Subject: Compliance Sampling Inspection
Marshall Steam Station
NPDESTermit No. NC0004987
Catawba County, N.C.
Dear Mr. Stowe:
Enclosed is a copy of the Compliance Sampling Inspection Report,for the inspection
conducted at the,subject facility on June 7, 2010 by Ms. Donna Hood and Mr. Wes Bell of the
Mooresvtle'Regional Office and,accompanied by Ms Autumn Romanski of the Raleigh
Regional Office. Please advise the facility's Operator -in -Responsible Charge of our findings by
forwarding a copy of the enclosed report. The results of the analyses collected by DWQ Staff
will be se -fit to you under separate cover.
'-The facility has several stormwater outfalls that discharge'into waters of the State
Although .he facility operates under an internal stormwater management program, potential
exposures to the,stormwater runoff as a result of the facility',s operations exist. Following
discussions with the Division's Stormwater Permitting Unit, the stormwater discharges will need
to be covered under an individual stormwater permit. A completed permit application and
supporting documentation (including fee) should be, mailed to the attention of Bradley Bennett,
Supervisor, DWQ/Stormwater Permitting Unit, 1617 Mail Service Center, Raleigh, N.C. 27699-
1617. The permit application and supporting information can be found at the following website
address. http://portal.ncdenr.orgjweb/wq/ws/su/npdessw#Generdl Permits NPDES. The
application and supporting documentation (including fee), should be submitted, to the Division
within 30 days'following receipt of this report.
Mooresville Regional Office
Location 610 East Center Ave, Suite 301 Mooresville, NC 28115 One
Phone (704),663-16991 Fax (704)'663.60401 Customer Service `7-87,7.623 6748 NorthCarolina
Internet. http/lportal'ncdenrorglwebNuq
An Equal Opportunity 1 ARrrnabve Action Employer— 50% Recycled/10% Post Consumer paper �atlrra!!r�
'Mr. Allen Stowe
Page Two
July 8, 2010
Should you have questions concerning this report, please do not hesitate to contact Mr.
Bell at (704) 663-1699 or Mr Bennett at (919) 807-6378.
Sincerely,
Robert B. Krebs
Regional Supervisor,
Surface Water Protection
Enclosuie:
Inspection Report
cc:
Catawba County Health -Deportment
a
Q
- United States Environmental Protection Agency Form Approved
EPA Washington, D C,20460 OMB No 2040-0057
Water Com o Mance Inspection Report Approval expires 8-31-98
Section A National Data System Coding (i_e , PCS)
Transaction Code NPDES yr/moiday Inspection Type Inspector Fac Type
1 17,11 2 JUS 31 NC10004987 Ill 121 10/06/07 117 181 SI 19L 20IU�
Remarks
2111111'illl-Illllli Illllflll`IIIIIIIIIIII'1111111116
Inspection Work Days Facility Self'Monttonng,Evaluation,Rating 61' QA -
671' 1 :5 169 701 41 711 NJ 721 NJ 73I I 174 751 I I 1 1 I I 18d
W
Section B Facility Data
Name and location of Facility, Inspected (For Industrial Userscdischarging,to'POTW, also include
Entry Time/Date
Permit Effective Date
'POTW name:and NPDES permit Number)
10.00 AM 10/06/07
09/07/01
{star&hall Steam `Station
Exit Time/Date
-Permit Expiration Date
NC Hwy- 150 -•
Terrell NC 28682
09.00 PM 10/06/07
10/04/3Q
Name(s) of Onsite Representative(s)lrities(s)/Phone and Fax Number(s)
Other Facility Data
Donna Lee Burrell/ORC/828-,,478`7820/
Jin nie Allen 9towe//704-382-4309 /
Name, Address of Responsible,Offiaal/Title/Phone and Fax Number
Contacted
Jimmie Al^Len Stowe"'26 S,Chruch St Charlotte NC
282011002//7041'-382-4309/704382984Q Yes
' Section,C' Ate -as Evaluated During Inspection (Check only those areas evaluated),
Permit Flow Measurement Operations & Maintenance Records/Reports
Self' Monitoring Program ■ Sludge Handling Disposal Facility Site Reyiew ® EflUent/Receiving Waters
Laboratory
Section D Summary of Findift /Comments Attach additional sheets of narrative and checklists as necessa
(See'attachment summary)
Name(s) and Signature(s) oPInspecI.. (s) Agency/Office/Phone and Fax Numbers Date
/
Wesley N Bell ��f �,G� MRO WQ//709-663-1699 Ext, 2192/ 7/ /te/! 0`
Donna Hood' MRO WQ//704-663-1699 Ext 2193/
tSi nature"of Management Q A evl wer Agency/Office/Phone and Fax Numbers Date
'T u
Marcia Allocco MRO WQ//704=663-1699 Ext 2204/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete
Page # 1
NPDES yr/mo/day Inspection Type
3I NC0004987 I11 121 10/06/,07 117 18I S
(cont ) 1
Section D Summary of Finding/Comments (Attach additional sheets olenarrative and checklists as necessary)
SUMMARY SECTION cont'd
The faclllty'has several stormwater outfalls that discharge directly Into waters of1the State Potential
stormwater exposures (from raw materials, by-products, metal storage dumpsters, etc ) as a result of the
facility's operations were observed The facility staff operate under a l Internal stormwater management
program that Includes the, identification of all stormwater outfalls and their respective,dralnage areas The
Division's Storm -water Pefmltting Unslt.has Indlcated,to MRO`staff that the facility will need to apply for
coverage under an Individual stormwater permit
FACILITY SITE REVIEW
The Division Issued an ATC on 4/27/10 for'the Installation of vertical flow wetland ,(VFW) cells containing
spent mushroom, compost for, the removal of selenium These VFW wetland cells will replace the existing
wetland cells 1A„ 1 B, and 1 C These wetland cells (1A, 1 B, 1 C) have been taken off line and the vegetation
from one,of,these wetland cells has already been removed The facility staff Indicated that the -vegetation
would be composted and, placed back Into an on-line wetland cell(s)
SLUDGE DISPOSAL
Fly ash, clarifier sludge, spec and off spec gypsum, etc are disposed Into the permitted landfills located
on-site The spec gypsum Is also reused'In the National Gypsum Company's manufacturing process
Page # 2
Permit NC0004987 Owner --,Facility MarshaWSteam Station
Inspection Date 06/07/2010 Inspection Type Compliance Sampling
Permit Yes No NA NE
(If the present permit expires in 6 months or less) Has the permittee submitted anew applications - e n n n
Is the facility as descrnbediin the permits ■ n n n
#,Are there any special conditionsJor the permits n n ■ n
Is access to the plant site restricted to the general publics ■ n n n
Is the inspector granted access'to all areas for inspection? ® n n n
Comment The subject permit,eXpired on 4`/30/10 and a permit renewal application
was received by the Division on 11/2/09 The facility is classified as a
Physical/Chemical, I treatment system, however, the facility also uses a constructed
Wetland, (biological) treatment�system for the, uptake/reduction of selenium The
`Division's Technical Assistance & Certification Unit has been forwarded this information
to determine if an,additional classification (Grade I Biological) is warranted The TACU
staffwill,provide a decision following the review of the,facility's treatment system -See
"Summary" for additional permitting comments
Record Keeping
Yes No NA NE
'Are records kept and maintamed;as required by the permit? _
■ _ n. n o
Is, -all required information'readily available,, complete and current?
■ 0 n n
Are aWrecords maintained for 3 years (lab reg required 5 years)?
■ n n n
Are analytical results consistent'witti data reported on DMRs?
■ n n n
Is the chain -of -custody complete?
n n n
Dates, times and location of sampling
'Name of individual performing the sampling
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
Transported CM
■
Are DMRs complete do they include,all permit parameters?
■ n n n
Has,the,facdity submitted its annual compliance repoit to,users and DWQ?
n n ■ n
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift?
n n ■ n
Is the ORC visitation log available and current?
■ n n n
Is, the ORC certified at grade equal to,or higher than the facility classification?,
■ ,n ,❑ 'n
Is,the backup operator certified, at one grade less or greater than the facility classification?
■ n n n
Is a copy of the current NPDES permit available on site?
t n n n
Page # 3
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? n n ■ n
Is sample collected below all treatment units? ■ n to n
Is°proper volume collected? ■ n n n
Is,the'tubing clean? n n ■ n
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees Celsius)? n n ■ n
Is the facility sampling performed as required by the permit (frequency, sampling type representative)? ■ n n n
Comment The subject permit requires effluent grab samples
Operations & Maintenance Yes No NA NE
Is the,plant generally clean with acceptable housekeeping? ■ n n n
Does the facility analyze process,control parameters, for ex MLSS, MCRT, Settleable Solids,,pH, DO, Sludge ■ n Q n
Judge, and`other that are applicable?
Comment The treatment system appeared to be properly operated and well'
maintained No chlorine is:added to the once, through, codling water'(Outfa111001) The
facility staff use.either Sodium hydroxide or CO2 for pH adjustment (as -needed basis) in
the ash basin discharge (Outfall 002) Process control monitoring, Includes pH
measurements at different treatment processes/units and in the receiving stream
adjacent to Outfall 002
Page # 4
s
Permit NC0004987 Owner - Facility Marshall Steam Station
Inspection Date 06/07/2010 Inspection Type Compliance Sampling
Record Keeping
Yes No NA NE
Facilit`y'has copy ofaprevious year's Annual Reporton file for review,?
n n ■ n
Comment The facility's records were organized and well maintained Discharge
Monitoring Reports (DMRs) were reviewed for,the,penod April 09, through May,10 No
effluent limit violations were reported and all monitoring frequencies were correct
Laboratory
Yes No NA NE
Are field parameters performed by certified `personnel or laboratory?
■ n n n
Are all other parameters(excluding field parameters) performed by a certified lab?
■ n n n
# Is'the facility using a contract lab?
■, n n n
# 4s proper,temperature set forsample,storage (kept at less than or equal'to 6 O,degrees Celsius)?
■ n n n
Incubator (Fecal Coliform) set'to 44 5-degrees Celsius+/- 0 2 degrees?
n .n ■ n
Incubator (BOD) set to 20 0 degrees Celsius +/- 1 O degrees?
00 ■ 'n
Comment. On-site field analyses'(pH and temperature) are performed under
laboratory certification #5155 ,The Duke Power Analytical Laboratory (Certification
#248) and the contracted services of ETS, Inc (Chronic Toxicity) also provide analytical
support The,pH meter,appeared to be properly calibrated (an, d,documented) The
thermocouples (temperature - Outfall 001) are also calibrated at a minimum of once per
year (and documented)
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? n n ■ n
Is sample collected below all treatment units? ■ n to n
Is°proper volume collected? ■ n n n
Is,the'tubing clean? n n ■ n
# Is proper temperature set for sample storage (kept at less than or equal to 6 0 degrees Celsius)? n n ■ n
Is the facility sampling performed as required by the permit (frequency, sampling type representative)? ■ n n n
Comment The subject permit requires effluent grab samples
Operations & Maintenance Yes No NA NE
Is the,plant generally clean with acceptable housekeeping? ■ n n n
Does the facility analyze process,control parameters, for ex MLSS, MCRT, Settleable Solids,,pH, DO, Sludge ■ n Q n
Judge, and`other that are applicable?
Comment The treatment system appeared to be properly operated and well'
maintained No chlorine is:added to the once, through, codling water'(Outfa111001) The
facility staff use.either Sodium hydroxide or CO2 for pH adjustment (as -needed basis) in
the ash basin discharge (Outfall 002) Process control monitoring, Includes pH
measurements at different treatment processes/units and in the receiving stream
adjacent to Outfall 002
Page # 4
Effluent Pipe Yes No NA _NE
Is right of way to -the outfall properly maintained? ■ n n n
Are the receiving water free of foam other than trace lamounts,and other debris? ■' n n 'n
If effluent (diffuser pipes are required) are they operating properly? n Q ■ n
Page;# 5
Permit NC0004987 Owner - Facility Marshall Steam Station
"
Inspection Date 06/07/2010' Inspection Type Compliance Sampling
Chemical Feed
Yes No NA NE
Is containment adequate?
■nnn
Is storage adequate _
■nn`n
Are backup pumps available?
■ n n n
Is the site free of excessive, leaking?
■ n n n,
Comment
Primary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater,?
n n' ■ n
Is the site free of excessive buildup of solids in center well of circular clarifier?
■ n n n
Are weirs level?
■ n n n
Is,the site free of weir blockage?
■ n n n
Is the site free of evidence ofshort-circuiting?
■ n n n
Is scum removal' adequate?
■ n n n
Is the site frmof excessive floating sludge?
n .n ■ n
Is the drive unit°operational?
■ n n n
Is,the sludge blanket level acceptable?
■ ❑ 'n ,fl _
Is the sludge blanket level acceptable? (Approximately'/. of the sidewall depth)
■ n n n
Comment A polymer (flocculant) is added prior to clarification to enhance-settling
Flow Measurement - Effluent
Yes ,No NA NE,
# Is flow meter used for reporting?
n n ■ n
Is flow meter calibrated, annually?
n n ,■ n
Is the flow meter operational?
n n ■ Cl
(If units are separated) Does the chart recorder match the flow meter?
n n ■ o
Comment `Effluent,flows from Outfall 001 are measured by pump logs ('calculations
InvolVing # of°pumps, pump,rates, pump run, times, etc) Outfall 002 flow Is measured
by staff gauge and weir (with supporting calculations) and Outfall 004 flow is measured
by an'ultrasonlc flow meter and flume
Effluent Pipe Yes No NA _NE
Is right of way to -the outfall properly maintained? ■ n n n
Are the receiving water free of foam other than trace lamounts,and other debris? ■' n n 'n
If effluent (diffuser pipes are required) are they operating properly? n Q ■ n
Page;# 5
Permit .NC0004987 Owner - Facility Marshall Steam Station
Inspection Date 06/07/2010 Inspection Type Compliance Sampling
Effluent Pipe Yes No NA NE
Comment Outfall 002 effluent appeared, clear with no floatable solid's or foam In
addition, no floatable solids or foam were observed at Outfall 001
Pagel 6