HomeMy WebLinkAboutNC0006033_Compliance Evaluation Inspection_20220321ROY COOPER
Governor
ELIZABETH 5. 3ISER
Secretary
RICHARD E. ROGERS, JR.
btrectar
NORTH CAROLINA
Miiriironm. ntar Qrsoltty
March 21, 2022
Ms. Stephanie Scheringer, Division Manager
Two Rivers Utilities
P.O. Box 1748
Gastonia, NC 28053
Subject: Compliance Evaluation Inspection
Eagle Road WWTP
NPDES Permit No. NC0006033
Gaston County
Dear Ms. Scheringer:
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted
at the subject facility on March 15, 2022, by Ori Tuvia and Maria Schutte. David
Shellenbarger's, and Doug Barker's cooperation during the site visit was much appreciated.
Please advise the staff involved with this NPDES Permit by forwarding a copy of the enclosed
report.
The report should be self-explanatory; however, should you have any questions, please
do not hesitate to contact Ori Tuvia at (704) 235-2190, or at ori.tuvia@ncdenr.gov.
cc: NPDES, MRO files (Laserfiche)
NORTH CAROLINA
oay,ro�em or Environmentalw.i
Sincerely,
DocuSigned by:
L46twH N ut4
F161 FB69A2D84A3...
for
W. Corey Basinger
Regional Supervisor
Mooresville Regional Office
Division of Water Resources
North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1601 East Center Avenue, Suite 301 I Mooresville, NC 28115
704.663.1699
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction
1 IN
Code
I 2
L
NPDES yr/mo/day Inspection Type Inspector Fac
3 I NC0006033 111 121 22/03/15 117 1810I 191S I 2011
Type
21IIIIII
IIIIIIIIIIIIIIIIII
I
IIIIII
IIIIIIIIIII
P6
Inspection
67I1.0
Work Days
Facility Self -Monitoring
I 70I4
Evaluation Rating
I 71IN
B1
I 72
QA
I N I
731
1
I I
Reserved
74 751
1
I
I I
I
I
I
180
l
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES Hermit Number)
Eagle Road WWTP
661 Eagle Rd
Belmont NC 28012
Entry Time/Date
02:10PM 22/03/15
Permit Effective Date
22/02/01
Exit Time/Date
02:45PM 22/03/15
Permit Expiration Date
27/01/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Douglas Edward Barker/ORC/704-922-4086/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Hubert Harold Hampton,2226 Old Hickory Grove Rd Mount Holly NC
281209694//704-825-6593/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s)
Maria Schutte
of Inspector(s) Agency/Office/Phone and Fax Numbers Date
c—DocuSigned by:
DWR/Division of Water Quality/704-663-1699/ 3/18/2022
OriATuvia
�C---i DWR/MRO WQ/704-663-1699/
BB057A2DE017498...
Signature of ManfrR@r1tsQ"A`Ik6Viewer
Andrew Pitneyy
Agency/Office/Phone and Fax Numbers Date
4 H 44151IVR/MRO WQ/704-663-1699 Ext.2180/ 3.21.22
F161FB69A2D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
NPDES yr/mo/day
31 NC0006033 111 121 22/03/15
I17
Inspection Type
18 [j
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page# 2
Permit: NC0006033
Inspection Date: 03/15/2022
Owner - Facility: Eagle Road WWTP
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ ❑
application?
Is the facility as described in the permit? • ❑ El El
# Are there any special conditions for the permit? El • El El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment: The subject permit expires on 1/31/2027
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
•
• ❑ ❑ ❑
❑ ❑ • ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The records reviewed during the inspection were organized and well maintained.
DMRs, COCs, ORC visitations logs, bench sheets, and calibration logs were reviewed
up to October 2021.
Page# 3
Permit: NC0006033
Inspection Date: 03/15/2022
Owner - Facility: Eagle Road WWTP
Inspection Type: Compliance Evaluation
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ • ❑
Comment: Influent and effluent analyses (including field) are performed under the City's Crowders
Creek Laboratory Certification #210. Pace (Hardness and pollutant scan) and
Meritech, Inc. (toxicity) have also been contracted to provide analytical support. The
laboratory instrumentation used for field analyses appeared to be properly
calibrated/verified and documented
Influent Sampling
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is sampling performed according to the permit?
Comment: The subject permit requires composite influent BOD and TSS samples.
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? • ❑ ❑ ❑
Is sample collected below all treatment units? • ❑ ❑ ❑
Is proper volume collected? • ❑ El ❑
Is the tubing clean? • El El El
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 • El El El
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • El El El
representative)?
Comment: The subject permit requires both composite and grab effluent samples.
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, ❑ El El
and sampling location)?
Page# 4
Permit: NC0006033
Inspection Date: 03/15/2022
Owner - Facility: Eagle Road WWTP
Inspection Type: Compliance Evaluation
Upstream / Downstream Sampling Yes No NA NE
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ME ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: At the time of the inspection the facility appeared to be properly operated and well
maintained. The operations staff incorporate a comprehensive process control
program with all measurements being properly documented and maintained on -site.
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Flow Measurement - Influent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: Comment: The flow meter was last calibrated/verified by Expert Services on
12/20/2021.
Yes No NA NE
•
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
MODE
Yes No NA NE
❑ • ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Surface
Is the basin free of dead spots? • ❑ ❑ ❑
Are surface aerators and mixers operational? • ❑ ❑ ❑
Are the diffusers operational? ❑ ❑ • ❑
Is the foam the proper color for the treatment process? • ❑ ❑ ❑
Page# 5
Permit: NC0006033
Inspection Date: 03/15/2022
Owner - Facility: Eagle Road WWTP
Inspection Type: Compliance Evaluation
Aeration Basins Yes No NA NE
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/I)
❑ ❑ • ❑
Comment: The aeration basin is equipped with four floating aerators (all operational) and
avcurtain baffle. Sodium hydroxide is added on an as -needed basis to maintain
appropriate pH/alkalinity levels.
Nutrient Removal Yes No NA NE
# Is total nitrogen removal required? • ❑ ❑ ❑
# Is total phosphorous removal required? • ❑ ❑ ❑
Type Chemical
# Is chemical feed required to sustain process? • ❑ El El
Is nutrient removal process operating properly? • El El El
Comment: Aluminum chlorohydrate is used to chemically reduce total phosphorus levels.
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • El El El
Is the site free of excessive buildup of solids in center well of circular clarifier? • ❑ ❑ ❑
Are weirs level? • El El El
Is the site free of weir blockage? ■ El El El
Is the site free of evidence of short-circuiting? • ❑ ❑ ❑
Is scum removal adequate? • ❑ ❑ ❑
Is the site free of excessive floating sludge? ■ El El El
Is the drive unit operational? • El El El
Is the return rate acceptable (low turbulence)? • ❑ ❑ ❑
Is the overflow clear of excessive solids/pin floc? • ❑ ❑ ❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) ■ El El El
Comment: Both secondary clarifiers are operational; however, only one was in operation due to
low influent flows.
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Yes No NA NE
Page# 6
Permit: NC0006033
Inspection Date: 03/15/2022
Owner - Facility: Eagle Road WWTP
Inspection Type: Compliance Evaluation
Pumps-RAS-WAS Yes No NA NE
Comment:
Disinfection -Liquid
Is there adequate reserve supply of disinfectant?
(Sodium Hypochlorite) Is pump feed system operational?
Is bulk storage tank containment area adequate? (free of leaks/open drains)
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
De -chlorination Yes No NA NE
Type of system ? Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)? • ❑ ❑ ❑
Is storage appropriate for cylinders? • ❑ ❑ ❑
# Is de -chlorination substance stored away from chlorine containers? ❑ ❑ • ❑
Comment:
Are the tablets the proper size and type? ❑ ❑ ■ ❑
Are tablet de -chlorinators operational? ❑ ❑ ■ ❑
Number of tubes in use?
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: Comment: The flow meter was last calibrated/verified by Expert Services on
12/20/2021.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
Yes No NA NE
• ❑ ❑ ❑
Yes No NA NE
Page# 7
Permit: NC0006033
Inspection Date: 03/15/2022
Owner - Facility: Eagle Road WWTP
Inspection Type: Compliance Evaluation
Effluent Pipe
If effluent (diffuser pipes are required) are they operating properly?
Comment: The effluent appeared clear with no floatable solids or foam
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Yes No NA NE
• ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: Digested bio-solids are land applied under the authority of Permit No. WQ0001793
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Comment: The facility is equipped with two standby generators
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 8