HomeMy WebLinkAboutNC0081825_Inspection_20221213United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code
1 IN I 2 IL
21IIIIII
NPDES yr/mo/day Inspection
I 3 I NC0081825 111 121 22/12/13 117
Type
1810I
IIIIIIIIIII
Inspector Fac Type
19I S I 2011
IIIIIIIIIII IIIIIII I IIIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
671 I 7° I I 711 172 I N I 73I 1 74 71
I I J
I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES Dermit Number)
Ansonville WWTP
NCSR 1627
Ansonville NC 28007
Entry Time/Date
10:OOAM 22/12/13
Permit Effective Date
21/07/01
Exit Time/Date
12:30PM 22/12/13
Permit Expiration Date
24/01/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Christopher J Mullis/ORC/704-776-8916/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Daniel Lane Wilson,PO Box 106 Ansonville NC 280070106//704-826-8404/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Facility Site Review Effluent/Receiving Wate Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s)
Hughie White
of Inspector(s) Agency/Office/Phone and Fax Numbers
�Docusigneaby: DWR/FRO WQ/910-433-3300 Ext.708/
Alug / 1Oh
-49E06C80007E432...
Date
1/6/2023
Signature of Management
Mark Brantl
Q A Reviewer Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
y Ilitztj& broxi AWR/FRO WQ/910-433-3300 Ext.727/ 1/9/2023
�E4E1A9691 DB248E...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
31
NPDES yr/mo/day
NC0081825 111 121 22/12/13
I17
Inspection Type
18 [j
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Records and log books appeared to be well organized and maintained. The ORC visitation log
appeared to be complete and current. Laboratory data was reviewed and all data that was reviewed
appeared to be correct, as reported on the DMR's. The facility appeared to be operated and
maintained properly with very good housekeeping. At the time of this inspection, the effluent
appeared to be very clear with no visible solids.
Page# 2
Permit: NC0081825
Inspection Date: 12/13/2022
Owner - Facility: Ansonville WWTP
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable II ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ El ❑
application?
Is the facility as described in the permit? • ❑ ❑ ❑
# Are there any special conditions for the permit? ❑ ❑ • ❑
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment:
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? • ❑ ❑ ❑
Is all required information readily available, complete and current? • ❑ ❑ ❑
Are all records maintained for 3 years (lab. reg. required 5 years)? • ❑ ❑ ❑
Are analytical results consistent with data reported on DMRs? • ❑ ❑ ❑
Is the chain -of -custody complete? • ❑ ❑ ❑
Dates, times and location of sampling •
Name of individual performing the sampling •
Results of analysis and calibration •
Dates of analysis •
Name of person performing analyses •
Transported COCs ■
Are DMRs complete: do they include all permit parameters? • ❑ ❑ ❑
Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ❑ •
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified ❑ ❑ • ❑
operator on each shift?
Is the ORC visitation log available and current? • ❑ ❑ ❑
Is the ORC certified at grade equal to or higher than the facility classification? • ❑ ❑ ❑
Is the backup operator certified at one grade less or greater than the facility • ❑ ❑ ❑
classification?
Page# 3
Permit: NC0081825
Inspection Date: 12/13/2022
Owner - Facility: Ansonville WWTP
Inspection Type: Compliance Evaluation
Record Keeping
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Comment: A copy of the current permit is not being kept on site.
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Yes No NA NE
❑ • ❑ ❑
❑ ❑ ❑ •
Yes No NA NE
•
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots? • ❑ ❑ ❑
Are surface aerators and mixers operational? ❑ ❑ • ❑
Are the diffusers operational? • ❑ ❑ ❑
Is the foam the proper color for the treatment process? • ❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface? • ❑ ❑ ❑
Is the DO level acceptable? • ❑ ❑ ❑
Is the DO level acceptable?(1.0 to 3.0 mg/I) • ❑ ❑ ❑
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Yes No NA NE
• ❑ ❑ ❑
• ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 4
Permit: NC0081825
Inspection Date: 12/13/2022
Owner - Facility: Ansonville WWTP
Inspection Type: Compliance Evaluation
Secondary Clarifier
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Disinfection -Tablet Yes No NA NE
Are tablet chlorinators operational? • ❑ ❑ ❑
Are the tablets the proper size and type? • ❑ ❑ ❑
Number of tubes in use? 1
Is the level of chlorine residual acceptable? ❑ ❑ ❑ •
Is the contact chamber free of growth, or sludge buildup? • ❑ ❑ ❑
Is there chlorine residual prior to de -chlorination? ❑ ❑ El •
Comment:
De -chlorination Yes No NA NE
Type of system ? Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)? • ❑ ❑ ❑
Is storage appropriate for cylinders? El El • ❑
# Is de -chlorination substance stored away from chlorine containers? • El El El
Comment:
Are the tablets the proper size and type? • El El El
Are tablet de -chlorinators operational? • ❑ ❑ ❑
Number of tubes in use? 1
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ • ❑
Page# 5
Permit: NC0081825
Inspection Date: 12/13/2022
Owner - Facility: Ansonville WWTP
Inspection Type: Compliance Evaluation
Flow Measurement - Effluent Yes No NA NE
Comment: The flow meter was calibrated in October.
Pump Station - Effluent Yes No NA NE
Is the pump wet well free of bypass lines or structures? • ❑ ❑ ❑
Are all pumps present? • ❑ ❑ ❑
Are all pumps operable? • ❑ ❑ ❑
Are float controls operable? • ❑ ❑ ❑
Is SCADA telemetry available and operational? • ❑ ❑ ❑
Is audible and visual alarm available and operational? • ❑ ❑ ❑
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ • ❑ ❑
Is sample collected below all treatment units? • ❑ ❑ ❑
Is proper volume collected? ■ ❑ ❑ ❑
Is the tubing clean? • ❑ El El
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 • ❑ ❑ ❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • ❑ ❑ ❑
representative)?
Comment: Compostie samples are collected at timed intervals.
Page# 6