids In center well of circular clarifier? ❑ ❑ 0 ❑ Are weirs level? ■ ❑ ❑ ❑ Is the site free of weir blockage? ! ❑ ❑ ❑ Is the site free of evidence of short-circuiting? 0 ❑ ❑ ❑ Is scum removal adequate? M ❑ ❑ ❑ Is the site free of excessive floating sludge? 0 ❑ ❑ ❑ Is the drive unit operational? ❑ ❑ N ❑ Is the return rate acceptable (low turbulence)? ❑ ❑ ❑ ■ Is the overflow clear of excessive solids/pin floc? ® ❑ ❑ ❑ Is the sludge blanket level acceptable? (Approximately %4 of the sidewall depth) ❑ ❑ ❑ 0 Comment: Disinfection - UV Yes No NA NE Are extra UV bulbs available on site? ❑ ❑ ❑ Are UV bulbs clean? ® ❑ ❑ ❑ Is UV Intensity adequate? 0 ❑ ❑ ❑ Is transmittance at or above designed level? ® ❑ ❑ ❑ Is there a backup system on site? _ 0 ❑ ❑ ❑ Is effluent clear and free of solids? N ❑ ❑ ❑ Comment: Not sure the transmittance is acceptable, the indicator lights were not illuminated Page# 5 1