HomeMy WebLinkAboutNC0076066_Compliance Evaluation Inspection_20151012North Carolina Department of Environmental Quality
Pat McCrory
Governor
October 12, 2015
Mr. Tommy Spicer
Wilkes County Schools
613 Cherry Street
North Wilkesboro, NC 28659
SUBJECT: Compliance Evaluation Inspection
North Wilkes High School WWTP
NPDES Permit # NCO076066
Wilkes County
Dear Mr. Spicer:
Donald R. van der Vaart
Secretary
A Compliance Evaluation Inspection was performed by George Smith on October 7, 2015. Mr. Tommy
Spicer, ORC was present at this inspection. The inspection is comprised of an overall evaluation of the
facilities equipment, and capability to produce an effluent discharge that meets NPDES permit limits.
Permit
Your NPDES permit became effective on October 1, 2013 and expires on September 30, 2018.
The eDMR requirement is included in the permit under Section A.(3). Wilkes County Schools did register
for eDMR, and is working on eDMR submission. Please remember that both paper and eDMR submission
are required at this time.
Records & Reports
Mr. Spicer maintains an operator log, which documents sampling, analysis, Operations & Maintenance, and his
visitations. The records are well organized and maintained in a file cabinet. All are in excellent order.
Facility Site Review
There are six (6) sandfilter beds at this location. All beds are dosed at the same time.
Distribution lines are all intact and properly dosing.
The small leak in the dosing tank was repaired.
Flow Measurement
The flow is measured with an electronic counter, which counts the number of doses the sandfilter receives. Each
dose is 1725 gallons.
450 W Hanes Mill Rd., Suite 300, Winston-Salem, NC 27105
Phone: 336-776-9800 t Internet: www.ncdenr.gov
An Equal opportunity 1 Affirmative Action Employer —Made in part by recycled paper
Laboratory
Wilkes County Schools is an approved field certified lab (# 5406).
The pH calibration is performed with a SensIon 156, using a three-point calibration method (buffers 4, 7,
10), and a midrange check at 7.0. The calibration is recorded.
Temperature is measured with the pH meter and is calibrated, documented, and is traceable to NIST.
The Dissolved Oxygen is measured with an YSI, Model 50B meter, and the air calibration is performed.
The Total Residual Chlorine is measured with a Hach DR2700 spectrophotometer. The 5-point annual
calibration is scheduled to be performed during October 2015.
Effluent/Receiving Waters
The effluent as observed in the effluent well, which is discharged into Wolf Branch, Class B waters was clear at the
effluent station.
Operations & Maintenance
The facility is satisfactorily operated and maintained. Mr. Tommy Spicer, Grade II is the ORC; Mr. Stacy Higgins,
Grade II, Back-up ORC.
The effluent from the sandfilter was discharged to a tablet chlorinator, which used two tubes; followed by tablet de -
chlorination, which used sodium sulfite tablets in two tubes. Both units are in good condition.
The sand beds need some sand added.
Soda ash (sodium carbonate) and Sodium bicarbonate are periodically added to the septic tank.
Self -Monitoring Program
A review of the monthly self -monitoring reports from January 2015 through July 2015 showed no limit violations.
The compliance evaluation inspection is satisfactory. If you have any questions please contact George
Smith or me at (336) 776-9800.
Sincerely,
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
cc: WSRO Files
United Stales Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expiresB-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 E 2 15 1 3 I NCO076066 I11 121 15/10/07 I17 18 I C I 19 Li I 201 I
211111 I I I I I I II I I I 11 III 11 I I I I I I I I I I I I I II I I I I I f6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 CA -------------Reserved ---
671 �I 7071 IitJI 72 L�J 73I 174 75I I —I —L I
80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES oermit Number)
11:44AM 15/10/07
13/12/01
North Wilkes High School WWPP
2986 Traphill Rd
Exit Time/Date
Permit Expiration Dale
Hays NC 28635
11:55AM 15/10/07
18/09/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
///
Thomas J Spicer/ORC/336-651-4010/
Name, Address of Responsible Officialfrille/Phone and Fax Number
Contacted
Ken Barfeld,201 W Main St Wilkesboro NC 28697//336-957-8601/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit E Flow Measurement Operations & Maintenance 0 Records/Reports
Self -Monitoring Program 0 Facility Site Review EffluenUReceiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
G�eo�rgge�S Smith WSRO WQ//336-776-9700/ C- G
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
Permit: NCO076066 Owner -Facility: North Wilkes High School WWiP
Inspection Date: 10/07/2015 Inspection Type: compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ 0 ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: operate visually
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
❑
application?
Is the facility as described in the permit?
M
❑
❑
❑
# Are there any special conditions for the permit?
0
❑
❑
❑
Is access to the plant site restricted to the general public?
M
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: eDMR requirement
Record Keepina
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
M
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
0
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
0
❑
(If the facility is = or> 5 MGD permitted flow) Do they operate 24/7 with a certified operator
- ❑
❑
0
❑
on each shift?
Is the ORC visitation log available and current?
0
❑
❑
❑
Is the ORC certified at grade equal to or higherJhan`the facility classification?,-0
❑.
Ef
El
Is the backup operator certified at one grade less or greater than the facility classification?
0
❑
'❑
❑
Is a copy of the current NPDES permit available on site?
❑
❑
0
❑
Page# 3
Permit: NC0076066 Owner -Facility: North Wilkes High School WVVrP
Inspection Date: 10/07/2015 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Facility has copy of previous year's Annual Report on file for review? 0 ❑ ❑ ❑
Comment: permita are in maintenance office and are available
Septic Tank
Yes No NA NE
(If pumps are used) Is an audible and visual alarm operational?
0
❑
❑
❑
Is septic tank pumped on a schedule?
M
❑
❑
❑
Are pumps or syphons operating properly?
0
❑
❑
❑
Are high and low water alarms operating properly?
0
❑
❑
❑
Comment:
Sand Filters (Low rate)
Yes No NA NE
(If pumps are used) Is an audible and visible alarm Present and operational?
0
❑
❑
❑
Is the distribution box level and watertight?
❑
❑
❑
Is sand filter free of ponding?
❑
❑
❑
Is the sand filter effluent re -circulated at a valid ratio?
❑
❑
0
❑
# Is the sand filter surface free of algae or excessive vegetation?
0
❑..
❑
❑
# Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1)
❑
❑
IN
❑
Comment: some sand is needed in the beds
Disinfection -Tablet
Yes No NA NE
Are tablet chlorinators operational?
0
❑
❑
❑
Are the tablets the proper size and type?
0
❑
❑
❑
Number of tubes in use?
2
Is the level of chlorine residual acceptable?
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
0
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
❑
❑
❑
Comment:
De -chlorination
Yes No NA NE
Type of system ?
Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)?
0 ❑
❑
❑
Is storage appropriate for cylinders?
❑ ❑
M
❑
# Is de -chlorination substance stored away from chlorine containers?
❑ ❑
0
❑
Page# 4
Permit: NCO076066
Inspection Date: 10/07/2015
De -chlorination
Comment:
Are the tablets the proper size and type?
Are tablet de -chlorinators operational?
Number of tubes in use?
Owner -Facility: North Wilkes High School WVVTP
Inspection Type: Compliance Evaluation
Yes No NA NE
E
❑ ❑ ❑
❑ ❑ ❑
Page# 5