HomeMy WebLinkAboutWQ0035784_NOD-2022-PC-0204_20230706ROY COOPER Governor ELIZABETH S. BISER Secretary RICHARD E. ROGERS, JR. Director NORTH CAROLINA Environmental Quality July 6, 2023 Delivered electronically via email to: Christopher.garnic _mapletree.com.sg Christopher Garnic Wallace Loft LLC 5 Bryant Park 28th Floor New York, NY 10018 SUBJECT: Continued Notice of Deficiency (NOD-2022-PC-0204) Follow Up Inspection The Cottages of Boone WWTP Permit No. WQ0035784 Watauga County Dear Mr. Garnic: On June 29, 2023, Division of Water Resources staff Caitlin Caudle and Kristen Potwora completed a follow up inspection. Todd Robinson, ORC, Christy Hodgen, Complex Manager, and David Smith, Maintenance Director, were present during the entire inspection. A review was completed of all Deficiency items noted in NOD-2022-PC-0204 dated January 9, 2023. This letter will address each item as listed in the NOD, and the permit schedule conditions in the most recently issued permit. Permit Condition 1.1: Within 30 days of permit issuance, the Permittee shall designate and employ one or more certified operators as back-up operators in responsible charge (BUORCs). On May 24, 2023, a BUORC was designated for the WW-2 classification of the system. The designation of ORCs and BUORCs was discussed during the inspection. Mr. Robinson stated that another EnviroLink employee is currently working towards a SI certification to serve as the BUORC for the facility. An employee in the complex is also assisting with the operation of the system and working under Mr. Robinson's license. As a reminder, a BUORC must be designated for the SI classification as well. Item A: The knife valve was reportedly replaced. No leaks were noted. North Carolina Department of Environmental Quality I Division of Water Resources Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 I Winston-Salem, North Carolina 27105 NoanicaaouNn oep.m.m or em�nmen� Qualm 336.776.9800 Item B: Pump P-8001 B was repaired by replacing the seal. The seal in pump P-8001A was replaced at the same time and is now leaking in the same manner as pump P-8001 B. Mr. Robinson has installed measures to direct all leaking wastewater to the floor drains, which drain to the sump tank. Mr. Robinson stated that the floors are washed down daily before staff leave for the day. Make the necessary repairs to the pump motor. Item C: The level transducers in the equalization basin were reportedly repaired. Mr. Robinson stated that the level transducers have been working correctly since he began operating the system. Item D: The dissolved oxygen meter was reportedly repaired. Mr. Robinson stated that it has been operating correctly since he began operating the system. Item E: The UV bank has not been repaired or replaced. Mr. Robinson stated that the UV bank will likely have to be replaced. Ms. Caudle reminded Mr. Robinson that if the UV bank is replaced, it must be replaced with a comparable model. Continue to make efforts to repair or replace the UV bank. As a reminder, the unit as described in the permit description is a 130 gpm Severn Trent UV disinfection system. Item F: The forcemain to Zones 1-4 was reportedly repaired and in operation when Mr. Robinson began operating the system. Ms. Caudle reviewed the PercRite system control panel and Z4 and Z6 had high flow failure messages, and Z1, 2, and 5 had high flow warning messages. The total flows showed that Z4 and 6 were not being irrigated. Zones 4 and 6 must be inspected and repaired as there is likely a break in the drip lines causing high flows. Zones 1, 2, and 5 must also be inspected and repaired as needed. Item G: The embankment above the storage tanks was not repaired at the time of inspection, but Ms. Hodgens provided an invoice for a landscaper that will be completing the work. Item of Concern: The storage tanks appeared to be in good condition with no visible leaks. Item of Concern: The brush screen room was cleaned, and efforts have been made to remove screenings on a more regular basis. The following items were noted during this follow up inspection: • A three sided, open atmosphere box was present over one access port of the sump tank. A screen was present at the bottom of the box. There was not a cover over the box, or a cap for the access point. Ms. Caudle recommended getting a cover for the box to prevent rainwater and stormwater from entering the treatment system. NORTH CARCLINAD ��R o.o+ro..m m EnNmnmenfnl n..i� North Carolina Department of Environmental Quality 1 Division of Water Resources Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 1 Raleigh, North Carolina 27105 336.776.9800 • At the time of inspection, irrigation Pump-B was not operational. Mr. Robinson stated that a work order has been submitted for the pump. Please repair the pump as soon as possible. • At the time of inspection, the cable for the freeboard marker was broken and the visible marker was on the ground. Mr. Smith stated that staff visually observe the freeboard in the tanks at least once a week by climbing the tanks. Please repair the cable as soon as possible to make freeboard readings readily visible for all staff. Please refer to the enclosed inspection report for additional comments and observations. If you have any questions, please contact me or Caitlin Caudle at the letterhead address and phone number, or by email at jenny.graznak6c�deg.nc.gov or Caitlin.caudle(a_deg.nc.gov. Sincerely, Docu Signed by: OD2D3CE3F1 B7456_. Jennifer F. Graznak, Assistant Regional Supervisor Water Quality Regional Operations Section Division of Water Resources, NCDEQ — WSRO Enc: Inspection Report Cc: Todd Robinson, ORC (electronic copy) Madelyn Mills, Envirol-ink (electronic copy) Christy Hodgen, Complex Manager (electronic copy) Watauga County Environmental Health (electronic copy) NORTH CAROLINAD � �� oeo+ro�.m m F,mro���w n�si� North Carolina Department of Environmental Quality I Division of Water Resources Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 1 Raleigh, North Carolina 27105 336.776.9800 Compliance Inspection Report Permit: WQ0035784 Effective: 06/05/23 Expiration: 04/30/30 Owner: Wallace Loft LLC SOC: Effective: Expiration: Facility: The Cottages of Boone WWTP County: Watauga 1002 Fallview Ln Region: Winston-Salem Boone NC 28607 Contact Person: Ashley Vargo Title: Phone: Directions to Facility: Take 140 BUS W/US-158 W/US-421 N from N Lierty Street. Follow 421 N to E King Street in Boone. Take US 221 S and NC 105 S to Boone Circle System Classifications: SI, WW2, Primary ORC: Todd Franklin Robinson Certification: 1006252 Phone: 704-881-4598 Secondary ORC(s): On -Site Representative(s): Related Permits: WQCSD0738 Wallace Loft LLC - Cottages of Boone WWCS Inspection Date: 06/29/2023 Entry Time 10:19AM Exit Time: 11:45AM Primary Inspector: Caitlin C udfle� °�llll°S 9°ed b". Phone: 336-776-9699 Secondary Inspector(s): uwuv, l,MD& 8B834968199D49D_ Reason for Inspection: Follow-up Inspection Type: Compliance Evaluation Permit Inspection Type: Wastewater Irrigation Facility Status: ❑ Compliant Not Compliant Question Areas: Miscellaneous Questions Treatment Treatment Barscreen End Use -Irrigation Treatment Disinfection Storage (See attachment summary) Page 1 of 6 Permit: WQ0035784 Owner - Facility: Wallace Loft LLC Inspection Date: 06/29/2023 Inspection Type: Compliance Evaluation Reason for Visit: Follow-up Inspection Summary: On June 29, 2023, Division of Water Resources staff Caitlin Caudle and Kristen Potwora completed a follow up inspection. Todd Robinson, ORC, Christy Hodgen, Complex Manager, and David Smith, Maintenance Director, were present during the entire inspection. A review of all Deficiency items noted in NOD-2022-PC-0204 dated January 9, 2023. This report will address each item as listed in the NOD, and the permit schedule conditions in the most recently issued permit. Permit Condition 1.1: Within 30 days of permit issuance, the Permittee shall designate and employ one or more certified operators as back-up operators in responsible charge (BUORCs). On May 24, 2023, a BUORC was designated for the WW-2 classification of the system. The designation of ORCs and BUORCs was discussed during the inspection. Mr. Robinson stated that another Envirol-ink employee is currently working towards a SI certification to serve as the BUORC for the facility. An employee in the complex is also assisting with the operation of the system and working under Mr. Robinson's license. As a reminder, a BUORC must be designated for the SI classification as well. Item A: The knife valve was reportedly replaced. No leaks were noted. Item B: Pump P-8001 B was repaired by replacing the seal. The seal in pump P-8001A was replaced at the same time and is now leaking in the same manner as pump P-8001 B. Mr. Robinson has installed measures to direct all leaking wastewater to the floor drains, which drain to the sump tank. Mr. Robinson stated that the floors are washed down daily before staff leave for the day. Make the necessary repairs to the pump motor. Item C: The level transducers in the equalization basin were reportedly repaired. Mr. Robinson stated that the level transducers have been working correctly since he began operating the system. Item D: The dissolved oxygen meter was reportedly repaired. Mr. Robinson stated that it has been operating correctly since he began operating the system. Item E: The UV bank has not been repaired or replaced. Mr. Robinson stated that the UV bank will likely have to be replaced. Ms. Caudle reminded Mr. Robinson that if the UV bank is replaced, it must be replaced with a comparable model. Continue to make efforts to repair or replace the UV bank. As a reminder, the unit as described in the permit description is a 130 gpm Severn Trent UV disinfection system. Item F: The forcemain to Zones 1-4 was reportedly repaired and in operation when Mr. Robinson began operating the system. Ms. Caudle reviewed the PercRite system control panel and Z4 and Z6 had high flow failure messages, and Z1, 2, and 5 had high flow warning messages. The total flows showed that Z4 and 6 were not being irrigated. Zones 4 and 6 must be inspected and repaired as there is likely a break in the drip lines causing high flows. Zones 1, 2, and 5 must also be inspected and repaired as needed. Item G: The embankment above the storage tanks was not repaired at the time of inspection, but Ms. Hodgens provided an invoice for a landscaper that will be completing the work. Item of Concern: The storage tanks appeared to be in good condition with no visible leaks. Item of Concern: The brush screen room was cleaned, and efforts have been made to remove screenings on a more regular basis. The following items were noted during this follow up inspection: • A three sided, open atmosphere box was present over one access port of the sump tank. A screen was present at the bottom of the box. There was not a cover over the box, or a cap for the access point. Ms. Caudle recommended getting a cover for the box to prevent rainwater and stormwater from entering the treatment system. • At the time of inspection, irrigation Pump-B was not operational. Mr. Robinson stated that a work order has been submitted for the pump. Please repair the pump as soon as possible. • At the time of inspection, the cable for the freeboard marker was broken and the visible marker was on the ground. Mr. Smith stated that staff visually observe the freeboard in the tanks at least once a week by climbing the tanks. Please repair the cable as soon as possible to make freeboard readings readily visible for all staff. Other observations: • Operator changes have caused some information to be lost. Mr. Robinson was able to speak to the state of the system since he was designated ORC and started operating the system. • Mr. Robinson stated that additional membrane bioreactors have been ordered. Page 2 of 6 Permit: WQ0035784 Owner - Facility: Wallace Loft LLC Inspection Date: 06/29/2023 Inspection Type: Compliance Evaluation Reason for Visit: Follow-up Type Yes No NA NE Infiltration System ❑ Reuse (Quality) ❑ Lagoon Spray, LR ❑ Single Family Spray, LR ❑ Activated Sludge Spray, HR ❑ Activated Sludge Drip, LR ❑ Recycle/Reuse ❑ Single Family Drip ❑ Activated Sludge Spray, LR Treatment Yes No NA NE Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑ Do all treatment units appear to be operational? (if no, note below.) ❑ 0 ❑ ❑ Comment: See summary. Treatment Barscreen Yes No NA NE Is it free of excessive debris? 0 ❑ ❑ ❑ Is disposal of screenings in compliance? ❑ ❑ ❑ Are the bars spaced properly? ❑ ❑ ❑ Is the unit in good condition? ❑ ❑ ❑ Comment: Treatment Disinfection Yes No NA NE Is the system working? 0 ❑ ❑ ❑ Do the fecal coliform results indicate proper disinfection? ❑ ❑ ❑ Is there adequate detention time (>=30 minutes)? ❑ ❑ ❑ Is the system properly maintained? ❑ ❑ ❑ If gas, does the cylinder storage appear safe? ❑ ❑ ❑ Is the fan in the chlorine feed room and storage area operable? ❑ ❑ ❑ Is the chlorinator accessible? ❑ ❑ ❑ If tablets, are tablets present? ❑ ❑ ❑ Are the tablets the proper size and type? ❑ ❑ ❑ Is contact chamber free of sludge, solids, and growth? ❑ ❑ ❑ If UV, are extra UV bulbs available? ❑ ❑ ❑ If UV, is the UV intensity adequate? ❑ ❑ ❑ # Is it a dual feed system? ❑ ❑ ❑ Page 3 of 6 Permit: WQ0035784 Owner - Facility: Wallace Loft LLC Inspection Date: 06/29/2023 Inspection Type: Compliance Evaluation Reason for Visit: Follow-up Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)? ❑ ❑ 0 ❑ If yes, then is there a Risk Management Plan on site? ❑ ❑ ❑ If yes, then what is the EPA twelve digit ID Number? (1 000-- ) If yes, then when was the RMP last updated? Comment: See summary. End Use -Irrigation Yes No NA NE Are buffers adequate? 0 ❑ ❑ ❑ Is the cover crop type specified in permit? ❑ ❑ ❑ Is the crop cover acceptable? ❑ ❑ ❑ Is the site condition adequate? ❑ ❑ ❑ Is the site free of runoff / ponding? ❑ ❑ ❑ Is the acreage specified in the permit being utilized? ❑ ❑ ❑ Is the application equipment present? ❑ ❑ ❑ Is the application equipment operational? ❑ ❑ ❑ Is the disposal field free of limiting slopes? ❑ ❑ ❑ Is access restricted and/or signs posted during active site use? ❑ ❑ ❑ Are any supply wells within the CB? ❑ ❑ ❑ Are any supply wells within 250' of the CB? ❑ ❑ ❑ How close is the closest water supply well? ❑ ❑ ❑ Is municipal water available in the area? ❑ ❑ ❑ # Info only: Does the permit call for monitoring wells? ❑ ❑ ❑ Are GW monitoring wells located properly w/ respect to RB and CB? ❑ ❑ ❑ Are GW monitoring wells properly constructed, including screened interval? ❑ ❑ ❑ Are monitoring wells damaged? ❑ ❑ ❑ Comment: See summa 5-DAY UPSET TANK - Storage Yes No NA NE Storage Type? Storage amount? # At what point is side -stream wastewater returned to treatment? Is there a Spill Control Plan? ❑ ❑ ❑ ❑ Aerated or Mixed? If aeration is present, is it adequate? ❑ ❑ ❑ ❑ If present, are diffusers cleaned regularly? ❑ ❑ ❑ ❑ Is influent structure acceptable? ❑ ❑ ❑ ❑ Are banks/berms free of seepage and erosion? ❑ ❑ ❑ ❑ Page 4 of 6 Permit: WQ0035784 Owner - Facility: Wallace Loft LLC Inspection Date: 06/29/2023 Inspection Type: Compliance Evaluation Reason for Visit: Follow-up Are banks/berms free of excessive vegetation? ❑ ❑ ❑ ❑ Is pond lined? ❑ ❑ ❑ ❑ Liner Type Is liner acceptable? ❑ ❑ ❑ ❑ Are baffles/curtains acceptable? ❑ ❑ ❑ ❑ Does the pond have a freeboard marker? ❑ ❑ ❑ ❑ Required freeboard? Actual freeboard? Is there suitable grassed vegetation? ❑ ❑ ❑ ❑ Is the vegetation maintained? ❑ ❑ ❑ ❑ Is the area free of excessive weeds and/or woody species? ❑ ❑ ❑ ❑ Is the area free from signs of overflow? ❑ ❑ ❑ ❑ Is color acceptable? ❑ ❑ ❑ ❑ Are floating mats acceptable? ❑ ❑ ❑ ❑ No excessive buildup of solids? ❑ ❑ ❑ ❑ Are aerators/mixers acceptable? ❑ ❑ ❑ ❑ Is effluent structure acceptable? ❑ ❑ ❑ ❑ If present, is pond cover acceptable? ❑ ❑ ❑ ❑ Comment: WET WEATHER STORAC Storage Yes No NA NE Storage Type? Storage amount? # At what point is side -stream wastewater returned to treatment? Is there a Spill Control Plan? ❑ ❑ ❑ ❑ Aerated or Mixed? If aeration is present, is it adequate? ❑ ❑ ❑ ❑ If present, are diffusers cleaned regularly? ❑ ❑ ❑ ❑ Is influent structure acceptable? ❑ ❑ ❑ ❑ Are banks/berms free of seepage and erosion? ❑ ❑ ❑ ❑ Are banks/berms free of excessive vegetation? ❑ ❑ ❑ ❑ Is pond lined? ❑ ❑ ❑ ❑ Liner Type Is liner acceptable? ❑ ❑ ❑ ❑ Are baffles/curtains acceptable? ❑ ❑ ❑ ❑ Page 5 of 6 Permit: WQ0035784 Owner - Facility: Wallace Loft LLC Inspection Date: 06/29/2023 Inspection Type: Compliance Evaluation Reason for Visit: Follow-up Does the pond have a freeboard marker? Required freeboard? Actual freeboard? Is there suitable grassed vegetation? Is the vegetation maintained? Is the area free of excessive weeds and/or woody species? Is the area free from signs of overflow? Is color acceptable? Are floating mats acceptable? No excessive buildup of solids? Are aerators/mixers acceptable? Is effluent structure acceptable? If present, is pond cover acceptable? Comment: ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ Page 6 of 6