SENT VIA ELECTRONIC MAIL ONLY: NO HARD COPY WILL BE MAILED.
April 5, 2023
Lynn Olson
Laurel Hills Homeowners Association
Email: lodj220@gmail.com
SUBJECT: Compliance Inspection Report
Laurel Hills WWTP
NPDES WW Permit No. NC0060844
Macon County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Laurel Hills WWTP on
3/23/2023. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0060844. The findings and comments
noted during this inspection are provided in the enclosed copy of the inspection report entitled
"Compliance Inspection Report".
The following compliance issues were noted during the inspection:
1. Bar Screen: The bar screen is not adequately screening debris. This is resulting in an excess of
floating solids throughout the plant. It is recommended to install a bar screen with grates that are
closer together.
2. Secondary Clarifier: At the time of inspection, one of the two skimmers was operating poorly. This is
contributing to the excess floating solids throughout the plant. It is recommended that the skimmer be
repaired or replaced. Additionally, because there is some excess grease throughout the plant it is
recommended to distribute FOG brochures and rag information to residents.
If you should have any questions, please do not hesitate to contact Lauren Armeni with the Water
Quality Regional Operations Section in the Asheville Regional Office at 828-296-4667 or via email at
lauren.armeni@ncdenr.gov.
DocuSign Envelope ID: D09C4D8A-D9E7-46A7-BBB9-4C89DC3BD6E3
Sincerely,
Daniel Boss, Assistant Regional Supervisor
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
Ec: Laserfiche
Mark Teague (ORC, Environmental Inc.)
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NC0060844 23/03/23 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Laurel Hills WWTP
Pete McCoy Rd
Franklin NC 28744
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
10:00AM 23/03/23 18/07/01
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Mark Fredrick Teague/ORC/828-586-5588/
Other Facility Data
11:15AM 23/03/23 22/11/30
Name, Address of Responsible Official/Title/Phone and Fax Number
Margaret Crownover,PO Box 1537 Franklin NC 28734//828-369-9162/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self-Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Melanie Kemp DWR/ARO WQ/ - - /
Lauren E Armeni DWR/ARO WQ/828-296-4500/
Mara G Chamlee DWR/ARO WQ/828-296-4500/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: D09C4D8A-D9E7-46A7-BBB9-4C89DC3BD6E3
4/6/2023
4/6/2023
4/6/2023
NPDES yr/mo/day
23/03/23
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Lauren Armeni, Mara Chamlee, and Melanie Kemp, with the Asheville Regional Office, conducted a
Compliance Evaluation Inspection of the Laurel Hills Homeowners Association WWTP on March 23,
2023. This inspection was conducted to determine whether the facility is being operated and
maintained in compliance with NPDES Permit No. NC0060844. Mr. Mark Teague (ORC -
Environmental Inc.) and Mr. Zach Story (Backup ORC in-training - Environmental Inc.) were present
and assisted in the inspection.
The following items were noted during the inspection:
Permit: The permit is missing several of the facility components including the aeration basin and
secondary clarifier. Ms. Armeni has contacted Mr. Charles Weaver (NCDEQ Permitting) regarding this
issue and he will be adding these components to the final permit once it's issued. The permit is
currently under renewal and the renewal application has been submitted.
Disinfection - UV: The contact chamber cover is very difficult to lift by one individual, which can inhibit
the ability to properly maintain the UV system. It is recommended to replace the lid with one that is
lighter and more water-tight.
The following compliance issues were noted during the inspection:
Bar Screen: The bar screen is not adequately screening debris. This is resulting in an excess of
floating solids throughout the plant. It is recommended to install a bar screen with grates that are
closer together.
Secondary Clarifier: At the time of inspection, one of the two skimmers was operating poorly. This is
contributing to the excess floating solids throughout the plant. It is recommended that the skimmer be
repaired or replaced. Additionally, because there is some excess grease througout the plant it is
recommended to distribute FOG brochures and rag information to residents.
NC0060844 17 (Cont.)
Page#2
DocuSign Envelope ID: D09C4D8A-D9E7-46A7-BBB9-4C89DC3BD6E3
Permit:NC0060844
Inspection Date:03/23/2023
Owner - Facility:
Inspection Type:
Laurel Hills WWTP
Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Since the 2018 inspection, a fence has been installed to secure the perimeter of the
facility and restrict access to the general public. The permit is missing several of the
facility components including the aeration basin and secondary clarifier. The permit is
currently under renewal and the renewal application has been submitted. See summary
for details.
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Process control parameters include pH, temperature, dissolved oxygen, and MLSS.Comment:
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain-of-custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Page#3
DocuSign Envelope ID: D09C4D8A-D9E7-46A7-BBB9-4C89DC3BD6E3
Permit:NC0060844
Inspection Date:03/23/2023
Owner - Facility:
Inspection Type:
Laurel Hills WWTP
Compliance Evaluation
Record Keeping Yes No NA NE
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Comment:
Flow Measurement - Influent Yes No NA NE
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Mr. Teague indicated that they use the well meter as the influent flow measurement.Comment:
Bar Screens Yes No NA NE
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
The bar screen is a small manual screen that is maintained by hand. At the time of
inspection, it was not adequately screening debris. See summary for details.
Comment:
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin’s surface?
Is the DO level acceptable?
Page#4
DocuSign Envelope ID: D09C4D8A-D9E7-46A7-BBB9-4C89DC3BD6E3
Permit:NC0060844
Inspection Date:03/23/2023
Owner - Facility:
Inspection Type:
Laurel Hills WWTP
Compliance Evaluation
Aeration Basins Yes No NA NE
Is the DO level acceptable?(1.0 to 3.0 mg/l)
The DO level at the time of inspection was 3.1. The settleability after 30 minutes was
150 mL. Due to the low level of flow that this plant recieves, the sludge present in the
plant appears to be older.
Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately ¼ of the sidewall depth)
At the time of inspection, one of the skimmers was not operating properly and is in
need of repair. As a result, there are some excess solids, including a few rags and
some grease. However, these solids are caught by the tertiary filter. At the time of
inspection, the sludge blankel level was around 1' in a 9' deep clarifier. See summary
for details.
Comment:
Aerobic Digester Yes No NA NE
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Mr. Teague indicated that the digester is pumped out twice a year and hauled to the
Franklin WWTP. At the time of inspection, the digester had been pumped out two
weeks prior.
Comment:
Filtration (High Rate Tertiary)Yes No NA NE
Type of operation:Down flow
Is the filter media present?
Is the filter surface free of clogging?
Page#5
DocuSign Envelope ID: D09C4D8A-D9E7-46A7-BBB9-4C89DC3BD6E3
Permit:NC0060844
Inspection Date:03/23/2023
Owner - Facility:
Inspection Type:
Laurel Hills WWTP
Compliance Evaluation
Filtration (High Rate Tertiary)Yes No NA NE
Is the filter free of growth?
Is the air scour operational?
Is the scouring acceptable?
Is the clear well free of excessive solids and filter media?
The filter media consists of anthracite. Mr. Teague indicated that the media was
replaced approximately 5 to 6 years prior to the inspection. Mr. Teague also indicated
that there is no air scour present in the filter but there is one backwash pump. The
tertiary filter has a backwash basin, and the backwash goes to the head of the plant.
Solids within the backwash basin are pumped out when the digester is pumped.
Comment:
Disinfection - UV Yes No NA NE
Are extra UV bulbs available on site?
Are UV bulbs clean?
Is UV intensity adequate?
Is transmittance at or above designed level?
Is there a backup system on site?
Is effluent clear and free of solids?
The UV contact chamber cover has been replaced since the last inspection report
indicated it was failing and in need of repair or replacement; however, Mr. Teague
stated that the current lid is very heavy and difficult to lift. Mr. Teague indicated that the
UV bulbs are cleaned and replaced annually. The backup disinfection system on site is
chlorination and dechlorination tablets. See summary for details.
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
The permit requires grab samples.Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
Page#6
DocuSign Envelope ID: D09C4D8A-D9E7-46A7-BBB9-4C89DC3BD6E3
Permit:NC0060844
Inspection Date:03/23/2023
Owner - Facility:
Inspection Type:
Laurel Hills WWTP
Compliance Evaluation
Effluent Pipe Yes No NA NE
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Standby Power Yes No NA NE
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
There is no permanent generator at the facility. Mr. Teague indicated that if the power
were to go out, the well pump supplying water to the homes would also not work, and
therefore no additional flow would go to the WWTP during this time.
Comment:
Page#7