HomeMy WebLinkAboutNCG551435_Inspection_20220518DocuSign Envelope ID: 77585EEF-0253-4352-8205-F39149012524
ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
Christopher B. Pope
106 Galena Court
Durham, NC 27704
Dear Mr. Pope:
NORTH CAROLINA
Environmental Quality
May 18, 2022
Subject: Compliance Evaluation Inspection
Single Family Wastewater Treatment System
General NPDES Permit NCG550000
Certificate of Coverage NCG551436
Facility: 106 Galena Court
Durham County
On April 22, 2022, Alys Hannum from the Raleigh Regional Office visited your single-family
residence wastewater treatment system to evaluate compliance with the subject General National
Pollution Discharge Elimination System (NPDES) Permit. Your wife's assistance during the
inspection and your assistance via email was greatly appreciated.
Our records indicate the treatment system consists of a septic tank, sub -surface sand filter, tablet
chlorinator with chlorine contact chamber, tablet dechlorinator, and discharge pipe.
General NPDES Permit NCG550000 and Certificate of Coverage (COC) NCG551436 authorize
the discharge of domestic wastewater from your treatment system to receiving waters designated
as an unnamed tributary to Little Lick Creek (classified WS-IV NSW) in the Neuse River Basin,
in accordance with the effluent limits and monitoring requirements established within the
General Permit. The following conditions were noted at your facility:
• Pumping the septic tank: You are required to inspect the septic tank at least yearly to
determine if solids must be removed or if other maintenance is necessary. Septic tanks
should be pumped out every five years or when the solids level is found to be more than
1/3 of the liquid depth in the septic tank compartment, whichever is greater. A pumping
company can check the status periodically and determine when pumping is required.
After the inspection, you provided documentation showing Bobby Davis Plumbing and
Septic pumped out the septic tank on July 22, 2021.
NORTH CAROLINA
Department of Environmental Quality
North Carolina Department of Environmental Quality I Division of Water Resources
Raleigh Regional Office 13800 Barrett Drive I Raleigh, North Carolina 27609
919.791.4200
DocuSign Envelope ID: 77585EEF-0253-4352-8205-F39149012524
Christopher Pope, NCG551436
May 18, 2022
Page 2 of 3
• Chlorine tablets in the chlorinator: You are reminded that it is required that chlorine
tablets be maintained in the chlorinator to ensure proper disinfection of the discharged
wastewater. Chlorine tablets provide effective disinfection and prevent/limit harmful
bacteria from discharging to the environment. The product label for these tablets must
indicate the tablets are approved for wastewater use and not for swimming pools. Part 1,
Section D (1) of General NPDES Permit NCG550000 requires the permittee to inspect
the tablet chlorinator weekly to ensure there is an adequate supply of tablets for
continuous and proper operation. Section D (4) requires the permittee to maintain all
system components in good operating order.
The inspector did not observe any chlorine tablets in the chlorinator, but you provided a
picture after the inspection showing that chlorine tablets had been added. Please continue
to ensure the correct type of tablets are used and maintained in the chlorinator as
required by the General NPDES Permit.
• Dechlorination tablets: You are responsible for always having dechlorination tablets in
place. They must be the kind for wastewater treatment and not for swimming pools.
The inspector did not observe any dechlorination tablets in the treatment unit, but you
provided a picture after the inspection showing that decchlorination tablets had been
added. Please continue to ensure the correct type of tablets are used and maintained in
the dechlorinator as required by the General NPDES Permit.
• Analyzing the effluent: Part 1. C., Effluent Limitations and Monitoring Requirements,
within General Permit NCG550000 requires a permittee to sample and analyze the
effluent leaving his/her treatment system prior to discharge annually. Parameters to be
sampled and analyzed include Flow, BOD (Biochemical Oxygen Demand), Total
Suspended Solids, Fecal Coliform and Total Residual Chlorine.
After the inspection, you informed the inspector that the effluent has not been monitored
within the last 12 months. Please collect a representative sample of the effluent, have it
analyzed by a certified commercial laboratory and submit the results to this office no
later than August 30, 2022. Failure to monitor the effluent discharge as required is a
violation of NPDES General Permit NCG550000.
• Discharge outlet location. The permittee is required to conduct a visual review of the
outfall location at least twice each year (one at the time of sampling) to ensure that no
visible solids or other obvious evidence of system malfunctioning is observed. Any
visible signs of a malfunctioning system shall be documented and steps taken to correct
the problem.
£ D_E
NORTH CAROLINA
Department of Environmental Quality
North Carolina Department of Environmental Quality I Division of Water Resources
Raleigh Regional Office 13800 Barrett Drive I Raleigh, North Carolina 27609
919.791.4200
DocuSign Envelope ID: 77585EEF-0253-4352-8205-F39149012524
Christopher Pope, NCG551436
May 18, 2022
Page 3 of 3
The end of discharge pipe was not visible nor accessible the day of the inspection, but
you provided a picture of the discharge pipe after the inspection. To comply with the
general permit monitoring requirements, you need to be able to sample and analyze the
effluent from your SFR system through the discharge pipe. Please keep the area around
the discharge pipe cleared of vegetation, soil and leaves. Maintaining the area will allow
you to monitor the discharge and to collect effluent samples as required by the subject
permit.
Part II Section B.14 of General Permit NCG550000 requires the permittee to "pay the annual
administering and compliance monitoring fee within thirty days after being billed by the
Division." The annual fee ($60 per year) for the period April 1, 2022 through May 31, 2021, was
due by April 1, 2022. This fee has not been paid and is overdue. Payment in the amount of $60
must be remitted to the Division as indicated on the attached Annual Permit Fee Invoice.
Please continue to periodically inspect the wastewater treatment system to ensure the treatment
components are always maintained and in good operating order. You are also reminded to
maintain all monitoring data and associated maintenance records onsite for a minimum of three
years for inspection.
If you have questions or comments about this inspection or the requirements to take corrective
action, please contact Alys Hannum at alys.hannum@ncdenr.gov, or by phone at 919-791-4255.
Sincerely,
—DocuSigned by:
iO ALSStt f.
`— B2916E6AB32144F...
Vanessa E. Manuel, Assistant Regional Supervisor
Water Quality Regional Operations Section
Raleigh Regional Office
Division of Water Resources, NCDEQ
Attachment(s): EPA Water Compliance Inspection Report
Annual Permit Fee Invoice — Due April 1, 2022
cc: RRO/SWP Files
Laserfiche
£D_E
NORTH CAROLINA
Department of Environmental Quality
North Carolina Department of Environmental Quality I Division of Water Resources
Raleigh Regional Office 13800 Barrett Drive I Raleigh, North Carolina 27609
919.791.4200
DocuSign Envelope ID: 77585EEF-0253-4352-8205-F39149012524
NORTH CAROLINA DEPARTMENT OF
ENVIRONMENTAL QUALITY
INVOICE
Annual Permit Fee
Overdue
This annual fee is required by the North Carolina Administrative Code. It covers the administrative costs associated with
your permit. It is required of any person holding a permit for any time during the annual fee period, regardless of the facili
operating status. Failure to pay the fee by the due date will subject the permit to revocation. Operating without a valid
permit is a violation and is subject to a $10,000 per day fine. If the permit is revoked and you later decide a permit is
needed, you must reapply, with the understanding the permit request may be denied due to changes in environmental,
regulatory, or modeling conditions.
Invoice Number:
Permit Number:
2022PR002377
NCG551436
Durham County
106 Galena Court
Christopher B. Pope
106 Galena Ct
Durham, NC 27704
Annual Fee Period: 2022-04-01 to 2023-03-31
Invoice Date: 03/02/2022
Due Date: 04/01/2022
Annual Fee: $60.00
Notes:
1. You may pay either by mail with check/money order OR by electronic payment (eCheck or Credit Card).
2. If payment is by check/money order, please remit payment to:
NCDEQ - Division of Water Resources
Attn: Animal/Discharge/Non-Discharge Billing
1617 Mail Service Center
Raleigh, NC 27699-1617
3. If payment is electronic, please see https://deq.nc.gov/epavments/wq to pay electronically. Payments by eCheck will debit your
checking account. Credit card transactions will incur a convenience fee.
4. Please include your Permit Number and Invoice Number on all correspondence.
5. A $25.00 processing fee will be charged for returned checks in accordance with North Carolina General Statute 25-3-512.
6. Non -Payment of this fee by the payment due date will initiate the permit revocation process.
7. Should you have any questions regarding this invoice, please contact the Annual Administering and Compliance Fee
Coordinator at 919-707-3698.
(Return This Portion With Check)
ANNUAL PERMIT INVOICE
Overdue
Invoice Number: 2022PR002377
Permit Number: NCG551436
Durham County
106 Galena Court
Christopher B. Pope
106 Galena Ct
Durham, NC 27704
Annual Fee Period: 2022-04-01 to 2023-03-31
Invoice Date: 3/2/2022
Due Date: 4/1/2022
Annual Fee: $60.00
Check Number:
DocuSign Envelope ID: 77585EEF-0253-4352-8205-F39149012524
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
1
21IIIIII
671
Transaction Code
IN I 2 IL I
NPDES yr/mo/day Inspection
3 I NCG551436 111 121 22/04/22 117
Type
1810I
IIIIIIIIIII
Inspector Fac Type
19I S I 2011
IIIIIIIIIII IIIIIII I IIIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
I 70I3 I 711 1 72 I N I 73I 1 74 71
I I
I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES oermit Number)
106 Galena Court
106 Galena Ct
Durham NC 27704
Entry Time/Date
10:OOAM 22/04/22
Permit Effective Date
21/08/18
Exit Time/Date
10:30AM 22/04/22
Permit Expiration Date
25/10/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Christopher B Pope,106 Galena Ct Durham NC 27704//919-625-9575/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Operations & Maintenar Self -Monitoring Progran
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s)
Alys K Hannum
of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Docusigned by: DWR/RRO WQ/919-791-4255/
air-W 5/16/z022
4C22170C5AA04F3...
Signature
of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
1 /atn.t,SSa f. �l.abu't,�, 5/17/2022
B?r9ni 628321 g4F )
EPA Form ..55�5bbUU ..ii (Kev 9-94 Previous editions are obsolete.
Page# 1
DocuSign Envelope ID: 77585EEF-0253-4352-8205-F39149012524
NPDES yr/mo/day
31 NCG551436 111 121 22/04/22
I17
Inspection Type
18LI
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page# 2
DocuSign Envelope ID: 77585EEF-0253-4352-8205-F39149012524
Permit: NCG551436
Inspection Date: 04/22/2022
Owner - Facility: 106 Galena Court
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable El El El
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Septic Tank
(If pumps are used) Is an audible and visual alarm operational?
Is septic tank pumped on a schedule?
Are pumps or syphons operating properly?
Are high and low water alarms operating properly?
Comment:
Sand Filters (Low rate)
(If pumps are used) Is an audible and visible alarm Present and operational?
Is the distribution box level and watertight?
Is sand filter free of ponding?
Is the sand filter effluent re -circulated at a valid ratio?
# Is the sand filter surface free of algae or excessive vegetation?
# Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1)
Comment:
Yes No NA NE
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Yes No NA NE
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
• ❑ ❑ ❑
❑ ❑ ❑ •
Disinfection -Tablet Yes No NA NE
Are tablet chlorinators operational? • ❑ ❑ ❑
Are the tablets the proper size and type? • ❑ ❑ ❑
Number of tubes in use? 2
Is the level of chlorine residual acceptable? ❑ ❑ ❑ •
Is the contact chamber free of growth, or sludge buildup? • ❑ ❑ ❑
Is there chlorine residual prior to de -chlorination? ❑ ❑ ❑ •
Comment: Resident did not have chlorine tablets at the time of the inspection. Sent picture proof
of new tablets bought after the inspection.
De -chlorination Yes No NA NE
Type of system ? Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)? • ❑ ❑ ❑
Page# 3
DocuSign Envelope ID: 77585EEF-0253-4352-8205-F39149012524
Permit: NCG551436
Inspection Date: 04/22/2022
Owner - Facility: 106 Galena Court
Inspection Type: Compliance Evaluation
De -chlorination Yes No NA NE
Is storage appropriate for cylinders? • ❑ ❑ ❑
# Is de -chlorination substance stored away from chlorine containers? ❑ El • El
Comment:
Are the tablets the proper size and type? • ❑ ❑ ❑
Are tablet de -chlorinators operational? ■ ❑ ❑ ❑
Number of tubes in use?
Comment: Resident did not have de -chlorination tablets in the de -chlorinator at the time of the
inspection. Sent picture proof of tablets after the inspection.
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ • ❑ ❑
Is sample collected below all treatment units? ❑ • ❑ ❑
Is proper volume collected? ❑ • ❑ ❑
Is the tubing clean? El ❑ • ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 El El • El
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type El • El El
representative)?
Comment: Resident has not yet sampled the effluent after purchasing the house last year.
Page# 4