HomeMy WebLinkAboutNC0086541 Compliance Inspection 2016 PAT MCCRORY
DONALD R. VAN DER VAART
Water Resources S. JAY ZIMMERMAN
t:NVIHoNMtL.NYAL QUAL'..' '! ....•.
February 3, 2016
RECEIVED/NCDEQ/DWR
Mr. James C. Duncan, Chief Engineer Manager
Cousins Properties Inc. FEB 1 1 2(1:h
800 W. Trade Street, Suite 100
Charlotte, NC 28202 Water Quality
Permitting Section
Subject: Compliance Evaluation Inspection
Gateway Village
Ground water remediation
NPDES Permit No. NC0086517
Mecklenburg County
Dear Mr. Duncan:
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted at
the subject facility on January 27, 2016 by Ori Tuvia and Ed Watson. Your cooperation during the
site visit was much appreciated. Please advise the staff involved with this NPDES Permit by
forwarding a copy of the enclosed report.
As was discussed on site please have ORC logs available for inspection during future
inspections.
Additionally, PH calibration must be done prior to sampling, and calibration logs need
reflect that. Calibration logs for 11/19/2015 and 2/27/2015 indicate PH meter was calibrated after
sampling.
The report should be self-explanatory; however, should you have any questions concerning
this report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at
ori.tuvia@ncdenr.gov.
Sincerely,
Ori Tuvia, Environmental Engineer
Mooresville Regional Office
Division of Water Resources, DEQ
Cc: NPDES (Derek Denard)
MRO Files
Hunter Hicks, PE (E-Copy)
Mooresville Regional Office
Location:610 East Center Ave.,Suite 301 Mooresville,NC 28115
Phone:(704)663-1699\Fax(704)663-6040\Customer Service:1-877-623-6748
United States Environmental Protection Agency Form Approved.
EPA Washington,D.C.20460 OMB No.2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A:National Data System Coding(i.e.,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 u 2 [ 1 3 I N00086517 111 12 I 16/01/27 117 18 I c I 19 1 s I 201 I
21111111 1111111111111111111111111 11111111111 p6
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA — -----Reserved-----------
67 11.0 1 701LJ 4 1 71 Iti 1 72 1 ti LJ 73I 1 (74 75I 1 I I I I I 180
Section B:Facility Data
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
POTW name and NPDES permit Number) 11:50AM 16/01/27 15/09/01
Gateway Village remediation site
800 W Trade St Exit Time/Date Permit Expiration Date
Charlotte NC 28202 01:30PM 16/01/27 20/06/30
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
///
Hunter Hicks///
James Duncan///
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
Randall Miller,800 W Trade St Charlotte NC 28202/Properly Manager/704-683-0104/
No
Section C:Areas Evaluated During Inspection(Check only those areas evaluated)
III Permit • Flow Measurement II Operations&MaintenancE • Records/Reports
Self-Monitoring Program • Sludge Handling Disposal $ Facility Site Review • Effluent/Receiving Waters
Laboratory
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Edward Watson MRO GW///
On A Tuvia MRO WQ//704-663-1699/
J
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
William C Basinger MRO WQ//704-235-2194/
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete. p
�ti76���' a.*yy
'fir J Mj � ® I
�Y) Page# 1
NPDES yr/mo/day Inspection Type 1
31 N00086517 111 121
16ro1/27 117 18 ,^,
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
Notes by Ed Watson.
A pattern was identified with regards to the on-site GAC containers. Lab results indicate Carbon
breakthroughs on an average of 6 month intervals. Manifest for spent carbon has been request to
document disposal of spend Carbon.
There are currently two sumps in place at this site. Only one sump is currently active. The treated
water is discharged into adjacent storm drain as per the NPDES permit therefore no outfall discharge
was able to be viewed.
Page# 2
Permit: NC0086517 Owner-Facility: Gateway Village remediation site
Inspection Date: 01/27/2016 Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new 0 0 • 0
application?
Is the facility as described in the permit? U 0 0 0
#Are there any special conditions for the permit? ❑ II 0 0
Is access to the plant site restricted to the general public? • 0 0 0
Is the inspector granted access to all areas for inspection? • 0 0 0
Comment: A copy of the permit is kept on site.
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? • 0 0 0
Is all required information readily available, complete and current? 0 • 0 0
Are all records maintained for 3 years(lab. reg. required 5 years)? • 0 ❑ ❑
Are analytical results consistent with data reported on DMRs? • ❑ 0 0
Is the chain-of-custody complete? • ❑ 0 0
Dates,times and location of sampling •
Name of individual performing the sampling •
Results of analysis and calibration •
Dates of analysis •
Name of person performing analyses •
Transported COCs •
Are DMRs complete:do they include all permit parameters? • 0 0 0
Has the facility submitted its annual compliance report to users and DWQ? ❑ 0 • ❑
(If the facility is=or>5 MGD permitted flow)Do they operate 24/7 with a certified operator ❑ ❑ • 0
on each shift?
Is the ORC visitation log available and current? ❑ U ❑ 0
Is the ORC certified at grade equal to or higher than the facility classification? • ❑ ❑ ❑
Is the backup operator certified at one grade less or greater than the facility classification? • ❑ ❑ 0
Is a copy of the current NPDES permit available on site? • 0 0 0
Facility has copy of previous year's Annual Report on file for review? 0 0 • ❑
Comment: No ORC logs kept on site. ORC logs were sent upon request. DMR for the years 2013-
2015 were reviewed. Records were well maintained..
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? • ❑ ❑ 0
Page# 3
Permit: NC0086517 Owner-Facility: Gateway Village remediation site
Inspection Date: 01/27/2016 Inspection Type: Compliance Evaluation
Laboratory Yes No NA NE
Are all other parameters(excluding field parameters)performed by a certified lab? • 0 0 0
#Is the facility using a contract lab? • ❑ 0 0
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees • 0 0 0
Celsius)?
Incubator(Fecal Coliform)set to 44.5 degrees Celsius+/-0.2 degrees? 0 0 • ❑
Incubator(BOD)set to 20.0 degrees Celsius+/-1.0 degrees? 0 0 IN 0
Comment: Research and Analytical perform sampling and testing. PH calibration must be done prior to
sampling, and calibration logs need reflect that. Calibration logs for 11/19/2015 and
2/27/2015 indicate PH meter was calibrated after sampling.
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ 0 • ❑
Is sample collected below all treatment units? • 0 0 0
Is proper volume collected? • ❑ 0 0
Is the tubing clean? • 0 0 0
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees • 0 0 0
Celsius)?
Is the facility sampling performed as required by the permit(frequency,sampling type • 0 0 0
representative)?
Comment: Research and Analytical perform sampling and testing. Facility has been approved to do
grub sampling.
Flow Measurement - Effluent Yes No NA NE
#Is flow meter used for reporting? U 0 0 0
Is flow meter calibrated annually? • ❑ 0 0
Is the flow meter operational? • 0 0 0
(If units are separated)Does the chart recorder match the flow meter? • 0 0 0
Comment: average flow of 0.01 MGD
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • 0 0 0
Does the facility analyze process control parameters,for ex: MLSS, MCRT, Settleable ❑ 0 U ❑
Solids,pH, DO, Sludge Judge,and other that are applicable?
Comment: The site has two sumps. There is one active sump receiving ground water from the entire
acreage of the site,4.19 AC. Flow from the sump is pumped into two carbon filters
connected in series. Carbon in filters is replaced twice a year by Haz-Met.