HomeMy WebLinkAboutWQ0029346_Monitoring - 03-2021_20210422 (2)GW-59A COMPLIANCE REPORT FORM Permit #
(.Sabmil one each nioaiforing period with GIV59 fornnsJ
]
Enter date monitoring results were due. �� -k Will this monitoring report (GW-59 and GW-59A)
YES
NO
be submitted after the established due date?
L
2
Was any required information missing on the GW-59 report forms?
YES
NO
L
IF the answer to question 1 or 2 is "YES" list in the space provided below the W/ identification number(s) and
explain the problems encountered in obtaining the required information,
3
Are any of the monitor wells in need of repair or maintenance (damaged casing, unlocked or missing cap, missing
YES
NO
identification plate, area overgrown, etc.)? If the aimver is "Yen ", contact the Regional Q11ice for guidance.
4
Are any monitored constituents equal to or above the established standards?
YES
NO
if the answer to question 4 is "NO", skip to section 8. C-i
0
if the answer to question 4 is "YES" list the affected wells individually with constituent(s) and conceffltmtion(s)
exceeding standards in the space provided below: ... C11
LL Cq
� a
L Q
5
For the constituents identified in question 4 above, have standards been exceeded prevlo 4y for the
YES
NO
same constituent(s) in the same well(s) in the last two years?
If the answer to question 5 is "NO", skip to section 8.
If the answer to question 5 is "YES", list in the space provided below, each well with constituent(s) exceeding
standards, concentrations) reported, and sample collection date for each occurrence (for the last two years).
Are the monitoring wells listed in section 5 located at or beyond the review boundary?
YES
NO
If the answer is "YES", a groundwater quality problem maybe occurring. CONTACT THE REGIONAL
OFFICE IMMEDIATELY FOR GUIDANCE. If the answer is "NO", monitoring wells maybe improperly
located; contact the Regional Office.
7
Is the permittee implementing previously approved actions required by the Division involving this
YES
NO
groundwater quality problem?
If the answer to question 7 is "YES", describe those actions in the space provided below.
If the answer to question 7 is "NO", contact the Regional Office within 90 days: an evaluation may be
required to determine the impact the waste disposal system is having at the review and compliance
boundaries surrounding this facility. Failure to do so may subject the permittee to a Notice of Violation
fines, and/or penalties.
g
The person completing this portion (GW-59A) of the monitoring report should sign below and submit this
form with G W-59 forms for required wells to the address provided at the top of the current GW-59 form.
I hereby acknowledge that the above Information was evaluated and the Information submitted in this
report (Compliance Report GW-59A) is true and complete to the best of my knowledge.
\M�J— + LO - 1A
Signature of Permittee (or Authorized Agent) Date
GW-59A 12/8/2003
SUBMIT FnRM ON YPI I OW PAPER nw v
GROUNDWATER QUALITY MONITORING:
DEPARTMENT OF ENVIRONMENTAL QUALITY - DIV. OF WATER RESOURCES
COMPLIANCE REPORT FORM
INFORMATION PROCESSING UNIT
1617 MAIL SERVICE CENTER, RALEIGH, NC 27699-1617
FACILITY INFORMATION
Please Print Clearly or Type
PERMIT Number: Expiration Date: 3/21/2022
Facility Name: Blue Ridge Mountain Club WWTP
Non -Discharge WQ0029346 UIC
Permit Name (if different):
NPDES Other
Facility Address: P.O. Box 1727
TYPE OF PERMITTED OPERATION BEING MONITORED
Blowing Rock NC
28605 County Wilkes
❑ Lagoon ❑ Remediation: Infiltration Gallery
X Spray Field ❑ Remediation:
Contact Person: Bob Barr
Telephone#: (828) 251-1900
❑ Rotary Distributor ❑ Land Application of Sludge
Well Location/Site Name: MW-1
No. of wells to be sampled:
1
❑ Water Source Heat Pump ❑ Other:
(from Pe"It)
SAMPLING INFORMATION
If WELL
WELL ID NUMBER (from Permit): MW-1
Date sample collected: 3/17/2021
FIELD ANALYSES:
WAS
Well Depth: 21.0 ft.
Well Diameter: 2
in.
pH 00400: 5.67 units Temp. 000lo: 13.3 oC
DRY at
Depth to Water Level 82546: 6.0
p ft. below measuring point Screened Interval: 6
ft. to 21
ft. Spec. Cond. 000sa: µMhos
time of
Measuring Point is 0 ft. above land surface
Relative M.P. Elevation:
ft.
Odor 00085:
sampling,check
Volume of water pumped/bailed before sampling:
gallons
Appearance
here:❑
Samples for metals were collected unfiltered: & YES
❑ NO and field acidified: YES
❑ NO
LABORATORY INFORMATION
Date sample analyzed:4/812021
Laboratory Name: Watertech
Labs
Certification No. 50
PARAMETERS NOTE: Values should reflect dissolved and colloidal concentrations.
COD 00335
mg/L
Nitrite (NO2) as N 00615
mg/L
Pb - Lead o1o51 u9 /L
Coliform: MF Fecal 31616 <1
/100mL
Nitrate (NO3) as N 00620 <0.1
mg/L
Zn - Zinc 01092 mg/L
Coliform: MF Total 31504
/100mL
Phosphorus: Total as P 00665 0.23
mg/L
(Note: Use MPN method for highly turbid samples)
Orthophosphate 70507
mg/L
Other (Specify Compounds and Concentration Units):
Dissolved Solids:Total 70300 18
mg/L
AI -Aluminum o11o5
mg/L
pH (Lab) 00403
units
Ba - Barium 01007
ug/L
TOC 00680 1.4
mg/L
Ca - Calcium 00916
mg/L
Chloride 00940 5.5
mg/L
Cd - Cadmium 01027
ug/L
Arsenic 01002
ug/L
Chromium: Total 01034
ug/L
Grease and Oils 00552
mg/L
Cu - Copper 01042
mg/L
ORGANICS: (by GC, GC/MS, HPLC)
Phenol 32730
ug/L
Fe - Iron 01045
ug/L
(Specify test and method #. ATTACH LAB REPORT.)
Sulfate 00945
mg/L
Hg - Mercury 71900
ug/L
Lab Report Attached? ❑ Yes (1) 0 No (0)
Specific Conductance 00095
µMhos
K - Potassium 00937
mg/L
VOC 7873 method #
Total Ammonia 00610 1.35
mg/L
Mg - Magnesium 00927
mg/L
method #
(Ammonia Nitrogen: NH38s N. Ammonia Nitrogen, Total)
Mn - Manganese 01055
ug/L
, method #
TKN as N 00625
mg/L
Ni - Nickel 01067
ug/L
method #
t-or Rememation Systems Only (Attach Lab Reports): Influent Total VOCs: mg/L Effluent Total VOCs: mg/L VOC Removal%
Robert P. Barr / Authorized Agent
Permittee (or Authorized Agent) Name and Title - Please print or type
GW-59 Rev.06-07-2018
#dRTER4rzCH L119S.Inc.
POST OFFICE 80; 1056 • #5 PINEWOOD PLAZA DR.
GRANITE FALLS, NORTH CAROLINA 28630
(828)396-4444
SAMPLE: Blue Ridge Mtn MW#1 COLLECTION DATE: 3/17/2021
PERMIT #: COLLECTION TIME: 12:40
ADDRESS: RPB Engineers RECEIVED DATE: 3/17/2021
RECEIVED TIME: 13:28
REPORTED: 4/8/2021
ANALYSIS
ANALYSIS
RESULTS
UNITS
DATE
ANALYST
TDS
18
mg/L
3/18/21
lag
Chloride
5.5
mg/L
3/24/21
lag
NH3
1.35
mg/L
3/18/21
jrg
Fecal Coliform
<1
/100mL
3/17/21
jrg
T. Phosphorus
0.23
mg/L
415/21
jdg
NO3
<0.1
mg/L
4/1/21
jdg
TOC
1.4
mg/L
3/28/21
LOG ID: 2103-286 REPORTED BY: NC CERTIFIED LAB # 50
foll��' a
Tony Gragg, Lab Supervisor
-Ra'lceAnalytical
www.pacelabs.com
I
ANALYTICAL RESULTS
Pace Analytical Services, LLC
1377 South Park Drive
Kernersville, NC 27284
(704)977-0981
Project: TOC-Blue Ridge Mtns/Boone Cott
Pace Project No.: 92528594
Sample: BLUE RIDGE MTN CLUB Lab ID: 92528594001 Collected: 03/17/21 12:40 Received: 03/18/21 11:15 Matrix: Water
MW1
Parameters
5310B TOC
Total Organic Carbon
Date: 03/29/2021 10:50 AM
Results Units Report Limit DF Prepared Analyzed CAS No. Qual
Analytical Method: SM 531OB-2011
Pace Analytical Services -Asheville
1.4 mg/L 1.0 1 03/28/21 17:20 7440A4-0
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, LLC.
Page 4 of 10