Loading...
HomeMy WebLinkAboutNC0075515_Compliance Evaluation Inspection_20151012North Carolina Department of Environmental Quality Pat McCrory Governor October 12, 2015 Mr. Tommy Spicer Wilkes County Schools 613 Cherry Street North Wilkesboro, NC 28659 SUBJECT: Compliance Evaluation Inspection Boomer -Ferguson Elementary WWTP NPDES Permit # NCO075515 Wilkes County Dear Mr. Spicer: Donald R. van der Vaart Secretary A Compliance Evaluation Inspection was performed by George Smith on October 7, 2015. Mr. Tommy Spicer, ORC was present at this inspection. The inspection is comprised of an overall evaluation of the facilities equipment, and capability to produce an effluent discharge that meets NPDES permit limits. Permit Your NPDES permit became effective on October 1, 2013 and expires on September 30, 2018. The eDMR requirement is included in the permit under Section A.(3). Wilkes County Schools did register for eDMR, and is working on eDMR submission. Please remember that both paper and eDMR submission are required at this time. Records & Reports Mr. Spicer maintains an operator log, which documents sampling, analysis, Operations & Maintenance, and his visitations. The records are well organized and maintained in a file cabinet. All are in excellent order. Facility Site Review There are two sandfilters, each one has a 6-inch main line. There are eight 4-inch dosing lines in each sandfilter. The beds appear to need more sand. The tablet chlorinator uses two tubes of Norweco calcium hypochlorite tablets. The tablet dechlorinator uses two tubes of Norweco sodium bisulfite tablets. There are two small trees adjacent to the beds that need to be removed. Flow Measurement The flow is measured using the intake water meter. 450 W Hanes Mill Rd., Suite 300, Winston-Salem, NC 27105 Phone: 336-776-9800 t Internet: www.nodenr.gov An Equal Opportunity \ Affirmative Action Employer — Made in part by recycled paper Laboratory Wilkes County Schools is an approved field certified lab (# 5406). The pH calibration is performed with a SensIon 156, using a three-point calibration method (buffers 4, 7, 10), and a midrange check at 7.0. The calibration is recorded. Temperature is measured with the pH meter and is calibrated, documented, and is traceable to NIST. The Dissolved Oxygen is measured with an YSI, Model 50B meter, and the air calibration is performed. The Total Residual Chlorine is measured with a Hach DR2700 spectrophotometer. The 5-point annual calibration is scheduled to be performed during October 2015. Effluent/Receiving Waters The effluent from the sandfilter is discharged through a tablet chlorinator and tablet dechlorinator. It then goes to a manhole just outside the fence on top of the bank followed by a second manhole down along a dirt road, which then discharges to an unnamed tributary to Warrior Creek, Class WS-IV waters. Operations & Maintenance The facility is satisfactorily operated and maintained. Mr. Tommy Spicer, Grade II is the ORC; Mr. Stacy Higgins, Grade II, Back-up ORC. Self -Monitoring Program Grab samples are taken at the manhole, which is adjacent to the gravel road. A review of the monthly self -monitoring reports from January 2015 through July 2015 showed no limit violations. The compliance evaluation inspection is satisfactory. If you have any questions please contact George Smith or me at (336) 776-9800. Sincerely, W. Corey Basinger, Regional Supervisor Water Quality Regional Operations Section Division of Water Resources, NCDEQ cc: WSRO Files United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 IS 1 3 I NCO075515 I11 12 15/10/07 17 18 I c I 19 t! I 201 I 211111111111111U11111111111111111111111111-26 Inspection Work Days Facility Self -Monitoring Evaluation Rating 131 CA ------ ---------Reserved------------- 67I I 7072 LNJ 73I 75L I L 1_LJj80 I� 70JI 71 LI Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 09:OOAM 15/10/07 13/12/01 Boomer Ferguson Elementary School Exit Time/Date Permit Expiration Date 556 Boomer -Ferguson Sch R Boomer NC 28608 11:OOAM 15/10/07 18/09/30 Names) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Thomas J Spicer/ORC/336-651-4010/ Name, Address of Responsible Offciallritle/Phone and Fax Number Contacted Ken Barfleld,201 W Main St Wilkesboro NC 28697//336-921-30151 No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit 0 Flow Measurement Operations & Maintenance E Records/Reports Self -Monitoring Program E Facility Site Review Effluent/Receiving Waters Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date George S Smith WSRO WQ//336-776-9700/ Signature of Management Q A Reviewer Agency/Office/Phone and FaxNumbers Date l2N—Zd I"S— EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# Permit: NCO075515 Owner -Facility: Boomer Ferguson Elementary School Inspection Date: 10107/2015 Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ 0 ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: observe beds Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ 0 ❑ application? Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? 0 ❑ ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection?. 0 ❑ ❑ ❑ Comment: eDMR requirement Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? M ❑ ❑ ❑ Is all required information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? 0 ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain -of -custody complete? ❑. ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? 0 ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ 0 ❑ (If the facility is = or> 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ 0 ❑ on each shift? Is the ORC visitation log available and current? 0 ❑ ❑ ❑ Is the ORC certified at grade equal-fo -or higher than the facility Cl�sslficjtlon?. : • 0 ❑ ❑ ' Is the backup operator certified at one grade less or greater than the facility classification? ❑- ❑ ❑ Is a copy of the current NPDES permit available on site? ❑ ❑ 0 ❑ Page# 3 Permit: NC0075515 Inspection Date: 10/07/2015 Record Keeping Facility has copy of previous year's Annual Report on file for review? Owner -Facility: Boomer Ferguson Elementary School Inspection Type: Compliance Evaluation Comment: Permits are at maintenance shop in a file. They are readily produced. Yes No NA NE ■ ❑ ❑ ❑ Sand Filters (Low rate) Yes No NA NE (If pumps are used) Is an audible and visible alarm Present and operational? M ❑ ❑ ❑ Is the distribution box level and watertight? 0 ❑ ❑ ❑ Is sand filter free of ponding? 0 ❑ ❑ ❑ Is the sand filter effluent re -circulated at a valid ratio? ❑ ❑ M ❑ # Is the sand filter surface free of algae or excessive vegetation? 0 ❑ ❑ ❑ # Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1) ❑ ❑ 0 ❑ Comment: Beds need more sand Disinfection -Tablet Yes No NA NE Are tablet chlorinators operational? 0 ❑ ❑ ❑ Are the tablets the proper size and type? 0 ❑ ❑ ❑ Number of tubes in use? 1 Is the level of chlorine residual acceptable? 0 ❑ ❑ ❑ Is the contact chamber free of growth, or sludge buildup? 0 ❑ ❑ ❑ Is there chlorine residual prior to de -chlorination? ❑ ❑ ❑ Comment: De -chlorination Yes No NA NE Type of system ? Tablet Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ 0 ❑ ❑ Is storage appropriate for cylinders? ❑ ❑ 0 ❑ # Is de -chlorination substance stored away from chlorine containers? ❑ ❑ 0 ❑ Are the tablets the proper size and type? 0 ❑ ❑ ❑ Comment: use 2 tubes Are tablet de -chlorinators operational? ❑ ❑ ❑ Number of tubes in use? 2 Comment: two dechlor tubes are used Effluent Sampling Yes No NA NE Page# 4 Permit: NCO075515 Owner - Facility: Boomer Ferguson Elementary School Inspection Date: 10/07/2015 Inspection Type: Compliance Evaluation Effluent Samplina Yes No NA NE Is composite sampling flow proportional? ❑ ❑ 0 ❑ Is sample collected below all treatment units? 0 ❑ ❑ ❑ Is proper volume collected? 0 ❑ ❑ ❑ Is the tubing clean? ❑ ❑ 0 ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑ 0 ❑ Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type 0 ❑ ❑ ❑ representative)? Comment: grab samples on ice Page# 5