Loading...
HomeMy WebLinkAboutWQ0043691_Application (FTSE)_20220812VccCL13(DcH Michael W. Robinson, P.E., P.L.S. August 05, 2022 NCDENR, Division of Environmental Quality Washington Regional Office 943 Washington Square Mall Washington, NC 27889 Engineering and Surveying Mailing Address: P.O. Box 2852 (104 Jester Court) Kill Devil Hills, North Carolina 27948 mrobinson@obxengineering.com Phone: 252-255-8026 Re: Ocean Breeze Townhomes Fast Track Application (FTA 04-16) For Receiving Sewer Utility - KDHWWTP, LLC Wastewater Collection System Extension (Pump Station and Force Main) Kill Devil Hills, Dare County, North Carolina Dear Sir/Madame, Enclosed please find FTA 04-16 and supporting data for a pump station and force main addition to the KDHWWTP, LLC wastewater utility. The following information is included with this submittal: 1. Fast Track application form completed and signed. 2. Project narrative with flow justification. 3. FTSE 04-16 signed. 4. Quad Sheet with project identified. 5. Current permit for receiving sewer (WQ0002829) 6. Reduced scale plans and details. 7. Application fee of $480.00. Thank you for your assistance with this project. If you have any questions please feel free to call me at 252-255-8026. I can also be reached by email at mrobinson@obxengineering.com. Sincerel Michael W. Ro lnson P.L., P.L.S. RECEIVED/NCDENFf1DWFd AUG 12 2022 Water Quality Regional Operations Section Washington Regional Office; DwR Division of Water Resources State of North Carolina Department of Environmental Quality Division of Water Resources 15A NCAC 02T .0300 — FAST TRACK SEWER SYSTEM EXTENSION APPLICATION INSTRUCTIONS FOR FORM: FTA 04-16 & SUPPORTING DOCUMENTATION This application is for sewer extensions involving gravity sewers, pump stations and force mains, or any combination that has been certified by a professional engineer and the applicant that the project meets the requirements of 15A NCAC 02T and the Division's Minimum Design Criteria and that plans, specifications and supporting documents have been prepared in accordance with, 15A NCAC 02T, 15A NCAC 02T .0300, Division policies and good engineering practices. While no upfront engineering design documents are required for submittal, in accordance with 15A NCAC 02T .0305(b), design documents must be prepared prior to submittal of a fast track permit application to the Division. This would include plans, design calculations, and project specifications referenced in 15A NCAC 02T .0305 and the applicable minimum design criteria. These documents shall be available upon request by the Division. Projects that are deemed permitted (do not require a permit from the Division) are explained in 15A NCAC 02T.0303. Projects not eligible for review via the fast track process (must be submitted for full technical review): ➢ Projects that require an environmental assessment in accordance with 15A NCAC 1 C .0100; ➢ Projects that do not meet any part of the minimum design criteria (MDC) document; ➢ Projects that involve a variance from the requirements of 15A NCAC 2T; ➢ Pressure sewer systems utilizing septic tank -effluent pumps (STEPs) or simplex grinder pumps; ➢ STEP or simplex grinder pumps connecting to pressurized systems (e.g. force mains); ➢ Vacuum sewer systems. General — When submitting an application, please use the following instructions as a checklist in order to ensure all required items are submitted. Adherence to these instructions and checking the provided boxes will help produce a quicker review time and reduce the amount of requested additional information. Failure to submit all required items will necessitate additional processing and review time, and may result in return of the application. Unless otherwise noted, the Applicant shall submit one original and one copy of the application and supporting documentation. A. One Original and One Copy of Application and Supporting Documents Required unless otherwise noted B. Cover Letter (Required for All Application Packages): List all items included in the application package, as well as a brief description of the requested permitting action. ➢ Be specific as to the system type, number of homes served, flow allocation required, etc. > If necessary for clarity, include attachments to the application form. C. Application Fee (All New and Major Modification Application Packages): ® Submit a check or money order in the amount of $480.00 dated within 90 days of application submittal. > Payable to North Carolina Department of Environmental Quality (NCDEQ) D. Fast Track (Form: FTA 04-16) Application (Required for All Application Packages): ® Submit the completed and appropriately executed application. > If necessary for clarity or due to space restrictions, attachments to the application may be made. ❑ If the Applicant Type in Item 1.2 is a corporation or company, provide documentation it is registered for business with the North Carolina Secretary of State. ❑ If the Applicant Type in Item 1.2 is a partnership or d/b/a, enclose a copy of the certificate filed with the Register of Deeds in the county of business. • The Project Name in Item 11.1 shall be consistent with the project name on the flow acceptance letters, agreements, etc. ® The Professional Engineer's Certification on Page 5 of the application shall be signed, sealed and dated by a North Carolina Licensed Professional Engineer. ® The Applicant's Certification on Page 5 of the application shall be signed in accordance with 15A NCAC 02T .0106(b). Per 15A NCAC 02T .0106(c), an alternate person may be designated as the signing official if a delegation letter is provided from a person who meets the criteria in 15A NCAC 02T .0106(b). INSTRUCTIONS FOR FORM: FTA 04-16 & SUPPORTING DOCUMENTATION Page 1 of 3 f E. Flow Tracking/Acceptance Form (Form: FTSE 04-16) (If Applicable): ➢ Submit the completed and executed FTSE form from the owners of the downstream sewers and treatment facility. ➢ Multiple forms maybe required where the downstream sewer owner and wastewater treatment facility are different. ➢ The flow acceptance indicated in form FTSE must not expire prior to permit issuance and must be dated less than one year prior to the application date. ➢ Submittal of this application and form FTSE indicates that owner has adequate capacity and will not violate G.S. 143- 215.67(a). ➢ Intergovernmental agreements or other contracts will not be accepted in lieu of a project -specific FTSE. F. Site Maps (All Application Packages): El Submit an 8.5-inch x 11-inch color copy of a USGS Topographic Map of sufficient scale to identify the entire project area and closest surface waters. > Location of the project (gravity sewer, pump stations & force main) ➢ Downstream connection points and permit number (if known) for the receiving sewer El Include a street level map (aerial) showing general project area so that Division staff can easily locate it in the field. G. Existing Permit (All Modification Packages): ® Submit the most recently issued existing permit. ❑ Provide a list of any items within the permit the Applicant would like the Division to address during the permit modification (Le., permit description, flow allocation, treatment facility, etc.). H. Power Reliability Plan (Required if portable reliability option utilized for Pump Station): ® Per 15A NCAC 02T .0305(h)(1), submit documentation of power reliability for pumping stations. > This alternative is only available for average daily flows less than 15,000 gallons per day ➢ It shall be demonstrated to the Division that the portable source is owned or contracted by the applicant and is compatible with the station. The Division will accept a letter signed by the applicant (see 15A NCAC 02T .0106(b)) or proposed contractor, stating that "the portable power generation unit or portable, independently -powered pumping units, associated appurtenances and personnel are available for distribution and operation of this pump station." > If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump stations' storage capacities and the rotation schedule of the portable power source or pump, including travel timeframes, shall be provided in the case of a multiple station power outage. (Required at time of certification) I. Certificate of Public Convenience and Necessity (All Application Packages for Privately -Owned Public Utilities): ® Per 15A NCAC 02T .0115(a)(1) provide the Certificate of Public Convenience and Necessity from the North Carolina Utilities Commission demonstrating the Applicant is authorized to hold the utility franchise for the area to be served by the sewer extension, or ❑ Provide a letter from the North Carolina Utilities Commission's Water and Sewer Division Public Staff stating an application for a franchise has been received and that the service area is contiguous to an existing franchised area or that franchise approval is expected. J. Operational Agreements (Applications from HOA/POA and Developers for lots to be sold): ❑ Home/Property Owners' Associations ❑ Per 15A NCAC 02T .0115(c), submit the properly executed Operational Agreement (FORM: HOA). ❑ Per 15A NCAC 02T .0115(c), submit a copy of the Articles of Incorporation, Declarations and By-laws. ❑ Developers of lots to be sold ❑ Per 15A NCAC 02T .0115(b), submit the properly executed Operational Agreement (FORM: DEV). For more information, visit the Division's collection systems website INSTRUCTIONS FOR FORM: FTA 04-16 & SUPPORTING DOCUMENTATION Page 2 of 3 THE COMPLETED APPLICATION PACKAGE INCLDING ALL SUPPORTING INFORMATION AND MATERIALS, SHOULD BE SENT TO THE APPROPRIATE REGIONAL OFFICE: REGIONAL OFFICE ADDRESS COUNTIES SERVED Avery, Buncombe, Burke, Caldwell, Cherokee, Clay, Graham, Haywood, Henderson, Jackson, Macon, Madison, McDowell, Mitchell, Polk, Rutherford, Swain, Transylvania, Yancey Asheville Reqional Office 2090 US Highway 70 Swannanoa, North Carolina 28778 (828) 296-4500 (828) 299-7043 Fax Water Quality Section Fayetteville Reqional Office Water Quality Section 225 Green Street Suite 714 Fayetteville, North Carolina 28301-5094 (910) 433-3300 (910) 486-0707 Fax Anson, Bladen, Cumberland, Harnett, Hok, Montgomery, Moore, Robeson, Richmonde Sampson, Scotland Mooresville Reqional Office Water Quality Section 610 E. Center Avenue Mooresville, North Carolina 28115 (704) 663-1699 (704) 663-6040 Fax Alexander, Cabarrus, and, Gaston, Iredeli, Lincoln, aMecklenburg, tawba, lIR Rowan, Stanly, Union Raleigh Reqional Office Water Quality Section 1628 Mail Service Center Raleigh, North Carolina 27699-1628 (919) 791-4200 ( Washington Reqional Office Water Quality Section 943 Washington Square Mall Washington, North Carolina 27889 (252) 946-6481 (252) 975-3716 Fax Beaufort, Bete, Camden, Chowan, Craven, Currituck, Dare, Gates, Greene, Hertford, Hyde, Jones, Lenoir, Martin, Pamlico, Pasquotank, Perquimans, Pitt, Tyrrell, Washington, Wayne Wilmington Reqional Office Water Quality Section 127 Cardinal Drive Extension Wilmington, North Carolina 28405 (910) 796-7215 (910) 350-2004 Fax Brunswick, Carteret, umbus, Duplin, New Hanover, Onslow, P nder Winston-Salem Reqional Office 450 W. Hanes Mill Road Suite 300 Winston-Salem, North Carolina 27105 (336) 776-9800 Alamance, Alleghany, Ashe, Caswell, Davidson, Davie, Forsyth, Guilford, Rockingham, Randolph, Stokes, Surry, Watauga, Wilkes, Yadkin Water Quality Section INSTRUCTIONS FOR FORM: FTA 04-16 & SUPPORTING DOCUMENTATION Page 3 of 3 DWR Division of Water Resources State of North Carolina Department of Environmental Quality Division of Water Resources 15A NCAC 02'I' .0300 — FAST TRACK SEWER SYSTEM EXTENSION APPLICATION FTA 04-16 & SUPPORTING DOCUMENTATION Application Number: (to be completed by DWR) All items must be com feted or the a lication will be returned I. APPLICANT INFORMATION: 1. Applicant's name: KDHWWTP LLC (company, municipality, HOA, utility, etc.) 2. Applicant type: El Individual ❑ Corporation ❑ General Partnership ®Privately -Owned Public Utility ❑ Federal ❑ State/County ❑ Municipal El 3. Signature authority's name: George E. Goodrich per 15A NCAC 02T .0106 b Other Title: Mana in Partner 4. Applicant's mailing address: P.O. Box 3629 City: Kill D� State: North Carolina Zip: 27948- 5. Applicant's contact information: Phone number: (252) 475-0874 Email Address: eddie oodrich villa ereal obx.com II. PROJECT INFORMATION: 1. Project name: OCEAN BREEZE TOWNHOMES 2. Application/Project status: ® Proposed P (New Permit) ❑Existing Permit/Project If a modification, provide the existing permit number: WQ00 and issued date: If new construction but part of a master plan, provide the existing permit number: WQ00 3. County where project is located: Dare 4. Approximate Coordinates (Decimal Degrees): Latitude: 36.00897° Longitude:-75.65501 ° 5. Parcel ID (if applicable): (or Parcel ID to closest downstream sewer) III. CONSULTANT INFORMATION: 1. Professional Engineer: Michael W. Robinson P.E. License Number: NC 18994 Firm: Michael W. Robinson P.E. P.L.S. Mailing address: P.O. Box 2852 City: Kill Devil State: NC Zip: 27948- Phone number: (252) 255-8026 Email Address: mrobinson(a?obxeneineeringcorn IV. WASTEWATER TREATMENT FACILITY (WWTF) INFORMATION: 1. Facility Name: KDHWWTP LLC Permit Number: W00002829 Owner Name: KDHWWTp LLC V. RECEIVING DOWNSTREAM SEWER INFORMATION (if different than WWTF): 1. Permit Number(s): WQ0002829 Downstream (Receiving) Sewer Size: 6 inch System Wide Collection System Permit Numbers) (ifappllicable): WQCS OwnerName(s): KDHWWTP LLC FORM: FTA 04-16 Page 1 of 5 VI. GENERAL REQUIREMENTS 1. If the Applicant is a Privately -Owned Public Utility, has a Certificate of Public Convenience and Necessity been attached? ® Yes ❑No ❑N/A 2. If the Applicant is a Developer of lots to be sold, has a Developer's Operational Agreement (FORM: DEV) been attached? ❑ Yes ❑No ®N/A 3. If the Applicant is a Home/Property Owners' Association, has an Operational Agreement (FORM: HOA) been attached? ❑ Yes ❑No ®N/A 4. Origin of wastewater: (check all that apply): ® Residential Owned ❑ Retail (stores, centers, malls) ❑ Car Wash ❑ Residential Leased ❑ Retail with food preparation/service ❑ Hotel and/or Motels ❑ School / preschool / day care ❑ Medical / dental / veterinary facilities ❑ Swimming Pool /Clubhouse El Food and drink facilities ❑ Church ❑ Swimming Pool/Filter Backwash ❑ Businesses / offices / factories ❑ Nursing Home ❑ Other (Explain in Attachment) 5. Nature of wastewater : 100 % Domestic/Commercial % Commercial % Industrial (See 15A NCAC 02T .0103(20)) 1----->Is there a Pretreatment Program in effect? ❑ Yes ❑ No 6. Has a flow reduction been approved under 15A NCAC 02T .0114(f)? ❑ Yes 1Z4 No > If ves, provide a copy of flow reduction approval letter 7. Summarize wastewater generated by project: Establishment Type (see 02T.0114(f)) Daily Design Flow a,b Multifamily- habitable room 120 gal/day gal/ gal/ gall gal/ gal/ a See 15A NCAC 02T .0114(b), (d), (e)(1) and (e)(2) for caveats to wastewater des,„ „vw rates (l.e., minimum tlow per dwelling; proposed unknown non-residential development uses; public access facilities located near high public use areas; and residential property located south or east of the Atlantic Intracoastal Waterway to be used as vacation rentals as defined in G.S. 42A-4). No. of Units Flow 120 14,400 GPD GPD GPD GPD GPD GPD Total 14,400 GPD b Per 15A NCAC 02T .0114(c), design flow rates for establishments not identified [in table I5A NCAC 02T.0114] shall be determined using available flow data, water using fixtures, occupancy or operation patterns, and other measured data. 8. Wastewater generated by project: 14,400 GPD (per 15A NCAC 02T .0114) ➢ Do not include future flows or previously permitted allocations If permitted flow is zero, indicate why: ❑ Pump Station or Gravity Sewer where flow will be permitted in subsequent permits that connect to this line ❑ Flow has already been allocated in Permit Number: ❑ Rehabilitation or replacement of existing sewer with no new flow expected ❑ Other (Explain): FORM: 1'TA 04-16 Page 2 of 5 VIL GRAVITY SEWER DESIGN CRITERIA (If Applicable) - 02� & MDC Gravi 1. Summarize gravity sewer to be permitted: tv Sewers). 111111111111111111.11111111111111111 111111111111111111111111111111111111 Section II & III of the MDC for Permitting of Gravity Sewers contains information related to design criteria Section III contains information related to minimum slopes for gravity sewer(s) VIII. Oversizing lines to meet minimum slope requirement is not allowed and a violation oft PUMP STATION DESIGN CRITERIA (If Applicable) — 02— & MDC Pum S he MDC COMPLETE FOR EACH PUMP STATION INCLUDED IN THIS PROJECTrce Mains): 1. Pump station number or name: 1 2. Approximate Coordinates (Decimal Degrees): Latitude: 36 0 0263° Longitude:-75.65501° 3. Design flow of the pump station: 0.2592 millions gallons per day (firm capacity) 4. Operational point(s) of the pump(s): 180 gallons per minute at 59 feet total dynamic head TD 5. Summarize the force main to be permitted (for this Pump Station): ( H) 6. Power reliability in accordance with 15A NCAC 02T .0305 h 1 ❑ Standby power source or pump with automatic activation and telemetry CAC ➢ Required for all pump stations with an average daily flow greater than r equal tro 15,000 T gallons per1day)_ ➢ Must be permanent to facility per day Or if the pump station has an average daily flow less than 15,000 gallons per day: ❑ Portable power source with manual activation, quick -connection receptacle and telemetry - 15A NCAC 02T ® Portable pumping unit with plugged emergency pump connection and telemetry - 15A It shall be demonstrated to the Division that the portable source is owned or contracted by NCAC 02T .0305(h)(1)(C): and is compatible with the station. If the portable power source or pump is dedicated to multiple pump the applicant (draft agreement) storage capacities and the rotation schedule of the portable power source or pump, including travel tim provided in the case of a multiple station power outage. stations, an evaluation of all the pump stations' eframes, shall be FORM: FTA 04-16 Page 3 of 5 IX. SETBACKS & SEPARATIONS — (02B .0200 & 15A NCAC 02T .0305(0): 1. Does the project comply with all separations found in 15A NCAC 02T .0305(fl & (g) > 15A NCAC 02T.0305(f) contains minimum separations that shall be provided for sewer systems: Setback Parameter* Storm sewers and other utilities not listed below (vertical) Water mains (vertical -water over sewer including in benched trenches) Water mains (horizontal) Reclaimed water lines (vertical - reclaimed over sewer) Reclaimed water lines (horizontal - reclaimed over sewer) **Any private or public water supply source, including any wells, WS-I waters of Class I or Class II impounded reservoirs used as a source of drinking water **Waters classified WS (except WS-I or WS-V), B, SA, ORW, HQW, or SB from normal high water (or tide elevation) and wetlands (see item IX.2) **Any other stream, lake, impoundment, or ground water lowering and surface drainage ditches Any building foundation Any basement Top slope of embankment or cuts of 2 feet or more vertical height Drainage systems and interceptor drains Any swimming pools Final earth grade (vertical) ® Yes ❑ No Separation Required 24 inches 18 inches 10 feet 18 inches 2 feet 100 feet 50 feet 10 feet 5 feet 10 feet 10 feet 5 feet 10 feet 36 inches > 15A NCAC 02T.0305(g) contains alternatives where separations in 02T.0305(f) cannot be achieved. ➢ **Stream classifications can be identified using the Division's NC Surface Water Classifications webpage > If noncompliance with 02T.0305(0 or (g), see Section X of this application 2. Does the project comply with separation requirements for wetlands? (50 feet of separation) ❑ Yes lEi ➢ See the Division's draft separation requirements for situations where separation cannot be meet NO ®N/A > No variance is required if the alternative design criteria specified is utilized in design and construction ➢ As built documents should reference the location of areas effected 3. Does the project comply with setbacks found in the river basin rules per 15A NCAC 02B .0200? ❑ Yes ❑ No ® N/A > This would include Trout Buffered Streams per 15A NCAC 2B.0202 4. Does the project require coverage/authorization under a 404 Nationwide or individual permits or 401 Water Quality Certifications? El Yes ®No > Information can be obtained from the 401 & Buffer Permitting Branch 5. Does project comply with 15A NCAC 02T.0105(c)(6) (additional permits/certifications)? ❑ Yes ® No Per 15A NCAC 02T.0105(c)(6), directly related environmental permits or certification applications are being prepared, have been applied for, or have been obtained. Issuance of this permit is contingent on issuance of dependent permits (erosion and sedimentation control plans, stormwater management plans, etc.). 6. Does this project include any sewer collection lines that are deemed "high -priority?" Per 15A NCAC 02T.0402, "high -priority sewer" means "any aerial sewer, sewer contacting surface waters, siphon, or sewer positioned parallel to streambanks that is subject to erosion that undermines or deteriorates the sewer. ❑ Yes ®No ❑ N/A ➢ If yes, include an attachment with details for each line, including type (aerial line, size, material, and location). High priority lines shall be inspected by the permittee or its representative at least once every six -months and inspections documented per 15A NCAC 02T.0403(a)(5) or the permitee's individual System -Wide Collection permit. FORM: FTA 04-16 Page 4 of 5 X. CERTIFICATIONS: 1, Does the submitted system comply with 1 SA NCAC 02T, the Minimum Desn Criteria for the Permitting of Pump Stations and Force Mains (latest version), and the Gravity Sewer Minimum Design Criteria (latest version.) as applicable? ® Yes [] No If No, complete and submit the Variance/Alternative Design Request application (VADC 10-14) and supporting documents for review. Approval of the request is required prior to submittal of the Fast Track Application and supporting documents. 2. Professional Engineer's Certification: I, ('IW4M e_ A). 126ruf-lsou attest that this application for (Professional Engineer's name from Application Item III.1.) has been reviewed by me and is accurate, complete and consistent with the information supplied in the plans, specifications, engineering calculations, and all other supporting documentation to the best of my knowledge. I further attest that to the best of my knowledge the proposed design has been prepared in accordance with the applicable regulations, Gravity Sewer Minimum Design Criteria for Gravity Sewers (latest version), and the Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains (latest version). Although other professionals may have developed certain portions of this submittal package, inclusion of these materials under my signature and seal signifies that I have reviewed this material and have judged it to be consistent with the proposed design. NOTE — In accordance with General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may include a fine not to exceed $10,000, as well as civil penalties up to $25,000 per violation. North Carolina Professional Engineer's seal, signature, and date: 3. Applicant's Certification Jper 15AANNCAC 02T .0106(b): / � / e ` " • 4/rr _L , 4 '"o"aq .e-L attest that this application for (Signature Authority's name & title from Application Item has been reviewed by me and is accurate and complete to the best of my knowledge. I understand that if all required parts of this application are not completed and that if all required supporting documentation and attachments are not included, this application package is subject to being returned as incomplete. I understand that any discharge of wastewater from this non - discharge system to surface waters or the land will result in an immediate enforcement action that may include civil penalties, injunctive relief, and/or criminal prosecution. I will make no claim against the Division of Water Resources should a condition of this pernut be violated. I also understand that if all required parts of this application package are not completed and that if all required supporting information and attachments are not included, this application package will be returned to me as incomplete. NOTE — In accordance with General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation. Signature: FORM: FTA 04-16 Date: Page 5 of 5 Project Narrative for Fast -track Application (FTA 04-16) OCEAN BREEZE TOWNHOMES Kill Devil Hills, Dare County, North Carolina Design flow =14,400 gpd Property Location and Property Data: Lot 1A, Block 9, Section 1, Kill Devil Hills Subdivision, Kill Devil Hills, Dare Co, NC Street Address: 902 S. Va. Dare Trail, Kill Devil Hills, NC 27948 Recorded Reference: P.C. 1 SI. 356, D.B. 2534 Pg. 033 Parcel: 027620000 PIN: 9883 08 98 2774 Proposed Development: Multifamily Development Consisting of 6 Multi -Family Residential Buildings with a mix of two, three, four and five bedroom units for 30 total units with 90 total bedrooms. Project Wastewater Design Flow: Design Flow: 90 bedrooms with 30 additional habitable rooms (one per unit) for a total of 120 habitable rooms at 120 gpd per habitable room = 14,400 gpd. The utility will be owned and operated by the public wastewater utility permitted as KDHWWTP, LLC by permit WQ0002829. The property was added to the KDHWWTP, LLC service on May 04, 2009, Reference NC Utilities Commission Docket W-1160, Sub. 9. Division of Water Resources State of North Carolina Department of Environmental Quality Division of Water Resources Flow Tracking/Acceptance for Sewer Extension Applications (FTSE 04-16) Entity Requesting Allocation: KDHWWTP, LLC Project Name for which flow is being requested: OCEAN BREEZE TOWNHOMES More than one FTSE may be required for a single project if the owner of the WWTP is not responsible for all pump stations along the route of the proposed wastewater flow. I. Complete this section only if you are the owner of the wastewater treatment plant. a. WWTP Facility Name: KDHWWTP, LLC b. WWTP Facility Permit #: WQ0002829 (July 14, 2017) All flows are in MGD c. WWTP facility's permitted flow 0.660000 d. Estimated obligated flow not yet tributary to the WWTP 0.206650 e. WWTP facility's actual avg. flow 0.232124 f. Total flow for this specific request 0.014400 g. Total actual and obligated flows to the facility 0.453174 h. Percent of permitted flow used 68.7 II. Complete this section for each pump station you are responsible for along the route of this proposed wastewater flow. List pump stations located between the project connection point and the WWTP: (A) (B) (C) (D)=(B+C) (E)=(A-D) Design Obligated, Pump Average Daily Approx. Not Yet Total Current Station Firm Flow** Current Avg. Tributary Flow Plus (Name or Capacity, * (Firm / pf), Daily Flow, Daily Flow, Obligated Available Number) MGD MGD MGD MGD Flow Capacity*** n/a * The Firm Capacity of any pump station is defined as the maximum pumped flow that can be achieved with the largest pump taken out of service. ** Design Average Daily Flow is the firm capacity of the pump station divided by a peaking factor (pf) not less than 2.5. *** A Planning Assessment Addendum shall be attached for each pump station located between the project connection point and the WWTP where the Available Capacity is < 0. Downstream Facility Name (Sewer): Downstream Permit Number: Page 1 of 6 FTSE 04-16 III. Certification Statement: I George E. Goodrich, Managing certify to the best of my knowledge that the addition of Partner the volume of wastewater to be permitted in this project has been evaluated along the route to the receiving wastewater treatment facility and that the flow from this project is not anticipated to cause any capacity related sanitary sewer overflows or overburden any downstream pump station en route to the receiving treatment plant under normal circumstances, given the implementation of the planned improvements identified in the planning assessment where applicable. This analysis has been performed in accordance with local established policies and procedures using the best available data. This certification applies to those items listed above in Sections I and II plus all attached planning assessment addendums for which I am the responsible party. Signature of this form indicates acceptance of this wastewater flow. Signin: OfciSignature Date Page 2 of 6 FTSE 04-16 40' �2 2000 v � 9000 10 000 South Croatan Hwy. OCEAN BREEZE TOWNHOMES 902 S. Virginia Dare Trail Kill Devil Hills, Dare County, NC NAGS HEAD 52 KAf .NT[R,OR—Ol Oi00,CAi euRv[v NreTON ViROM�_+ep, '42 443":"^E ROAD CLASSIFICATION Light -duty road, hard or Improved surface . QUADRANGLE LOCATION CONTOURS AND ELEVATIONS IN METERS Primary highway, hard surface --po -vy o'rR ass� s Secondary highway, 11 y hard surface -- -- — Unimproved road yos Trails n a.aow Interstate Route U. S. Route State Route KITTY HAWK, N. C. SW/4 KITTY HAWK 15' QUADRANGLE N3600- W7537.5/7.5 1982 DMA 5856 II SW -SERIES V8420 ROY COOPER Governor ELIZABETH S. BISER Secretary RICHARD E. ROGERS, JR. Director GEORGE E. GOODRICH — MANAGER KDHWWTP, L.L.C. POST OFFICE BOX 3629 KILL DEVIL HILLS, NORTH CAROLINA 27948 Dear Mr. Goodrich, _nn• f QILW VV° NORTH CAROLINA Environmental Quality July 29, 2022 Subject: Permit No. WQ0002829 KDHWWTP Reclaimed Water Generation, Dedicated Utilization, and High -Rate Infiltration System Dare County In accordance with your permit renewal request received May 6, 2022, we are forwarding herewith Permit No. WQ0002829 dated July 29, 2022, to KDHWWTP, L.L.C. for the continued operation of the reclaimed water generation, high -rate infiltration, and dedicated reclaimed utilization facilities , as well as the continued operation and subsequent conversion of the Train A reclaimed water generation facilities. This permit shall be effective from the date of issuance through April 30, 2029, shall replace Permit No. WQ0002829 issued July 14, 2017, and shall be subject to the conditions and limitations therein. The Permittee shall submit a renewal application no later than November 1, 2028. Please pay attention to the monitoring requirements listed Attachments A, B, and C for they may differ from the previous permit issuance. Failure to establish an adequate system for collecting and maintaining the required operational information shall result in future compliance problems. The Division has removed the following permit conditions since the last permit issuance dated July 14, 2017: > Old Condition I.1 — This condition has been removed as the Town of Kill Devil Hills does not own any of the reclaimed water irrigation sites. > Old Condition I.2 — This condition has been met. > Old Condition 1.6 — This condition is no longer required. > Old Condition 11.6 — This condition has been removed as the green area requirements have been repealed. > Old Condition 1II.20 — This condition has been removed because it is inherently covered under new Condition 1I1.8. rgrvn D E �� North Carolina Department of Environmental Quality I Division of Water Resources 512 North Salisbury Street 11617 Mail Service Center I Raleigh, North Carolina 27699-1617 919.707.9000 Mr. George E. Goodrich July 29, 2022 Page 2 of 2 The following permit conditions are new since the last permit issuance dated July 14, 2017: > Condition I.2 — This condition requires that the Permittee notify the Washington Regional Office at least two business days in advance of initial operation of the modified facilities so that the Division can conduct an inspection. > Conditions II.11, II.12, and 1I.13 — These conditions denote separation distances for the reclaimed water distribution lines. > Condition III.4 — This condition requires an operator be on call 24 hours per day. > Condition III.7 — This condition requires that irrigation not occur during inclement weather. > Condition 1I1.8 — This condition requires metering equipment be tested and calibrated annually. > Condition II1.25 — This condition requires continuous online monitoring and recording of turbidity. > Condition 11I.26 — This condition requires the Permittee to notify the public and its employees about the use of reclaimed water. > Condition I1I.27 — This condition requires the Permittee to develop and implement an education program to inform users and its employees about the proper use of reclaimed water. > Condition IV.5 — This condition has been revised to include additional recording requirements. > Condition VI.3 — This condition states that there are no variances to administrative codes or general statutes governing the construction or operation of the facilities permitted herein. If any parts, requirements, or limitations contained in this permit are unacceptable, the Permittee has the right to request an adjudicatory hearing upon written request within 30 days following receipt of this permit. This request shall be in the form of a written petition, conforming to Chapter 150B of the North Carolina General Statutes, and filed with the Office of Administrative Hearings at 6714 Mail Service Center, Raleigh, NC 27699-6714. Otherwise, this permit shall be final and binding. If you need additional information concerning this permit, please contact Lauren Raup-Plummer at (919) 707-3660 or Lauren.Plummer(cr�ncdenr ov. cc: Dare County Health Department (Electronic Washington Regional Office, Water Quality Laserfiche File (Electronic Copy) Digital Permit Archive (Electronic Copy) Sincerely, Richard E. Rogers, Jr., Director Division of Water Resources Copy) Regional Operations Section (Electronic Copy) NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION DEPARTMENT OF ENVIRONMENTAL QUALITY RALEIGH RECLAIMED WATER GENERATION, DEDICATED UTILIZATION, AND HIGH -RATE INFILTRATION SYSTEM PERMIT In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended, and other applicable Laws, Rules, and Regulations PERMISSION IS HEREBY GRANTED TO KDHWWTP, L.L.C. Dare County FOR THE operation of a 660,000 gallon per day (GPD) reclaimed water generation, dedicated utilization, and high - rate infiltration facility consisting of the: continued operation and subsequent conversion (as permitted December 9, 2016) of: the existing 312,000 gallon extended aeration "Train A" into a 5-stage Bardenpho Process with Integrated Fixed Film Activated Sludge (IFAS) configuration consisting of: a 70,097 gallon pre -anoxic Zone 1 with four 2 horsepower (hp) mixers; a 32,903 aeration Zone 1A with high -density polyethylene (HDPE) media; a 47,208 gallon aeration Zone 1 B with HDPE media; a 55,791 gallon aeration Zone 2A with HDPE media; a 24,319 gallon aeration Zone 2B with HDPE media and two 350 gallon per minute (GPM) recycle pumps; a 55,791 gallon post - anoxic Zone 1 with three 2 hp mixers and a carbon chemical feed system; a 22,889 re -aeration Zone 1 with an alum chemical feed system; and all associated piping, valves, controls, and appurtenances; the continued operation of a 660,000 GPD reclaimed water generation system consisting of: a stainless steel mechanically -cleaned helical fine screen; a 43,000 gallon flow equalization basin A; a 118,000 gallon aerated flow equalization basin C; a 38,630 gallon aerated flow equalization basin B with two 416 GPM equalization pumps; an aluminum flow splitter box with an alkalinity chemical feed system; a 312,000 gallon extended aeration "Train A"; a 310,000 gallon 5-stage Bardenpho Process "Train B" with a 70,195 gallon pre -anoxic Zone 2 with two 0.75 hp mixers and one 1.5 hp mixer, an 84,234 gallon aeration Zone 3, an 81,426 gallon aeration Zone 4 and two recycle pumps, a 56,156 gallon post -anoxic Zone 2 with one 1.5 hp mixer and a carbon chemical feed system, and a 16,846 gallon re -aeration Zone 2 with an alum chemical feed system; two 91,000 gallon clarifiers with rotating skimmers and served by two 600 GPM variable speed sludge return pumps; a 35,000 gallon filter dosing tank with two 833 GPM filter dosing pumps; two 156 square foot (ft) rapid sand filters served by a 781 cubic foot per minute (CFM) air scour blower; a 20,000 gallon mudwell with two 280 GPM return pumps; two 71,655 aerated sludge digesters with a decant pump; four 1,479 CFM rotary positive blowers, and an 800 CFM centrifugal blower serving the flow equalization, aeration, and sludge digester basins; a 50,000 gallon clearwell with two 957 GPM pumps; an effluent flow meter; a turbidimeter; an ultraviolet (UV) disinfection system with four banks each rated at 400,000 GPD; a stand-by power system consisting of a 45 kilowatt (kW) generator; a 115 kW generator; and all associated piping, valves, controls, and appurtenances; the WQ0002829 Version 3.0 Shell Version 200201 Page 1 of 13 continued operation ofa high -rate spray infiltration system consisting of: three 7.5 hp pumps; seven 15 hp pumps; a 1.35 acre high -rate spray infiltration area consisting of eight spray beds; and all associated piping, valves, controls, and appurtenances; the continued operation ofa low -flow infiltration pond consisting of: a 2,000 gallon pump station with two 7.5 hp pumps and alarms; a 2.1 acre infiltration pond (i.e., Pond 1); and all associated piping, valves, controls, and appurtenances; and the continued operation of a dedicated reclaimed water utilization system consisting of: an irrigation pump station with a 25 hp pump and a 3 hp pump; a 24.55 acre of spray irrigation area consisting of seven zones; and all associated piping, valves, controls, and appurtenances to serve the KDHWWTP, with no discharge of wastes to surface waters, pursuant to the application received May 6, 2022, and in conformity with the Division -approved plans and specifications considered a part of this permit. This permit shall be effective from the date of issuance through April 30, 2029, shall replace Permit No. WQ0002829 issued July 14, 2017, and shall be subject to the following conditions and limitations: I• SCHEDULES 1. Upon completion of construction and prior to operation of the permitted modifications, the Permittee shall submit an engineering certification from a North Carolina licensed Professional Engineer certifying that the permitted facility has been constructed in accordance with G.S. 143-215.1, Administrative Code Title 15A Subchapter 02T, this permit, and the Division -approved plans and specifications. For phased and partially certified facilities, the Permittee shall retain the responsibility to track further construction approved under this permit, and shall provide a final engineering certification upon project completion. Mail the Engineering Certification to the Division of Water Resources, Non -Discharge Branch, 1617 Mail Service Center, Raleigh, NC 27699-1617, or Non- Discharge.Reports(a)ncdenr.gov. [15A NCAC 02T .0116(a)] 2. The Permittee shall notify the Washington Regional Office, telephone number (252) 946-6481, at least two business days in advance of initial operation of the modified facilities so that the Division can conduct an inspection. [15A NCAC 02T .0108(b)(1)(B)] 3. The Permittee shall request renewal of this permit on Division -approved forms no later than November 1, 2028. [15A NCAC 02T .0105(b), 02T .0109] II. PERFORMANCE STANDARDS 1. The Permittee shall maintain and operate the subject non -discharge facilities so there is no discharge to surface waters, nor any contravention of groundwater or surface water standards. In the event the facilities fail to perform satisfactorily, including the creation of nuisance conditions due to improper operation and maintenance, or failure of the infiltration areas to assimilate the effluent, the Permittee shall take immediate corrective actions, including Division required actions, such as the construction of additional or replacement reclaimed water generation, utilization, or disposal facilities. [15A NCAC 02T .0108(b)(1)(A)] 2. This permit shall not relieve the Permittee of their responsibility for damages to groundwater or surface water resulting from the operation of this facility. [15A NCAC 02T .0108 b 1 A )] 3. Groundwater monitoring wells shall be constructed in accordance with 15A NCAC 02C .0108 (Standards of Construction for Wells Other than Water Supply), and any other jurisdictional laws and regulations pertaining to well construction. [15A NCAC 02C .0108] WQ0002829 Version 3.0 Shell Version 200201 Page 2 of 13 4. Effluent quality shall not exceed the limitations specified in Attachment A. [15A NCAC 02T .0705(b), 02U .0301] 5. Application rates, whether hydraulic, nutrient, or other pollutant shall not exceed those specified in Attachment B. [15A NCAC 02T .0705(m), 15A NCAC 02U .0401(g)] 6. All reclaimed water valves, storage facilities, and outlets shall be tagged or labeled to warn the public or employees that the water is not intended for drinking. [15A NCAC 02U .0403(b)] 7. All reclaimed water piping, valves, outlets, and other appurtenances shall be color -coded, taped, or otherwise marked to identify the source of the water as being reclaimed water as follows: a. All reclaimed water piping and appurtenances shall be either colored purple (Pantone 522 or equivalent) and embossed or integrally stamped or marked "CAUTION: RECLAIMED WATER - DO NOT DRINK" or be installed with a purple (Pantone 522 or equivalent) identification tape or polyethylene vinyl wrap. The warning shall be stamped on opposite sides of the pipe and repeated every three feet or less; b. Identification tape shall be at least three inches wide and have white or black lettering on purple (Pantone 522 or equivalent) field stating "CAUTION: RECLAIMED WATER - NOT DRINK". Identification tape shall be installed on top of reclaimed water pipelines, fasten dOat east every 10 feet to each pipe length and run continuously the entire length of the pipe; and c. Existing underground distribution systems retrofitted for the purpose of con�eving reclaimed water shall be taped or otherwise identified as noted in II.7.a. and II.7.b. This identification need not extend the entire length of the distribution system but shall be incorporated within 10 feet of crossing any potable water supply line or sanitary sewer line. [I5A NCAC 02U .0403(c)] 8. All reclaimed water valves and outlets shall be ofa type, or secured in a manner, that permits operation by personnel authorized by the entity that operates the reclaimed water system. [15A NCAC 02U .0403(d)] 9. Hose bibs shall be located in locked, below grade vaults that shall be labeled as being of non -potable quality. As an alternative to the use of locked vaults with standard hose bib services, other locking mechanisms such as hose bibs that can only be operated by a tool may be placed above ground and labeled as non -potable water. [15A NCAC 02U .0403(e)] 10. There shall be no direct cross -connections between the reclaimed water and potable water systems, unless such connection has been approved by the Department pursuant to 15A NCAC 18C .0406. [15A NCAC 02U .04030)] 11. Reclaimed water distribution lines shall be located at least 5 feet horizontally from and 18 inches below any water line if practicable. If these separation distances cannot be met, the piping and integrity testing procedures shall meet water main standards in accordance with 15A NCAC 18C. [15A NCAC 02U .0403(g), 02U .0403(h)] 12. Reclaimed water distribution lines shall not be less than 50 feet from a well unless the piping integrity testing procedures meet water main standards in accordance with 15A NCAC 18C, but in no case shall they be less than 25 feet from a private well. [15A NCAC 02U .0403(g), 3]and 13. Reclaimed water distribution lines shall meet the separation distances to sewer lines in accordance with 15A NCAC 02T .0305. [15A NCAC 02U .0403(g), 02U .0403(j)] WO0002829 Version 3.0 Shell Version 200201 Page 3 of 13 14. The compliance and review boundaries for the reclaimed utilization system permitted prior to September 1, 2006 (i.e., Pond 1 and utilization sites) are established at the property boundary. Any exceedance of groundwater standards at or beyond the compliance boundary shall require corrective action. Division -approved relocation of the compliance boundary shall be noted in Attachment B. Multiple contiguous properties under common ownership and permitted for use as a disposal system shall be treated as a single property with regard to determination of a compliance boundary. [15A NCAC 02L .0106, 02T .0105(h), 02H .0219(k)(1)(C)(0(111), G.S. 143-215.1(i), G.S. 143-215.1(k)] 15. The high -rate infiltration system (i.e., Basins 1-A, 1-B, 3, 4, 5, 6, 7-A, and 7-B) was individually permitted on or after December 30, 1983, and therefore has a compliance boundary that is either 250 feet from the infiltration area, or 50 feet within the property boundary, whichever is closest to the infiltration area. Any exceedance of groundwater standards at or beyond the compliance boundary shall require corrective action. Division -approved relocation of the compliance boundary shall be noted in Attachment B. Multiple contiguous properties under common ownership and permitted for use as a disposal system shall be treated as a single property with regard to determination of a compliance boundary. [15A NCAC 02L .0106(d)(2), 02L .0107(b), 02T .0105(h), G.S. 143-215.1(i), G.S. 143- 215.1(k)] 16. The review boundary for the high -rate infiltration system (i.e., Basins 1-A, 1-B, 3, 4, 5, 6, 7-A, and 7- B) is midway between the compliance boundary and the infiltration area. Any exceedance of groundwater standards at or beyond the review boundary shall require preventative action. [15A NCAC 02L .0106(d)(1), 02L .0108] 17. The Permittee shall apply for a permit modification to establish a new compliance boundary prior to any sale or transfer of property affecting a compliance boundary (i.e., parcel subdivision). [15A NCAC 02L .0107(c)] 18. No wells, excluding Division -approved monitoring wells, shall be constructed within the compliance boundary except as provided for in 15A NCAC 02L .0107(g). [15A NCAC 02L .0107] 19. Except as provided for in 15A NCAC 02L .0107(g), the Permittee shall ensure any landowner who is not the Permittee and owns land within the compliance boundary shall execute and file with the Dare County Register of Deeds an easement running with the land containing the following items: a. A notice of the permit and number or other description as allowed in 15A NCAC 02L .0107(0(1); b. Prohibits construction and operation of water supply wells within the compliance boundary; and c. Reserves the right of the Permittee or the State to enter the property within the compliance boundary for purposes related to the permit. The Director may terminate the easement when its purpose has been fulfilled or is no longer needed. [15A NCAC 02L .0107(0] WQ0002829 Version 3.0 Shell Version 200201 Page 4 of 13 20. The facilities herein were permitted per the following setbacks: a. The high -rate infiltration sites (i.e., Basins 1-A, 1-B, 3, 4, 5, 6, 7-A, and 7-B) were originally permitted June 21, 2004. The setbacks for infiltration sites originally permitted or modified from February 1, 1993 to September 1, 2006 are as follows (all distances in feet): i. Each private or public water supply source: ii. Surface waters: 100 iii. Groundwater lowering ditches: 200 200 iv. Surface water diversions (upslope): v. Surface water diversions (downslope): 200 vi. Each well with exception of monitoring wells: 200 vii. Each property line: 100 viii. Top of slope of embankments or cuts of two feet or more in vertical height: 100 ix. Each water line: x. Each swimming pool: 10 xi. Public right of way: 100 50 xii. Nitrification field: xiii. Each building foundation or basement: 20 xiv. Each impounded public surface water supply: 15 pp y' 500 xv. Each public shallow ground water supply (less than 50 feet deep): 500 Setbacks to property lines are not applicable when the Permittee, or the entity from which the Permittee is leasing, owns both parcels separated by the property line. [15A NCAC 02H .0404(g), 02H .0219(j)(5)] b. The reclaimed water irrigation sites were originally permitted June 16, 2006. The setbacks for reclaimed irrigation sites originally permitted or modified from June 1, 1996 to August 31, 2006 are as follows (all distances in feet): i. Surface waters classified SA: [15A NCAC 02H .0219(k)(1)(C)(i)] ii. Surface waters not classified SA: 100 iii. Each water supply well: 25 iv. Each non -potable well: 100 10 v. Each swimming pool: 25 c. The storage and treatment units were modified November 5, 2008. The setbacks for storage and treatment units originally permitted or modified from September 1, 2006 to August 31, 2018 are as follows (all distances in feet): i. Each habitable residence or place of assembly under separate ownership: 100 ii. Each on -property residential unit if the unit is to be sold: iii. Each private or public water supply source: 10 100 iv. Surface waters: 50 v. Each well with exception of monitoring wells: 100 vi. Each property line: 50 2 Habitable residences or places of assembly under separate ownership constructed after the facilities herein were originally permitted or subsequently modified are exempt from this setback. WQ0002829 Version 3.0 Shell Version 200201 Page 5 of 13 2 Setbacks to ro P perty lines are not applicable when the Permittee, or the entity from which the Permittee is leasing, owns both parcels separated by the property line. [15A NCAC 02H .0404(g), 02T.0706(d), 02T.0706(0, 02T.0706(g)] III. OPERATION AND MAINTEN ANCE RE UIREMENTS 1. The Pennittee shall operate and maintain the subject facilities as a non -discharge system. 02T .0700, 02U .0101] g[15A NCAC 2. The Permittee shall maintain an Operation and Maintenance Plan, which shall include: a. A description of the operation of the system in detail to show what operations are necessary for the system to function and by whom the operations are to be conducted; b. A description of anticipated maintenance of the system; c. Provisions for safety measures, including restriction of access to the site and equipment; and d. Spill control provisions that include response to upsets and b containment, and remediation, and contact information for regulatory agencies; bypasses, including control, personnel, emergency responders, and [15A NCAC 02T .0707(a), 02U .0801(a)] 3. Upon the Water Pollution Control System Operators Certification Commission's classification of the subject non -discharge facilities, the Penn ittee shall designate and employ a certified operator in responsible charge (ORC),ne(WPCSOCC) .0 their back-up shall operate and visit the facilities oas required ed byed perators as back-up ORCs. The ORC or theor the WPCSOCC. [ISA NCAC 02T 17] 4. An operator certified by the Water Pollution Control System Operators Certification Commission (WPCSOCC) ofa grade equivalent or greater than the facility classification shall be on call 24 hours per day. [15A NCAC 02U .0401(e)] 5. The Permittee shall maintain vegetative cover on the irrigation sites, such that crop health is optimal, o allws even effluent distribution, and allows inspection of the irrigation system. [ISA NCAC 02U .0806. The Permittee shall take measures to prevent effluent ponding in or runoff from the infiltration and irrigation sites listed in Attachment B. [15A NCAC 02T .0707(c), 02U .0801(c)] 7. The Permittee shall not irrigate treated effluent during inclement weather, or when the soil is in a condition that will cause ponding or runoff. [15A NCAC 02U .0401(k)] 8. All infiltration and irrigation equipment shall be tested and calibrated once per permit cycle. [15A NCAC 02T .0707(d), 02U .0801(d)] 9. Only ted uent from the Attachment B. [15A NCAC 02T 00701, 02U .0101] HWWTP shall be infiltrated or irrigated on the sites listed in e10. The Permittee shall not allow vehicles or heavy machinery on the infiltration or irrigation areas, except during equipment installation or maintenance activities. [15A NCAC 02T .O 11. The Pennittee shall prohibit public access to the wastewater treatment, storage, and infiltration tra] facilities. [15A NCAC 02T .0705(p), 02U .0402(e)] and 12. Public access to reclaimed water utilization sites shall be controlled during active site use. Such controls may include the posting of signs showing the activities being conducted at each site. [15A NCAC 02U .050I (a)(2)] WQ0002829 Version 3.0 Shell Version 200201 Page 6 of 13 13. The Perrrittee shall dispose or utilize 02T .0708, 02T .1100, 02U .0802]• generated residuals in a Division -approved manner. [15A NCAC 14. The Permittee shall dive notrt or bypass untreated or (•) 02U.0402(g)] partially treated wastewater from the subject facilities. [1SA NCAC 15. Freeboard in the0infiltration .0401(basin (i.e., Pond 1) shall not be less than two feet at any 02d(ein.04 16. A gauge to monitor waste levels in the infiltration basin r.e. time. [I SA NCAC e shall have readilymnvisible wast permanent infiltration s followinghall( nth Pond 1) shall i becr provided. indicating This elevations: maximum li g at iect or tf th stea foot i liguidnts, vume; minimum liquid level at the bottomgofdthe tem at the to of mtop imuof dam. p the e Volumry liquid storage the e [15A NCAC 02T.0707 temporary liquid storage volume; and the lowest 17. A (�, 02U.oso1(t)] point on protective vegetative cover shall be established erosion control areas, svegetative water diversions, and earthed embank and maintained maximum allowable water on all outside.e., to pipee runs, maxi wood temporary storage elevation on the inside ofthe rembankment e Trees, shrubs, to otherwoodyshall vegetation shallpt not be or llowed tto otrolled grow on the earthen dikes or embankments. rgarthen embankments U .nk 0 and accessible. [15A NCAC 02T. 18. Metering 0707(g), g equipment shall be tested and calibrated annually. [15A NCAC 19. An automatically activated standby 02T.0707 d be on site and o power source capable of O, nU units shall be tested weekly operational at all times. If a generator is employedp as an a alls essential treatmentwrsupply, shall Y by interrupting the primary power source. [1 SA NCAC 02 Tate power 20. If turbidity0705 k it shall routed to thexcieds 100 TUs or if spray all )' effluent shall l be permitted pathogen levels cannot problems s,sshall be reclaimed water generation system have beendcorr cted a 1 13 until the U.0402 21. The infiltration areas shall be cleaned at least[15,q NCAC 02U • associated with the 0402(d)] may impede the areas hall clean. once perpermit and shopll be avtration topr tce Division nupn lbmaintainedcycle to removetthedeposited cility materials years,that Cleaning records shall a at facility for five number (252) made946available shall be notified prior to request each cleaning. Regional Office, 22. Spray g• [15A NCAC 02T. telephone p y beds shall be raked as needed and all vegetation shall be kept out of the spray 0 beds att] The spray beds shall also be raked when solids and ruts develop infiltration. [15A NCAC 08 all times. (b)(1)(q)] within the beds, which results in uneven 23. The application of chemicals to the high-rate02Tchemicals infiltration spray P y beds is expressly prohibited [15A 9 measures shall be taken to divert sto infiltration basin (i.e., Pond 1), and the dedicated reclaimed irrigation .0108(6)(1)(Mrmwater from the high -rate infiltration sites, the g areas. [1SA NCAC 02T 25. Continuous online monitoring and recording prior to storage, distribution, or utilization of eclaimedfor rwate particle count and flow shall be 26. The Permitter shall provide notification to the [ A NCAC 02U , provided 0401(b)] ed water, and that lprovide water is not intended for ledrinking. public andits Such notifyeesication about the use of provided to employees in a language they can understand. Such notification shall be provided to [15A NCAC 02U .0501(a)(2)] WQ0002829 Version 3.0 Shell Version 200201 Page 7 of 13 27. The Permittee shall develop ent an education about the proper use ofreclaim d�watermEducational m material shall be provided to all reits sidents and/or other facilities provided with reclaimed water, and these materials hall be maintained and to inform users employees consistent with the reclaimed water uses. All educational materials shall be made available to the Division upon request. [15A NCAC 02U.0501(a)(4)] IV. MONITORING AND REPORTING RE UIREMENTS 1. The Permittee shall conduct and report any Division required monitoring necessary to evaluate this facility's impact on groundwater and surface water. [15A NCAC 02T . 2. ADivision-certified laborato 0108(c)] I SA shall conduct all analyses for the required effluent, [ NCAC 02H .0800] groundwater, and surface water parameters. 3. Flow through the treatment facility shall be continuously monitored, and daily reported on Form NDMR. Facilities with a permitted flow Tess than 10,000 flow from water usage records flow values shall be flow fro provided the water source is metered. [15A NCAC 02T .0105 k , mayPD estimate their 4. The Pennittee shall monitor the treated effluent at the frequencies and locations for the a) 02T specified in Attachment A. [15A NCAC 02T.0108(c)] q parameters 5. The Permittee shall maintain records tracking the amount of effluent infiltrated. These records shall include the following information for each infiltration site listed in Attachment B: a. Date of infiltration; b. Volume of effluent infiltrated; c. Site infiltrated; d. Length of time site is infiltrated; e. Loading rates to each infiltration site listed in Attachment B; and f Weather conditions. [15A NCAC 02T.0108(c)] 6. The Permittee shall maintain records tracking the amount of reclaimed water irrigated/infiltrated. These records shall include the following information for each irrigation site listed in Attachment B: a. Date of reclaimed water utilization; b. Volume of reclaimed water irrigated/utilized; c. Site irrigated/utilized; d. Length of time site is irrigated/utilized; e. Continuous weekly, monthl , sites; y and year-to-date hydraulic (inches/acre) loadings for irrigation f. Weather conditions; and g. Maintenance of cover crops. [15A NCAC 02T .0108(c)] 7. Freeboard (i.e., waste level to the lowest embankment elevation) in the infiltration basin i e shall be measured to the nearest inch or tenth ofa foot, and recorded week] shall be ( Pond 1) maintained for five years, and shall be made available to the Division upon request. [15A NCAC 02T .0108(c)] Y• Weekly freeboard records WQ0002829 Version 3.0 Shell Version 200201 Page 8 of 13 8. Three copies of all monitoring data (as specified in Conditions IV.3. and IV.4.) PPI, three copies of all operation and utilization records (as specified in Condition IV.6) on Form NDAR-1 for every dedicated utilization site listed in Attachment B, oniForm NDMR forn and disposal records (as specified in Conditions IV.5. and IV.7,and three copies ef all operation site in Attachment B shall be submitted on or before the last da occurred during the monitoring) on FOB NDAR-2 for every infiltration of the ectivi month, monitoring reports are sot ll required documenting the f the following month. If no absence 1y. All information shall be submitted to the following address: Division of Water Resources Information Processing Unit 1617 Mail Service Center Raleigh, North Carolina 27699-1617 [15A NCAC 02T .0105(1)j 9. Pursuant to G.S. 143-215.1C(a) the Permttee shall provide to its users and the Division of Water Resources an annual report summarizing the performance of the reatment, high -rate infiltration, and reclaimed utilization facility wastewater in federal or State laws,s regulations, and the extent to which the facility hasty violated this permit, oror be prepared on either a calendar fiscal year basis and shall be provided no later than 60 days after rules related to the protection of water quality. This report shall the end of the calendar or fiscal year. Two copies of the annual report provided to the Permittee's users shall be submitted to: [G.S. 143-215.1 C(a)] Division of Water Resources Water Quality Permitting Section 1617 Mail Service Center Raleigh, North Carolina 27699-1617 10. The Pennite° shall maintain a record of all residuals removed from this facility. maintained for five years, and shall be made available to the Division upon request. This record shall include: 1y. This record shall be a. Name of the residuals hauler; b. agring to accept the residuals; Non -Discharge permit number authorizing the residuals disposal, or a letter from a municipality c. Date the residuals were hauled; and d. Volume of residuals removed. [15A NCAC 02T .0708(6), 02U .0802(b)] 1 1 • A maintenance log shall be kept at this facility. be made available to the Division u This log shall be maintained for five years, and shall pon request. This log shall include: a. Date of flow measurement device calibration; b. Date of infiltration equipment calibration; c. Date of turbidimeter calibration; d. Date and results of power interruption testing on alternate power supply; e. Visual observations of the plant and plant site; f. Record of preventativePP y� Record spray bed raking, maintenance (e.g., changing g and cleanings, etc.); and g of equipment, adjustments, testing, g. Record of all discharges of reclaimed water to surface waters or the land surface, including of occurrence, estimated volume, and corrective action taken. [15A NCAC 02T .0707(i), 02U .0801(h)] the date 12• Monitoring wells CW-A,frequeorins and for the CW-C' CW-D CW-F CW-G, parameters specified in Attachment B-I, and CW_g_I shall be sampled at the well abandonment forms and monitorinAll e in well number and theh forms nomenclature as rovided in Attachment C andaFi ure shall] refer to the ermit number and well WQ0002829 Version 3.0 [ISA NCAC 02T.0105 Shell Version 200201 (m)] Page 9 of 13 13. Two copies of the monitoring well sampling and analysis results shall be submitted on a Co Monitoring Form (GW-59), along with attached copies of laboratory working day of the month following the sampling Compliance ol include this e P g month. The Compliance Fbefore the last shall nform shall be submitted the apprth opriate h set w lidentification number, Monitoring nnd e GW-59a csubmitted to the following results. All information shallbe g address: [15A NCAC 02T .0105(m)] 14. Noncompliance Notification: within 24 hours of first knowledge of the following: The Pennittee shall report to the Washington Regional Office, telephone number (252) 946-6481, a. Treatment of wastes abnormal in quantity or characteristic, including the known hazardous substance. b. Any passage of a process unit (e.g., atreatme t. mechanical, electrical, etc.) rendering the facility{❑ c. Any facility failure resulting in a discharge to surface waters. capable of adequate wastewater d. Any failure resulting in a discharge of reclaimed water directly to surface waters or any tted release of reclaimed water to land surface greater than or equal releases less than 5,000 gallons to land surface shall be documented by the Pennittee in accordance with Condition IV.I 1. to 5,000 gallons. Unpennitted g. but do not require Regional Office notification. e. Any time self -monitoring indicates the facilityhas limitations. tions. gone out of compliance with its f. Pondingin or Permit runoff from the infiltration and irrigation sites. g. Effluent breakout from the infiltration basin (Le., Pond 1). Emergencies requiring reporting outside normal an)l bus5s hours(80shall8 call6 , the (919) 73 Emergency noncompliance notificaat tionsshallfile a writhone number 8ten 662-7956,reporttothe Washington days of first knowledge bof ons occurrence,or al Office within All ensure the problem does not recur. and this report shall outline the actions'proposed ors taken to [15A NCAC 02T.0108(b)(1)(A)] Division of Water Resources Information Processing Unit 1617 Mail Service Center Raleigh, North Carolina 27699-1617 WO0002829 Version 3.0 Shell Version 200201 Page 10 of 13 V. INSPECTIONS 1. The Permittee shall perform inspections and maintenance to ensure proper operation of the reclaimed water generation, utilization, and infiltration facilities. [I5A NCAC 02T .0707(j), 02U .0801(i)] 2. The Pennittee shall inspect the reclaimed water generation, utilization and infiltration facilities to prevent malfunctions, facility deterioration, and operator errors that may result in discharges of wastes to the environment, threats to human health, or public nuisances. The Pennittee shall maintain an inspection log that includes the date and time of inspection, observations made, repairs, or corrective actions taken. The Permittee shall maintain this inspection log and for a period of five years from the date of the inspection, and this log shall be made available to the Division upon request, [15A NCAC 02T .0707(i), 02T .0707(j), 02U .0801(i)] 3. Division authorized representatives may,P quest. pect any property, authorized r placersrrepresdentatives to upon presentation of credentials, enter and ins facilities permitted herein at any reasonable time for determ watnir generation, and ng compliance with this eDi anon authorized representatives may inspect or copy records maintained under the terms and conditions of this permit, and may collect groundwater, surface water, or leachate s P nmt. Division VI. GENERAL CONDITIONS amPles. [G.S. 143-215.3(a)(2)] 1. Failure to comply with the conditions and limitations contained herein may subject the Permittee to a Division enforcement action. [G.S. 143-215.6A, 143-215.6B, 143-215.6C] 2. This permit is effective only with respect to the nature and volume of wastes described in the e application, and Division -approved plans and specifications. [G.S. 143-215.1(d)] 3 • Unless specifically requested and approvedin this opera p there are variances to administrative codes permit n or general statutes governing the construction or operation of the facilities permitted herein. []SA NCAC 02T.0105(n)] 4. The issuance of this permit does not exempt the Pennittee from complying regulations, or ordinances that other jurisdictional government agencies(e.g., may require. [15A NCAC 02T .0105 c with all statutes, ides, ( )(6)] local, state, and federal) 5. If the permitted facilities change ownership, or the Pennittee submit ae permitmitt d modification a e ow on Division -approved changes their name, the shall comply wall allth terms and conditions of this permit until the e pProved forms. l5erms ems• The Pennittee comply 143- P permit is transferred to the successor -owner. [G.S. 143- 6. The Permittee shall retain a set of Division -approved plans and specifications for the life of the facilities permitted herein. [15A NCAC 02T .0105(o)] 7. The Pennittee shall maintain this permit until the proper closure of all facilities permitted herein, or until the facilities permitted herein are permitted by another authority. [15A NCAC 02T .0105(j)] WQ0002829 Version 3.0 Shell Version 200201 Page 11 of 13 8. This permit is subject to revocation or modification upon 60-day notice whole or part for: from the Division Director, in a. violation of any terms or conditions of this permit or Administrative Code 02T; Title 15A Subchapter b. obtaining a permit by misrepresentation or failure to disclose all relevant facts; c. the Permittee's refusal to allow authorized Department employees upon res i• to enter the Permittee's premises where a system is located or where presentation of credentials: to be kept; any records are required b ii. to have access to any permit required documents and records; iii. to inspect any monitoring equipment or method as required in this e iv. to sample any pollutants; p rmit; or d. the Permittee's failure to pay the annual fee for administering and compliance e. a Division determination that the conditions of this a monitoring; Administrative Code or General Statutes. Carolina or permit are in conflict with North [15A NCAC 02T .0110] 9. Unless the Division Director grants a variance, expansion of the facilities permitted herein shall not occur if any of the following apply: a. The Permitter or any parent, subsidiary, or other affiliate of the Pertnittee has been convicted of environmental crimes under G.S. 14or oB prosecuted under G.S. 143-215.6B , or under Federal law that would otherwise be exhausted. pu, and all appeals of this conviction have been abandoned or b. The Permitter or any parent, subsidiary,without or other properly closing the the ili ittee has previously abandoned c. ty. The Permitter or any parent, subsidiar y, or otheraof the tnittee has not paid a civil penalty, and all appeals of this penal ty abandoned been abann doneone d or exhausted. d. The Permitter or any parent, subsidiar y, or other affiliate of the Permitter is currently not compliant with any compliance schedule in a permit, settlement agreement, or order. e. The Permitter or any parent, subsidiary, or other affiliate of the Permitter has fee. [15A NCAC 02T .0120(b), 02T .0120(d)] not paid an annual 10. This permit shall not be renewed if the Permittee or any affiliation has no [15A NCAC 02T .0120(c)] t paid the required annual fee. Permit issued this the 29th day of July 2022 NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION dz Richard E. Rogers, Jr., Director Division of Water Resources By Authority of the Environmental Management Commission Permit Number WQ0002829 WQ0002829 Version 3.0 Shell Version 200201 Page 12 of 13 L NVId A1num 11V81 Saba VINISerlA H1nos d06 rmario fuxov _ S3WOHNMOI 3Z3388 NV330,101 NVld A111110 L 1IV211 3Nyp VIN1981A H1f10S ZOb Vxnoay xwax � S3WOHNMO13Z33218 NV3OO I Ma pN '$TMH 1N3p illy iSgi 'p'd 9NIA3AN11g ONY 91,4I2133N19143 S'l'd ' 3"d 'NOSN18021 'M 13VH9114 NY -Id 9NiOV119 NVId 33/03S llval Savo VINI9211n Hlflos ao6 t6[Z �x STLx 11.,30ZSIE iNM Krd 0NIA3S 0NV 9 ABNNI1133NIDN3 'S'l'd "3'd 'NOSNIBON 'M 13VHDIN L NVId 9NIQV219 NV'Id 33/03S ',Ancona µWON S3WOHNM01 3Z3388 NV300 °-•: ,.ti APcjz 3 s e 0-m3a Tim zset z0d 9NIA31ly�5 ONtl ONI1133N19N3 'S'l'd "3'd 'NOSNIBOH 'M 13VH0I14 L NVId 1IV130 11V211 Java VINI98IA H1f os Z06 NVId 2131VM31SVM 1IVal Sava Hlnos ZO6 A� IN III ieif t i 11 Pep I ,I 11 Id °1 1;Ilt(IIJIdi 1h!11 .II a t;iJll pi 11/1io 'f'i!du1 C ' 10 9 $ l!!I!Id1l111 sill +II{ 11p 1 9,6U ON Vila lwO ZSo) XOO p TIN ONIA3ANN5 ONV ONIN33NION3 .S'1"d " 3 d 'NOSNI8021 'M l3VHoI4 NV18 2131VM31SVM SNOISIA3N 1IV81 3NV0 VINI98IA H1110S ZO6 VIG76OVJ NWON ADM) 3NYp S3WOHNM01 3Z3388 Nd300 P 9tau 96tZ f5TIo# TA JN 0 alO lMM $NIA3Alfls UNV 9NIa33N,'ON3 S l'd '3'd 'NOSNI9021 'M 13VHDIW L NVId 831VM31SVM T1111111111_ie 11� 1,1, I, IIIIII lb, . i„.1111l,_ 11il i 111111 111111,11111 9BBB09B0B8BB NREBII NERI998998EZEll 000003iQO11Q1DO]Jf711 nuumuj.iuuin P ,. Mg ni-w : y- m,,,,. B06t2 9x SHiOM a TAN LSFIC MOONIA3ANfS ONV 9NI2133N19N3 'S'1'd "3'd 'NOSNI8O3 'M 13VH)IW NVId 2131VM31SVM SN0131Aa8 1 1117111 Sava VINI081A Htnos 306 TNfl081,3 HUM,' ALL10.l 9NV0 VIM 3330 TIM S3WOHNM01 3Z3388 NV930 is = m S pl J P wgewa+wb+h•Po�.ww.. Tu -:a.> rhea OM STIw 1039 TMM MSS[ MOr .90 ONIARAMAS (INV ONIM33NI9N3 'S'l"d •'3"d 'NOSNI13021 'M 13VH3IW NVId JNIJH911 { GM \ . . f • • t '"d 11'011 RelVa VINIONIA H1f10S ZOb MNf1WV3 RUIN AFN003 SWYo S/=DI 'IIASQ TiIX SJWOHNM01 3Z33218 NV3D0 r a� t. • O'• e e a• " s A • \\-:Rs t. __ ESP ice. SITE STATISTICS Ni rc 15 41,00 0 1 O 3j 1 81 �4 13 gIF 315 tr3 901 5 g1 D Y1 If J E P -es ORE ON 01104YIYB 149) 7N30 TMM EWE MOB '0'd 9NIA3A909 ONV 910933N19N3 'NOSN18021 'M 13YH0IW S31IdOd4 83M3S ra•mam saw. SNOISIA3N llt/al Sava VIN19tA Hlnos ZO6 YAT19NY3 MOOS J1A003 311110 SR01 7100 TOM S3WOHNM01 3Z33218 NV3DO as N S a 5 0000.8 vS J113X3A7d d0 9903 cy.a (r 13.019 719999 995) 3031703 .Zr SEdf+1 YIS AAV1-J0-L19RI 9r'09+1 Y1S 11174 34773 .91'I - 9919 J7 919 .09.0 - 'ATE( AN WINO 9JS MUMS Jd[f L ,OrZ - UV 1110 ANI 4 6 .0S'O -. Z719 Nl AN1 y 8.—•—_----00'00+0 YJS r /AR m c a OS'{BH YJS JN3119AYd d0 9003 • S P10 ,090 - A9'13 J00 Ale - A877 Ill AN1 . .O00 - A979 AM wEL; AIM J00 Y10 ,09Z • 'AM 910 414 .0011- 4.412 9B'rs.1 Yts r 1MA .09E - UPI JIM A# ,01E - 0379 1O AM -__ __000 • A9191179 01 E2.0 Y[S S JAA • AiWK vS it �e p.9 21115. p9G .09'9 ,69'[ ,99[ .010 .26'G 0 Mr! .BB'[ .6["1 .00 B a N O O + SANITARY SEWER TIE IN 1k 9 0 P Ba6(Z 91JN '9122 1130 1121 Z99Z 111 0NIA3Atl05 ON19 0NItl33NI0N3 "S•1"d "3"d 'N0SNI800 "M 13V140144 S3'IIJOe1d 2:13MJS mew Yv SN013100N 0 1IV211 Sava VINI92:1IA Hinos Z06 YEPIL91I3 391000 AWOa, 3EY0 STEX 7N30 7I13I S3WOHNM01 3Z332i8 NV3D0 09 4 .002 = A3i3 0410 AEI ,009 = A2R3 MY YL aa.a XIS L /MR .09E 11319100 AIR .0LS = A917 XI AA7 _-___ .009 •_1319 RIX 08 rc.I w9 a ha 1372 U10 AEI .009 = ATI3 MN aA 0a.0 US 1 /MX .00 S = 'A377 100 AID .009 - A313/1M it 90E2.2 YLS S /XR „ws E 8 .09r - A313 100 AEI ec H ,OL S - 2373 M/ Ala 24 y 009 - A313 M7 2029.1 YLS 2 /101 LYtN .000 = A373 1110 AEI .009 • 2313 RI9 E axaE 4202 DOSE 010E Lm mna a>wa 008E 0A31 1YbE era 2802.0 000 1 /101 g :I tt45 3xm a5aa S s 3xaa a'sa El OA. aYE 7.832 aYE nv.na aS.E r o g 09 .291 .000 .061 .00e .09'L .S2 .00'0 .000 ,29L .00'0 0 0 J 7 1l9 0 0 :nnoH 13011!WJ d 40 % ZZOZ (No %06 / %08 >) :mold pau.!Lw d Q O O o z O v D c D N NJ O O Nj O O 0 0 O N N 1"' 1� 1-4N NJ r•J I-, I—'N F-, N W 4N 0 N N I-h IM-h NJ v ivw U' Cn co D V M T 0 £EEE'EE9Z9I 8tSE-6IDSIZ N Ol W 0 0 L8E817SEEEE 6ZI"9ISS9E L60L'8E8ESZ EEEE'EE96EZ ZE06'ZI9SLI T fD Cr N O NJ 6Z1I'LSEESI 1LL9-60LI9I :aol Mold AIJeaA ageJanv # 4pAnad 'atueu Ampe j 6Z8Z000bM 0ll `d1MMHQN