HomeMy WebLinkAboutWQ0010528_Notice of Deficiency_20230706ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
IITa7 • Mom, 7IMV1R: eweI[_
Town of Ramseur
P.O. Box 545
Ramseur, NC 27316
NORTH CAROLINA
Environmental Quality
July 6, 2023
SUBJECT: Notice of Deficiency (NOD-2023-PC-0196)
2022 Annual Report Review
Town of Ramseur SDU
Permit No. WQ0010528
Randolph County
Dear Mayor Caudle:
On June 13, 2023, Division of Water Resources staff Caitlin Caudle completed a review
of the 2022 Annual Report. This review reflected non-compliance with the subject permit.
The following deficiency was noted:
A. Per Permit Condition IV.2 the residuals from each source generating facility shall
be analyzed to demonstrate they are non -hazardous and a table of parameters is
provided. Based on the available information, the residuals from the Ramseur
Water Treatment Plant were not analyzed for herbicides (2,4-D and 2,4,5-TP (or
Silvex)), ignitability, and reactivity. Moving forward, please ensure that the
residuals are analyzed for all parameters included in Permit Condition IV.2.
Please refer to the enclosed inspection report for additional comments and observations.
If you have any questions, please contact me or Caitlin Caudle at the letterhead address
and phone number, or by email at or
Caitlin.caudle(a�deg.nc.gov.
Sincerely,
Docu Signed by,
OD2D3CE3F1 B1456_.
Jennifer F. Graznak, Assistant Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ — WSRO
Enc: Inspection Report
Cc: Terry Lewallen, ORC (electronic copy)
Randolph County Environmental health (electronic copy)
DffNorth Carolina Department of Environmental Quality I Division of Water Resources
oan caaouNn
Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 1 Winston-Salem, North Carolina 27105
M336.776.9800
oep.m.m or em�nmen� Qualm
Compliance Inspection Report
Permit: WQ0010528 Effective: 07/31/20 Expiration: 08/31/26 Owner: Town of Ramseur
SOC: Effective: Expiration: Facility: Town of Ramseur SDU
County: Randolph 4735 Roundleaf Rd
Region: Winston-Salem
Ramseur NC 27316
Contact Person: Bobbie Hatley Title: Phone: 336-824-8530
Directions to Facility:
System Classifications:
Primary ORC: Certification: Phone:
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
NC0026565 Town of Ramseur - Ramseur WWTP
Inspection Date: 06/13/2023 Entry Time 01:OOPM Exit Time: 02:OOPM
Primary Inspector: Caitli Cr8B834968199D49D_.
r(flb'9"ed by: Phone: 336-776-9699
Secondary Inspector(s):ruv' C&L& &
Reason for Inspection: Routine Inspection Type: Annual Report Review
Permit Inspection Type: Surface Disposal of Residual Solids (503)
Facility Status: ❑ Compliant Not Compliant
Question Areas:
Miscellaneous Questions Record Keeping Treatment
Sampling Pathogen and Vector Attraction
(See attachment summary)
Page 1 of 4
Permit: WQ0010528 Owner - Facility: Town of Ramseur
Inspection Date: 06/13/2023 Inspection Type: Annual Report Review Reason for Visit: Routine
Inspection Summary:
On June 13, 2023, Division of Water Resources staff Caitlin Caudle completed a review of the 2022 Annual Report. This
review reflected non-compliance with the subject permit. The following deficiency was noted:
A. Per Permit Condition IV.2 the residuals from each source generating facility shall be analyzed to demonstrate they are
non -hazardous and a table of parameters is provided. Based on the available information, the residuals from the Ramseur
Water Treatment Plant were not analyzed for herbicides (2,4-D and 2,4,5-TP (or Silvex)), ignitability, and reactivity. Moving
forward, please ensure that the residuals are analyzed for all parameters included in Permit Condition IV.2.
Other observations:
• Lime stabilization logs and TCLP results were provided on 6/14/23 after Ms. Caudle requested them.
• Sampling for the WTP was completed on 9/17/22, and sampling for the WWTP was completed on 12/29/22.
• Residuals from the WTP were applied in September, and residuals from the WWTP were applied in July and October.
Page 2 of 4
Permit: WQ0010528 Owner - Facility: Town of Ramseur
Inspection Date: 06/13/2023 Inspection Type: Annual Report Review
Reason for Visit: Routine
Type
Yes No NA NE
Distribution and Marketing
❑
Land Application
❑
Record Keeping
Yes No NA NE
Is GW monitoring being conducted, if required?
0
❑ ❑ ❑
Are GW samples from all MWs sampled for all required parameters?
0
❑ ❑ ❑
Are there any GW quality violations?
0
❑ ❑ ❑
Is GW-59A certification form completed for facility?
0
❑ ❑ ❑
Is a copy of current permit on -site?
❑
❑ 0 ❑
Are current metals and nutrient analysis available?
0
❑ ❑ ❑
Are nutrient and metal loading calculating most limiting parameters?
0
❑ ❑ ❑
a. TCLP analysis?
0
❑ ❑ ❑
b. SSFA (Standard Soil Fertility Analysis)?
❑
❑ 0 ❑
Are PAN balances being maintained?
❑
❑ 0 ❑
Are PAN balances within permit limits?
❑
❑ 0 ❑
Has land application equipment been calibrated?
❑
❑ 0 ❑
Are there pH records for alkaline stabilization?
0
❑ ❑ ❑
Are there pH records for the land application site?
❑
❑ 0 ❑
Are nutrient/crop removal practices in place?
❑
❑ 0 ❑
Do lab sheets support data reported on Residual Analysis Summary?
0
❑ ❑ ❑
Are hauling records available?
0
❑ ❑ ❑
Are hauling records maintained and up-to-date?
0
❑ ❑ ❑
# Has permittee been free of public complaints in last 12 months?
0
❑ ❑ ❑
Has application occurred during Seasonal Restriction window?
❑
❑ 0 ❑
Comment: Occasional TDS violations.
Pathogen and Vector Attraction
Yes No NA NE
a. Fecal coliform SM 9221 E (Class A or B)
❑
❑ ❑ ❑
Class A, all test must be <1000 MPN/dry gram
❑
Geometric mean of 7 samples per monitoring period for class B<2.0*10E6 CFU/dry gram
❑
Fecal coliform SM 9222 D (Class B only)
❑
❑ ❑ ❑
Geometric mean of 7 samples per monitoring period for class B<2.0*10E6 CFU/dry gram
❑
b. pH records for alkaline stabilization (Class A)
❑
❑ ❑ ❑
c. pH records for alkaline stabilization (Class B)
❑ ❑ ❑
Temperature corrected
d. Salmonella (Class A, all test must be < 3MPN/4 gram day)
❑
❑ ❑ ❑
Page 3 of 4
Permit: WQ0010528 Owner - Facility: Town of Ramseur
Inspection Date: 06/13/2023 Inspection Type: Annual Report Review Reason for Visit: Routine
e. Time/Temp on: ❑ ❑ ❑ ❑
Digester (MCRT) ❑
Compost ❑
Class A lime stabilization ❑
f. Volatile Solids Calculations ❑ ❑ ❑ ❑
g. Bench -top Aerobic/Anaerobic digestion results ❑ ❑ ❑ ❑
Comment:
Treatment
Yes No NA NE
Check all that apply
Aerobic Digestion
❑
Anaerobic Digestion
❑
Alkaline Pasteurization (Class A)
❑
Alkaline Stabilization (Class B)
Compost
❑
Drying Beds
❑
Other
❑
Comment:
Sampling Yes No NA NE
Describe sampling:
Is sampling adequate? 0 ❑ ❑ ❑
Is sampling representative? 0 ❑ ❑ ❑
Comment:
Page 4 of 4