HomeMy WebLinkAboutWQ0040079_Final Permit_20240117ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
STEVEN J. PINKSTON — PLANT MANAGER
CONSOLIDATED DIESEL COMPANY
POST OFFICE BOX 670
WHITAKERS, NORTH CAROLINA 27891
Dear Mr. Pinkston,
NORTH CAROLINA
Environmental Quality
January 17, 2024
Subject: Permit No. WQ0040079
Consolidated Diesel Company
WaterHub
Reclaimed Water Generation
and Conjunctive Utilization
System
Nash County
In response to your permit renewal request received on October 30, 2023, we are forwarding
herewith Permit No. WQ0040079 dated January 17, 2024, to Consolidated Diesel Company for the
continued operation of the subject reclaimed water generation and conjunctive utilization facilities.
This permit is effective from June 1, 2024, through May 31, 2032, shall replace Permit No.
WQ0040079 issued on December 21, 2022, and is subject to the conditions and limitations therein. The
Permittee shall submit a renewal application no later than December 3, 2031.
Please pay attention to the monitoring requirements listed in Attachments A and B for they may
differ from the previous permit issuance. Failure to establish an adequate system for collecting and
maintaining the required operational information may result in future non-compliance.
The Division has removed the following permit condition since the last permit issuance dated
December 21, 2022:
➢ Old Conditions L1 and L2 —The Division has removed these conditions because the Permittee
has completed the Compliance Schedules.
The following permit conditions and attachment are new or modified since the last permit
issuance dated December 21, 2022:
➢ Condition L1 — Within 90 days of this permit's effective date, the Permittee shall submit an
amended Operation and Maintenance Plan. The Permittee shall submit the amended Operation
and Maintenance Plan via the Non -Discharge online portal.
➢ Condition L2 — The Division has moved Old Condition VL5 from Section VI to Section I.
D � North Carolina Department of Environmental Quality i Division of Water Resources
512 North Salisbury Street 11617 Mail Service Center I Raleigh, North Carolina 27699-1617
NORTH CAROLINA
,.,roMMm 0; /I 919,707,9000
Mr. Steven J. Pinkston
January 17, 2024
Page 2 of 2
➢ Condition IIL 14 — The Division has modified Old Condition IIL 14 to replace "City of Rocky
Mount Permit No. 1900" with "Permit No. NCO030317 — IUP 91900 (Tar River Regional
WWTP)"
➢ Condition IIL17 — Reclaimed water used for activities other than irrigation shall not cause
exposure to aerosols.
➢ Condition IIL 18 — The Permittee or Permittee-authorized users shall not use reclaimed water
for swimming pools, hot tubs, spas, or similar uses.
➢ Condition IV.2 — The Division has modified Old Condition IV.2 to include "Parameters
measured on -site with in -line metering equipment are exempt from a Division -certified
laboratory analysis".
➢ Conditions IV.7, IV.8, and V.2 — The Division has modified the recordkeeping duration in Old
Conditions IV.7, IV.8, and V.2 from five years to eight years because this permit renewal will
be for eight years per 15A NCAC 02T .01 I I (e).
➢ Condition VI.10 — The Permittee shall pay an annual fee for each year of the term of this permit
pursuant to the schedule in G.S. 143-215.31)(a). The Permittee shall continue to pay annual
fees for any facility operating on an expired permit that the Division has not rescinded or
revoked.
➢ Attachment A — The Division has modified Footnote 1 of PPI 001 to replace "City of Rocky
Mount sewer system" with "Tar River Regional WWTP (Permit No. NCO030317 — IUP
41900)".
This permit can be contested as provided in Chapter 150B of the North Carolina General Statutes
by filing a Petition for a Contested Case Hearing (Petition) with the North Carolina Office of Administrative
Hearings (OAH) within 30 calendar days. Requirements for filing a Petition are set forth in Chapter 150B
of the North Carolina General Statutes and Title 26 of the North Carolina Administrative Code. Those
interested in filing may access additional information regarding the requirements for filing a Petition and
Petition forms at the OAH website or by calling the OAH Clerk's Office at (919) 431-3000. A party filing
a Petition shall serve a copy of the Petition on the Department of Environmental Quality's Office of General
Counsel at 1601 Mail Service Center, Raleigh, NC 27699-1601. If the party filing the Petition is not the
Permittee, then the party shall also serve the Permittee pursuant to G.S. 15013-23(a).
If you need additional information concerning this permit, please contact Zachary Mega at (919)
707-3658 or zachM.me ag (cr�,deq.nc. og_v.
Sincerely,
�
Do�cuySigned by -
Richard E. Rogers, Jr., Director
Division of Water Resources
cc: Nash County Health Department (Electronic Copy)
Raleigh Regional Office, Water Quality Regional Operations Section (Electronic Copy)
Laserfiche File (Electronic Copy)
Digital Permit Archive (Electronic Copy)
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENTAL QUALITY
RALEIGH
RECLAIMED WATER GENERATION AND CONJUNCTIVE UTILIZATION SYSTEM
PERMIT
Pursuant to the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended,
and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
Consolidated Diesel Company
Nash County
FOR THE
operation of a 75,000 gallon per day (GPD) reclaimed water generation and conjunctive utilization facility
consisting of the:
continued operation of a reclaimed water generation system consisting of. an influent screen with a flow
meter; two 175 gallon per minute (GPM) grinder pumps; two automatic screens with 2 millimeter (mm)
openings; a 71,125 gallon anoxic basin with two 2.8 horsepower (hp) mechanical mixers; a 113,000 gallon
aeration basin with two 675 cubic feet per minute (CFM) blowers; a 65,000 gallon aeration basin
(hydroponic tank) with a 337 CFM blower; two 10,533 gallon membrane tanks each supported by a 480
square meter (mZ) ceramic membrane bioreactor (MBR) unit with 80 ceramic membrane modules and
served by two I I I CFM membrane blowers, two 52 GPM permeate pumps, two 34 GPM permeate transfer
pumps, and a 1,200 gallon permeate tank; three 2 gallon per hour (GPH) sodium hypochlorite feed skid
systems; a 2 GPH citric acid feed system; a 2 GPH antiscalant feed system; a 2 GPH ammonia feed system;
a reverse osmosis (RO) filtration system with two 60.3 GPM RO booster pumps, and a 80 GPM RO clean -
in -place (CIP) pump; a 250,000 gallon chlorination tank; two 417 GPM recycle/waste activated sludge
(RAS/WAS) pumps; a 2 GPH sodium hydroxide feed system; a 2 GPH aluminum sulfate feed system; a
30,000 gallon aerobic digester; a 17 GPM utility water pump; two turbidimeters; an effluent flow measuring
device; and all associated piping, valves, controls, and appurtenances; and the
continued operation of a conjunctive utilization system consisting of a ground storage tank; a pump house;
and all associated piping, valves, controls, and appurtenances for reclaimed water utilization in a cooling
tower
to serve the Consolidated Diesel Company WaterHub, with no discharge of wastes to surface waters,
pursuant to the application received on October 30, 2023, and in conformity with the Division -approved
plans and specifications considered a part of this permit.
This permit is effective from June 1, 2024, through May 31, 2032, shall replace Permit No. WQ0040079
issued on December 21, 2022, and is subject to the following conditions and limitations:
WQ0040079 Version 2.0 Shell Version 230811 Page 1 of 9
I. SCHEDULES
1. Within 90 days of this permit's effective date, the Permittee shall submit an amended Operation and
Maintenance Plan. The Permittee shall submit the amended Operation and Maintenance Plan via the
Non -Discharge online portal. [15A NCAC 02T .0108(b)(1)(B), 02U .0108, 02U .0801(a)]
2. If the permitted facilities change ownership or the Permittee changes its name, the Permittee shall
submit a permit modification request on Division -approved forms within 90 days of the change of
ownership. The Permittee shall comply with all terms and conditions of this permit until the Division
transfers the permit to the successor -owner. [G.S. 143-215.1(d3)]
3. The Permittee shall request renewal of this permit on Division -approved forms no later than December
3, 2031. [ 15A NCAC 02T .0105(b), 02T .0109, 02U .0105, 02U .0109]
II. PERFORMANCE STANDARDS
1. The Permittee shall operate and maintain the subject reclaimed water generation and conjunctive
utilization facilities so there is no discharge to surface waters, nor any contravention of groundwater or
surface water standards. In the event the facilities do not perform as designed, including the creation
of nuisance conditions due to improper operation and maintenance, the Permittee shall take immediate
corrective actions, including Division -required actions, such as the construction of additional or
replacement reclaimed water generation and conjunctive utilization facilities, or cessation of reclaimed
water conjunctive utilization. [15A NCAC 02T .0108(b)(1)(A), 02U .0108]
2. This permit shall not relieve the Permittee of its responsibility for contravention of groundwater or
surface water standards resulting from the operation of this facility. [ 15A NCAC 02T .0108(b)(1)(A),
02U .0108]
3. Reclaimed water quality shall not exceed the limitations specified in Attachment A. [15A NCAC 02U
.0301]
4. The Permittee shall only utilize generated reclaimed water at the sites and for the activities specified in
Attachment B. [ 15A NCAC 02U .0401(a)]
5. The Permittee shall tag or label all reclaimed water valves, storage facilities, and outlets to warn the
public or employees that the reclaimed water is not for drinking. [ 15A NCAC 02U .0403(b)]
6. The Permittee shall color -code, tape, or otherwise mark all reclaimed water piping, valves, outlets, and
other appurtenances to identify the source of the water as reclaimed water as follows:
a. All reclaimed water piping and appurtenances shall be either colored purple (Pantone 522 or
equivalent) and embossed or integrally stamped or marked "CAUTION: RECLAIMED WATER -
DO NOT DRINK" or installed with a purple (Pantone 522 or equivalent) identification tape or
polyethylene vinyl wrap. The warning shall be on opposite sides of the pipe and repeated every
three feet or less.
b. Identification tape shall be at least three inches wide and have white or black lettering on a purple
(Pantone 522 or equivalent) field stating "CAUTION: RECLAIMED WATER - DO NOT
DRINK." The Permittee shall install identification tape on top of reclaimed water pipelines
fastened at least every 10 feet to each pipe length and run continuously the entire length of the pipe.
c. The Permittee shall tape or otherwise identify existing underground distribution systems retrofitted
for conveying reclaimed water as described in Paragraphs a. and b. above. The Permittee shall
perform this identification within 10 feet of any potable water supply line or sanitary sewer line
crossing a reclaimed water line. The Permittee does not need to perform this identification for the
entire length of the distribution system.
[15A NCAC 02U .0403(c)]
WQ0040079 Version 2.0 Shell Version 230811 Page 2 of 9
7. The Permittee shall secure all reclaimed water valves and outlets such that only Penn ittee-authorized
personnel can operate them. [15A NCAC 02U .0403(d)]
8. The Permittee shall place hose bibs in locked, below -grade vaults and label them non -potable. The
Permittee may place hose bibs above ground and label them non -potable if the hose bibs require a tool
to operate. [15A NCAC 02U .0403(e)]
9. There shall be no direct cross -connections between the reclaimed water and potable water systems
unless such connection is Department -approved pursuant to 15A NCAC 18C .0406. [15A NCAC 02U
.0403 ]
10. Reclaimed water distribution lines shall be at least five feet horizontally from and 18 inches below any
water line if practicable. If these separation distances cannot be met, the piping and integrity testing
procedures shall meet water main standards pursuant to 15A NCAC 18C. [ 15A NCAC 02U .0403(a),
02U .0403(h)1
11. Reclaimed water distribution lines shall not be less than 50 feet from a well unless the piping and
integrity testing procedures meet water main standards pursuant to 15A NCAC 18C, but in no case
shall they be less than 25 feet from a private well. [ 15A NCAC 02U .0403(g), 02U .0403(i)]
12. Reclaimed water distribution lines shall meet the separation distances to sewer lines pursuant to 15A
NCAC 02T .0305. [15A NCAC 02U .0403(a), 02U .0403(i)]
13. The Permittee shall operate and maintain the permitted facilities pursuant to the following setbacks:
a. The Division permitted modifications to the treatment and storage units on June 25, 2019, with an
application received on April 30, 2019, and December 21, 2022, with an application received on
September 29, 2022. The setbacks for treatment and storage units originally permitted or modified
with an application received on or after September 1, 2018, are as follows (all distances in feet):
I. Each habitable residence or place of assembly under separate ownership:
1001
ii. Each private or public water supply source:
100
iii. Surface waters:
50
iv. Each well with exception of monitoring wells:
100
v. Each property line:
50 Z
Habitable residences or places of assembly under separate ownership constructed after the
Division originally permitted or subsequently modified the facilities are exempt from this
setback.
2 Setbacks to property lines are not applicable when the Permittee, or the entity from which the
Permittee is leasing, owns both parcels separated by the property line.
[ 15A NCAC 02T .0506(b), 02U .0701(a), 02U .0701(h), 02U .0701(i)]
b. The Division originally permitted the final effluent storage units on October 26, 2018, with an
application received on June 13, 2018. The setbacks for final effluent storage units originally
permitted or modified with an application received from June 18, 2011, through August 31, 2018,
are as follows (all distances in feet):
I. Each private or public water supply source: 100
ii. Surface waters: 50
iii. Each well with exception of monitoring wells: 100
iv. Each property line: 50 1
' Setbacks to property lines are not applicable when the Permittee, or the entity from which the
Permittee is leasing, owns both parcels separated by the property line.
[ 15A NCAC 02U .0701(b)]
WQ0040079 Version 2.0 Shell Version 230811 Page 3 of 9
III. OPERATION AND MAINTENANCE
1. The Permittee shall operate and maintain the subject facilities as anon -discharge system. [15A NCAC
02U .0101]
2. The Permittee shall maintain an Operation and Maintenance Plan, which shall include:
a. A description of the operation of the system in sufficient detail to show what operations are
necessary for the system to function and who shall conduct the operations.
b. A description of the anticipated maintenance of the system.
c. Provisions for safety measures, including restriction of access to the site and equipment.
d. Spill control provisions that include response to upsets and bypasses, including control,
containment, and remediation; and contact information for personnel, emergency responders, and
regulatory agencies.
f 15A NCAC 02U .080I (a)]
3. Upon the Water Pollution Control System Operators Certification Commission's (WPCSOCC)
classification of the subject non -discharge facilities, the Permittee shall designate and employ a certified
Operator in Responsible Charge (ORC), and one or more certified operators as Back-up ORCs. The
ORC or its Back-up shall operate and visit the facilities as required pursuant to 15A NCAC 08G .0204
and 08G .0205. [ 15A NCAC 02T .0117, 02U .0117]
4. An operator certified by the Water Pollution Control System Operators Certification Commission
(WPCSOCC) of a grade equivalent or greater than the facility classification shall be on call 24 hours
per day. [ 15A NCAC 02U .0401(e)]
5. The Permittee shall only utilize reclaimed water generated from the Consolidated Diesel Company
WaterHub at the sites and for the activities listed in Attachment B. [15A NCAC 02U .0101]
6. The Permittee shall prohibit public access to the reclaimed water generation and storage facilities. [15A
NCAC 02T .0108(b)(1)(A), 02U .0108]
7. The Permittee shall control public access to reclaimed water utilization sites during active site use.
[ 15A NCAC 02U .0501(a)(2)]
8. The Permittee shall dispose of or utilize generated residuals in a Division -approved manner. [15A
NCAC 02T .1101, 02U .0802].
9. The Permittee shall not divert or bypass untreated or partially treated reclaimed water from the subject
facilities unless diverted to an alternate permitted treatment or collection system. [ 15A NCAC 02T
.0108(b)(1)(A), 02U .0108]
10. The Permittee shall establish and maintain a protective vegetative cover on all berms, pipe runs, erosion
control areas, surface water diversions, and earthen embankments (i.e., the outside toe of the
embankment to the maximum allowable temporary storage elevation on the inside of the embankment).
The Permittee shall remove all trees, shrubs, and other woody vegetation from earthen dikes and
embankments. The Permittee shall keep all earthen embankments mowed or otherwise controlled and
accessible. [15A NCAC 02U .0801(g)]
11. The Permittee shall test and calibrate metering equipment annually. [15A NCAC 02U .0801(d)]
12. The Permittee shall provide an automatically activated standby power source or other means to prevent
improperly treated wastewater from entering the storage, distribution, or utilization system. If the
Permittee employs a generator as an alternate power supply, the Permittee shall test it weekly. [15A
NCAC 02U .0401(d)]
WQ0040079 Version 2.0 Shell Version 230811 Page 4 of 9
13. The Permittee shall provide continuous online monitoring and recording for turbidity or particle count
and flow prior to storage, distribution, or utilization of reclaimed water. [ 15A NCAC 02U .0401(b)]
14. If the generated reclaimed water exceeds 10 nephelometric turbidity units (NTUs) or the pathogen
limits in Attachment A, the Permittee shall prohibit all generated reclaimed water from entering the
storage, distribution, or utilization system, and shall dispose of the generated reclaimed water pursuant
to Permit No. NCO030317 — IUP 91900 (Tar River Regional WWTP) until the reclaimed water
standards are met. [ 15A NCAC 02U .0401(c)]
15. The Permittee shall provide notification to the public and its employees about the use of reclaimed
water and that reclaimed water is not for drinking. The Permittee shall provide notification to
employees in a language they understand. [15A NCAC 02U .0501(a)(2)]
16. The Permittee shall develop and implement an education program to inform users and its employees
about the proper use of reclaimed water. The Permittee shall provide educational material to all
residents and/or other facilities provided with reclaimed water. The Permittee shall make all
educational materials available to the Division upon request. [15A NCAC 02U .0501(a)(4)]
17. Reclaimed water used for activities other than irrigation shall not cause exposure to aerosols. [ 15A
NCAC 02U .0501(b)(6)]
18. The Permittee or Permittee-authorized users shall not use reclaimed water for swimming pools, hot
tubs, spas, or similar uses. [ 15A NCAC 02U .0501(c)]
19. The Permittee shall not cultivate food chain crops in the hydroponic reactor. [15A NCAC 02T
.0108(b)(1)(A), 02U .1401]
WQ0040079 Version 2.0 Shell Version 230811 Page 5 of 9
IV. MONITORING AND REPORTING
1. The Permittee shall conduct and report any Division -required monitoring, including the monitoring of
groundwater, surface water or wetlands, waste, reclaimed water, residuals, soil, treatment processes,
lagoon or storage ponds, and plant tissue, if necessary to evaluate this facility's impact on groundwater
and surface water. [ 15A NCAC 02T .0108(c), 02U .01081
2. A Division -certified laboratory shall conduct all analyses for the required parameters specified in
Attachment A. Parameters measured on -site with in -line metering equipment are exempt from a
Division -certified laboratory analysis. [15A NCAC 02H .0805]
The Permittee shall continuously monitor flow through the treatment facility and report daily flow
values on Form NDMR. Facilities with a permitted flow of less than 10,000 GPD may estimate its
flow from water usage records provided the water source has a metering device. [15A NCAC 02T
.0105 k , 02T .0108(c), 02U .0105, 02U .01081
4. The Permittee shall monitor the generated reclaimed water at the frequencies and locations for the
parameters specified in Attachment A. [15A NCAC 02T .0105(k), 02T .0108(c), 02U .0105, 02U
.0108]
5. The Permittee shall maintain records tracking the amount of reclaimed water distributed and shall
include the following information:
a. Date reclaimed water distributed; and
b. Volume of reclaimed water distributed to each site specified in Attachment B.
The Permittee shall sum the monthly water distributed and report on Form NDMR (see Attachment A)
under parameter WQO1 (Flow, Reclaimed Water Distributed). This value shall represent the total
volume of reclaimed water distributed for that month. [ 15A NCAC 02T .0108(c), 02U .0108]
6. On or before the last day of the month following the previous month's sampling, the Permittee shall
submit monitoring data (as specified in Conditions IV.3, IVA, and IV.S) on Form NDMR for each PPI.
If no activities occurred during the monitoring month, the Permittee shall still submit monitoring reports
documenting the absence of the activity. The Permittee shall submit the reports via the Non -Discharge
monitoring report portal_ [15A NCAC 02T .0105(1), 02U .0105]
7. The Permittee shall maintain records of all residuals removed from this facility. The Permittee shall
maintain these records for eight years and shall make them available to the Division upon request.
These records shall include:
a. Name of the residuals hauler.
b. Non -Discharge permit number authorizing the residuals disposal, or a letter from a municipality
agreeing to accept the residuals.
c. Residuals hauling date.
d. Volume of residuals removed.
[ 15A NCAC 02U .0802(b)]
WQ0040079 Version 2.0 Shell Version 230811 Page 6 of 9
8. The Permittee shall keep a log of all maintenance done at this facility. The Permittee shall maintain
this log for eight years and shall make it available to the Division upon request. This log shall include:
a. Date of flow measurement device calibration.
b. Date of turbidimeter calibration.
c. Visual observations of the plant and plant site.
d. Record of preventative maintenance (e.g., changing of equipment, adjustments, testing,
inspections, cleanings, etc.).
e. Date and results of the alternate power supply testing.
f Record of all discharges of reclaimed water to surface waters or the land surface, including the date
of occurrence, estimated volume, and corrective action taken.
[ 15A NCAC 02U .080I (h)]
9. Noncompliance Notification:
The Permittee shall report to the Raleigh Regional Office, telephone number (919) 791-4200, within
24 hours of first knowledge of the following:
a. Treatment of wastes abnormal in quantity or characteristic, including the known passage of a
hazardous substance.
b. Any process unit failure (e.g., mechanical, electrical, structural, etc.) that makes the facility
incapable of adequate reclaimed water generation.
c. Any facility failure resulting in a discharge to surface waters.
d. Any time self -monitoring indicates the facility has gone out of compliance with its permit
limitations.
e. Any failure resulting in a discharge of reclaimed water directly to surface waters or any release of
reclaimed water to land surface greater than or equal to 5,000 gallons. The Permittee shall
document releases less than 5,000 gallons to land surface pursuant to Condition IV.8.f but does not
require Regional Office notification.
Emergencies requiring reporting outside normal business hours shall call the Division's Emergency
Response personnel at the telephone number (800) 858-0368. All noncompliance notifications shall
file a written report to the Raleigh Regional Office within five days of first knowledge of the
occurrence, and this report shall outline the actions proposed or taken to ensure the problem does not
recur. [15A NCAC 02T .0108(b)(1)(A), 02U .0108]
V. INSPECTIONS
1. The Permittee shall perform inspections and maintenance to ensure proper operation of the reclaimed
water generation and conjunctive utilization facilities. [15A NCAC 02U .0801(i)1
2. The Permittee shall inspect the reclaimed water generation and conjunctive utilization facilities to
prevent malfunctions, facility deterioration, and operator errors that may result in discharges of wastes
to the environment, threats to human health, or public nuisances. The Permittee shall maintain an
inspection log that includes the date and time of inspection, observations made, and maintenance,
repairs, or corrective actions taken. The Permittee shall maintain this inspection log for eight years
from the date of the inspection and shall make this log available to the Division upon request. [15A
NCAC 02U .0801(h), 02U .0801(i)]
Division -authorized representatives may, upon presentation of credentials, enter and inspect any
property, premises, or place related to the permitted reclaimed water generation and conjunctive
utilization facilities at any reasonable time for determining compliance with this permit. Division -
authorized representatives may inspect or copy records maintained under the terms and conditions of
this permit and may collect influent, treatment process water, generated reclaimed water, residual, soil,
plant tissue, groundwater, or surface water samples. [G.S. 143-215.3(a)(2)]
WQ0040079 Version 2.0 Shell Version 230811 Page 7 of 9
Vl. GENERAL
1. The Permittee's failure to comply with this permit's conditions and limitations may subject the
Permittee to a Division enforcement action. [G.S. 143-215.6A, 143-215.6B, 143-215.6C]
2. This permit is effective only for the nature and volume of wastes described in the permit application
and Division -approved plans and specifications. [G.S. 143-215.1(d)1
3. There are no variances to administrative codes or general statutes governing the construction or
operation of the permitted facilities unless the Permittee specifically requested a variance in the
application and the Division approved the variance as noted in this permit's facility description. [15A
NCAC 02T .0105(b), 02U .0105]
4. This permit does not exempt the Permittee from complying with all statutes, rules, regulations, or
ordinances that other jurisdictional government agencies (e.g., local, state, and federal) may require.
[15A NCAC 02T .0108(b)(1)(A), 02U .01081
5. The Permittee shall retain this permit and the Division -approved plans and specifications for the life of
the permitted facilities. [15A NCAC 02T .0105(o), 02T .0116(d), 02U .0105, 02U .0116]
6. The Permittee shall comply with all permit conditions and requirements until the proper closure of the
permitted facilities, or until another appropriate authority permits the facilities. [15A NCAC 02T
.0105 , 02U .0105]
7. This permit is subject to revocation or modification upon 60-day notice from the Division Director in
whole or part for:
a. Violation of any terms or conditions of this permit or 15A NCAC 02U.
b. Obtaining a permit by misrepresentation or failure to disclose all relevant facts.
c. The Permittee's refusal to allow authorized Department employees upon presentation of
credentials:
I. To enter the Permittee's premises where a system is located or where the Permittee keeps any
Division -required records under the terms and conditions of this permit.
ii. To have access to any permit -required documents and records.
iii. To inspect any monitoring equipment or method as required in this permit.
iv. To sample any pollutants.
d. The Permittee's failure to pay the annual fee for administering and compliance monitoring.
e. A Division determination that the conditions of this permit conflict with the North Carolina
Administrative Code or General Statutes.
[ 15A NCAC 02T .0110, 02U .0110]
WQ0040079 Version 2.0 Shell Version 230811 Page 8 of 9
8. Unless the Division determines that the Permittee needs a permit modification for the construction of
facilities to resolve non-compliance with any environmental statute or rule, or the Division Director
grants a variance, expansion of the permitted facilities shall not occur if any of the following apply:
a. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has been convicted of
environmental crimes under G.S. 143-215.6B or under Federal law that would otherwise be
prosecuted under G.S. 143-215.6B, and the Permittee or any parent, subsidiary, or other affiliate of
the Permittee has abandoned or exhausted all appeals of this conviction.
b. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has previously abandoned
a wastewater treatment facility without properly closing the facility in accordance with its permit
or 15A NCAC 02U.
c. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has not paid a civil
penalty, and the Permittee or any parent, subsidiary, or other affiliate of the Permittee has
abandoned or exhausted all appeals of this penalty.
d. The Permittee or any parent, subsidiary, or other affiliate of the Permittee is currently not compliant
with any compliance schedule in a permit, settlement agreement, or order.
e. The Permittee or any parent, subsidiary, or other affiliate of the Permittee has not paid an annual
fee pursuant to 15A NCAC 02T .0105(e)(2) via 15A NCAC 02U .0105.
[ 15A NCAC 02T .0120(b), 02T .0120(d), 02U .0120]
9. Unless the Division Director grants a variance, the Division shall not renew this permit if the Permittee
or any affiliation has not paid an annual fee pursuant to 15A NCAC 02T .0I05(e)(2). [15A NCAC 02T
.0120 c , 02T .0120(d), 02U .0105, 02U .0120]
10. The Permittee shall pay an annual fee for each year of the term of this permit pursuant to the schedule
in G.S. 143-215.31)(a). The Permittee shall continue to pay annual fees for any facility operating on
an expired permit that the Division has not rescinded or revoked. [15A NCAC 02T .0105(e)(2), 02U
.0105]
Permit issued this the 17t1i day of January 2024
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
DocuSigned
by-3...
Richard E. Rogers, Jr., Director
Division of Water Resources
By Authority of the Environmental Management Commission
Permit Number WQ0040079
WQ0040079 Version 2.0 Shell Version 230811 Page 9 of 9
THIS PAGE BLANK
ATTACHMENT A — LIMITATIONS AND MONITORING REQUIREMENTS
Consolidated Diesel Company
PPI 001— Reclaimed Water Generation System Effluent
Certification Date: January 17, 2024
Permit Number: WQ0040079 Version: 2.0
EFFLUENT CHARACTERISTICS
EFFLUENT LIMITS
MONITORING REQUIREMENTS
PCS
Code
Parameter Description
Units of
Measure
Monthly
Average
Monthly
Geometric Mean
Daily Minimum
Daily Maximum
Measurement
Frequency
Sample
Type
00310
BOD, 5-Day (20 °C)
mg/L
10
15
Monthly
Composite
50060
Chlorine, Total Residual
mg/L
5 x Week
Grab
31616
Coliform, Fecal ME, M-FC Broth, 44.5 °C
#/100 mL
14
25
Monthly
Grab
50050
Flow, in Conduit or thru Treatment Plant
GPD
75,000
Continuous
Recorder
00610
Nitrogen, Ammonia Total (as N)
mg/L
4
6
Monthly
Composite
00530
Solids, Total Suspended
mg/L
5lir
10
Monthly
Composite
00076
Turbidity, HCH Turbidimeter
NTU
10
Continuous
Recorder
1. The Permittee shall only sample reclaimed water utilized in the cooling tower. The Permittee does not need to sample effluent discharged to the Tar River Regional W WTP (Permit No. NCO030317
— IUP #1900). If the Permittee does not utilize reclaimed water during an entire calendar month, the Permittee shall mark "No Flow" on Form NDMR.
PPI 002 — Distributed Reclaimed Water for Conjunctive Utilization
EFFLUENT CHARACTERISTICS
EFFLUENT LIMITS
MONITORING REQUIREMENTS
PCs
Parameter Description
Units of
Monthly Total
Monthly
Daily Minimum
Daily Maximum
Measurement
Sample
Code
Measure
Geometric Mean
Frequency
Type
WQ01
Flow, Reclaimed Water Distributed
gallons
Monthly
Estimate
WQ0040079 Version 2.0 Attachment A Page 1 of 1
THIS PAGE BLANK
ATTACHMENT B — APPROVED LAND APPLICATION SITES AND LIMITATIONS
Consolidated Diesel Company
Certification Date: January 17, 2024
Permit Number: WQ0040079 Version: 2.0
UTILIZATION AREA INFORMATION
APPLICATION LIMITATIONS
Site
Owner
Parcel No.
County
Latitude
Longitude
Net
Acreage
Dominant
Soil Series
Approved Use
Parameter
Hourly
Rate
Units
1
Consolidated Diesel Company
020807
Nash
36.092851'
-77.724558'
Cooling Tower
Total:
WQ0040079 Version 2.0 Attachment B Page 1 of 1
L
A AF
CUMMINS RMEP SITEIPROPERTY
+
9377 US-301,
WHITAKERS, NC
PIN 3879WIS 1410
q
k 7V-
OHNSTO� ROAD
41�
;0011
cId
-UPNSOLIDATED Dll� EL
lo* OMPANYWATEHUB FA91LITY4
IL
v
�,u 4e7 A IL
No— P55
L
CUMMINS RMU MAIN
PRODUCTION FAdLI
40r
.481
?1 7
401 OA IF
A
ri
i Ft
IF
Ac 0
4', 0
*o 0
. . . .
V
SEAL
4 ,A
*0 047235
co
opv **.4G IN c-, Soo 0 250 500 1000 i,
. 'z
3/0°on0000pn `r iinch 500 ft.
411WI
4
I's
WA I""' AS NO-ED NO Withers Rave nel
I Drawn By m IDate 212VD22 CDC WATERHUB M B R REPLACEMENT SITE LOCATION MAP 1110 Engineers. PlarinerS I Surveyor'
y lJou No. 115 M-kmn Drir I Cary. NC 2 7SI I
IWR 02211s31.00 WHITAKERS NASH COUNTY k 919_4691340 I lice- #: F- 1471) 1
!i
I
^ '\ 0.00,
Nv
*I
jo
ooa¢u¢¢¢a¢noaQ
ODO ��SYI-� �O9�OpO
Q
o
v
028FOC3 ` o�
Q SEAL r
p o 047235 o g
a°o [I oO000 G i
31� MPS 06
j
3� RECLAIM 1VA17E STDRriCE TANK ;
� J—
..r
r�
r� g APPFQXIMP.ZE PROPERTYISITE BOUNDARY
�VIOL
V ,i
COVER€"EMBRANE BIOREACTOR TANKS f
(LOCATION OF ALL PROJECT WORK)
A - 1 tiL J \ 1 . ' r4 J 3 % •f �,
INFLUENT PUMP STATION \• `
t rV.
5 —E BOUNDARY FENCE
CONS04ATED DIESEL w
COMPANAVATER HUB FACILITY
l d�`
t �;-v •- `
No
—'ti'.
Aw
_
- GRAPHIC SCALE
t0� 0 so 100 200
' r
��• ��`'° ^0\ l 1 inch = 100 Ft.
7
::> J!
AOO
Revirion fl�.1" 4 pesigner 5[aiIII e �� WithersRavenel
sir �2 CDC WATERHUB MBR REPLACEMENT WATERHUB FACILITY ON51TE LOCATION MAP �� Z
Q+awn By Gate Engineers. Planners Surveyors
Checked By 135 MacKenan Drive I Lary, NC 27511
WR 02211s31.00 WHITAKERS EDGECDMBE NC �: 91P-469.33d011icense N: F•1474 1 www.withersrauenel-mm