HomeMy WebLinkAboutWQ0033359_Inspection_20220530
May 30, 2022
Ms.Anne H. Lindsey
5025 Walnut Cove Road
Chapel Hill, NC 27516
Subject: Compliance Evaluation Inspection
Single Family Wastewater Treatment System
Nondischarge Permit WQ0033359
Facility: 5025 Walnut Cove Road
Chapel Hill, NC 27516
Orange County
Dear Mrs. Lindsey:
On May 11, 2022, Dorothy Robson from the Raleigh Regional Office visited your single-family
residence (SFR) wastewater treatment and irrigation system to evaluate compliance with the
Nondischarge Permit WQ0034596. The assistance Ms. Anne Lindsey and Bob McDonald from
McFarlan Septic provided was greatly appreciated.
Division records indicate a treatment system consisting of a 1,200-gallon baffled septic tank; a
2,000-gallon dosing pump tank with a 0.3 horsepower (hp) transfer pump; two 100.8 square
feet vegetated sand filters; a 4,000-gallon storage/irrigation pump tank with a 0.5-hp irrigation
pump; an ultra -violet (UV) disinfection unit; a 0.21 acre drip irrigation area with two zones, a
rain gauge; and all associated piping, valves, controls and appurtenances.
During the inspection, the following was observed:
Schedule (Section I of permit):
1. As a reminder, the Permittee shall submit a permit renewal application no later than
August 4, 2027
Performance (Section II):
2. The facility meets the performance standards as stipulated in Section II of the permit.
Operation and Maintenance (O&M) (Section III):
3. The permittee is responsible for the O&M of the entire treatment and disposal system
(Section III. 13). Although there is an O&M Plan with McFarland Septic to service the system
twice a year and to respond to alarms, as needed, the system shall be inspected monthly to
make certain of the proper operation of the spray heads, that the system is free of leaks,
that the vegetative growth allows a proper spray pattern, that the soil is assimilating the
disposed treated wastewater with no surface runoff, and that no objectionable odors are
being generated. In addition, the ultraviolet (UV) disinfection unit shall be checked weekly
to ensure proper operation. During the inspection, the UV unit was not functioning. This
DocuSign Envelope ID: C72B4A9A-6F23-4DA2-83EC-0E3714E0599A
P a g e | 2
problem was indicated to Mr. McDonald with McFarlan Septic during the inspection. Mr.
McDonald assessed the issue and found that the GFI outlet the UV unit was plugged in had
malfunctioned. Mr. McDonald put in a work order to replace it immediately. However, as
the permittee, you are responsible for any failures in the treatment system and
irrigation area, as stipulated in the permit. Within 30 days receipt of this letter,
submit a written response to this office indicating actions you will take, or have
taken, to ensure this issue will be avoided.
Monitoring and Reporting (Section IV):
4. As a reminder, the Permittee shall report to the Raleigh Regional Office, telephone
number (919) 791-4200, as soon as possible, but in no case more than 24 hours, or on the
next working day following the occurrence or first knowledge of the occurrence of any
system failure, changes/ removal of parts to the system/irrigation area, including ponding or
runoff of wastewater.
General Conditions (Section V):
5. As a reminder, this permit is effective only with respect to the nature and volume of
wastes described in the permit application, Division approved plans and specifications, and
other supporting documentation. No variances to applicable rules governing the construction
or operation of the permitted facilities are granted, unless specifically requested and
approved in this permit pursuant to 15A NCAC 02T. 0105(n). G. S. 14.- 215. 11. In addition,
failure to comply with the conditions and limitations contained herein may subject the
Permittee to an enforcement action by the Division in accordance with North Carolina
General Statutes 143- 215. 6A to 143- 215. 6C. [ G. S. 143- 215. 6A to 143- 215. 6C]
This report is a notification of the results of the compliance inspection. Within 30-days
receipt of this letter, submit a written response to this office addressing the issues
noted in item 3 above.
Please be aware that non-compliance with your permit could result in enforcement action by
the Division of Water Resources for these and any other violations of State law. The Raleigh
Regional Office encourages you to take all necessary actions to bring your facility into
compliance.
If you have questions or comments about this inspection or the requirements to take corrective
action, then please contact via email at dorothy.robson@ncdenr.gov or 919-791-4241.
Sincerely,
Vanessa E. Manuel, Assistant Regional Supervisor
Water Quality Regional Operations Section
Raleigh Regional Office
Division of Water Resources, NCDEQ
Attachment(s): NCDEQ Compliance Inspection Form
Cc: Laserfiche