HomeMy WebLinkAboutWQSV00004_Variance Request_20240130DocuSign Envelope ID: D75C8AF3-8BC0-4334-B7BB-011CCF77D921
ROY COOPER
Governor
ELIZABETH S. BISER 'fvu
Secretary
RICHAM E. ROGERS, JR. NORTH CAROLINA
Director Environmental Quality
January 30, 2024
Bruce Miller, Senior Project Manager
City of Charlotte
600 E. 4th St.
Charlotte, NC 28202
Subject: Variance Request Approval
Variance No. WQSV00004 (Permit No. WQ0044903)
Charlotte Fire Station 30 and CVOC — Sewer Main Extension
Mecklenburg County
Dear Mr. Miller:
The Division of Water Resources (Division) has reviewed the submitted variance request received on January 17,
2024 and additional information received on January 30, 2024 for the subject project. The Division will grant the
variance request for the installation of approximately 350 linear feet of 6-inch public gravity sewer in lieu of the
minimum of 8-inch as required for public gravity sewer lines per 15A NCAC 02T.0305(i)(1) in accordance with the
provisions for alternative design under 15A NCAC 02T.0105(n).
Regardless of the variance approval, in the event that the wastewater collection facilities fail to perform
satisfactorily, including the creation of nuisance conditions, the Permittee shall take immediate corrective action,
including those as may be required by this Division, such as the construction of additional or replacement facilities.
All other elements of this project shall be constructed in accordance with all applicable rules and statues including,
15A NCAC 2T; the Division of Water Resources' (Division) Gravity Sewer Minimum Design Criteria adopted February
12, 1996 as applicable; and the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations
and Force Mains adopted June 1, 2000 as applicable. Approval of the variance request does not constitute approval
of the permit.
If you have any questions, please contact Zac Lentz, P.E. at (919)-707-3620 or via email at Zac.Lentz@deg.nc.gov.
Sincerely,
EnDo'c'u,Siigne'd byy:n `1, .� Iw.'' `
C464531431644FE...
Michael Montebello, Supervisor
Municipal Unit- Pretreatment, Division of Water Resources, NCDEQ
cc: Morgan Woolner, PE of Benesch
Mooresville Regional Office, Water Quality Section Regional Operations
Water Resources Central Files: WQ0044903, WQSV00004
Municipal Unit -Collection Systems (electronic copy)
North 0krolina Department of Environmental Quality Dni sLon of Wafer Resources
D E Q�� 512 North Salisbury Street 1611 NEI Service Center Raleigh,North Carolina 27G99-1G11
NORTH OARORNA 919.707.9mo
oepnrhnmof EmimnmanW 9ual� —