HomeMy WebLinkAboutWQ0029042_Regional Office Historical File Pre 2018Michael F. Easley, Governor
William G. Ross Jr., Secretary 1
North Carolina Department of Environment and Natural Resources
July 15, 2005
Ms. Christie Putnam, Interim Director
Union County Public Works
400 North Church Street
Monroe, North Carolina 28112
Alan W.•Klimek, P.E. Director
Division of Water Quality
Subject: Permit No. WQ0029042
Fair Haven Off -Site Trunk Sewer
Wastewater Collection System Extension
Union County, North Carolina
Dear Ms. Putnam: '
In accordance with your application received on June 30, 2005, we are forwarding herewith
Permit No. WQ0029042, dated July 15, 2005, to Union County Public Works for the construction only of
the subject wastewater collection system extension. This permit shall be effective from the date of
issuance until rescinded, and shall be subject to the conditions and limitations as specified therein. This
cover letter shall be considered a part of this permit and is therefore incorporated therein by reference.
Please pay particular attention to Permit Condition 3 which requires that the wastewater
collection facilities be properly operated and maintained in accordance with 15A NCAC 2H .0227 or any
individual system -wide collection system permit issued to the Permittee.
Permitting of this project does not constitute an acceptance of any part of the project that does
not meet 1) 15A NCAC 2H .0200; 2) the Division of Water Quality's (Division) Gravity Sewer Minimum
Design Criteria adopted February 12, 1996, as applicable; 3) and the Division's Minimum Design
Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000, as
applicable, unless specifically mentioned herein. Division approval is based on acceptance of the
certification provided by a North Carolina -licensed Professional Engineer in the application. It shall be
the Permittee's responsibility to ensure that the as -constructed project meets the appropriate design
criteria and rules. Failure to comply may result in penalties in accordance with North Carolina General
Statute §143-215.6A through §143-215.6C, construction of additional or replacement wastewater
collection facilities, and/or referral of the North Carolina -licensed Professional Engineer to the licensing
board.
Mooresville Regional Office 610 East Center Ave., Suite 301 Mooresville, NC 28115 Phone: (704) 663-1699 Fax: (704) 663-604f
Internet h2o.enr.state.nc.us Customer Service: 1-877-623-6748
An Equal Opportunity/Affirmative Action Employer--50% Recycled/10% Post Consumer Paper
Prr.nam
July 15, 2005
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North
Carolina as amended, and other applicable Laws, Rules, and Regulations, permission is hereby
granted to Union County Public Works for the construction only of approximately 800 linear feet of 18-
inch gravity sewer as part of the Fair Haven Off -Site Trunk Sewer project, and the transfer of 0 gallons
per day of collected domestic wastewater into Union County's existing sewerage system, pursuant to
the application received June 30, 2005, and in conformity with 15A NCAC 2H .0200; the Division's
Gravity Sewer Minimum Design Criteria adopted February 12, 1996, as applicable; the Division's
Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted
June 1, 2000, as applicable; and other supporting data subsequently filed and approved by the
Department of Environment and Natural Resources and considered a part of this permit.
The sewage and wastewater collected by this system shall be treated in the Union County
WWTP (Twelve Mile Creek NPDES No. NC0085359) prior to being discharged into the receiving
stream.
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the
right to request an adjudicatory hearing upon written request within 30 days following receipt of this
permit. This request must be in the form of a written petition, conforming to Chapter 150E of North
Carolina General Statutes, and filed with the Office of Administrative Hearings, 6714 Mai! Service
Center, Raleigh, NC 27699-6714. Unless such demands are made, this permit shall be final and
binding.
If you need additional information concerning this matter, please contact Dee Browder at (704)
663-1699.
Sincerely,
J2 ?- lam` r
for Alan W. Klimek, P.E.
cc: Union County Health Department
Mooresville Regional Office, Surface Water Protection (WWTP Permit No. NC0085359)
Jay D. Banks, Mckim & Creed
Surface Water Protection Central Files
Marie Doklovic, PERCS
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
RALEIGH
WASTEWATER COLLECTION SYSTEM EXTENSION PERMIT
This permit shall be effective from the date of issuance until rescinded and shall be subject to the
following specified conditions and limitations:
1. This permit shall become voidable unless the wastewater collection facilities are constructed in
accordance with the conditions of this permit; 15A NCAC 2H .0200; the Division of Water Quality's
(Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996, as applicable; the
Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force
Mains adopted June 1, 2000, as applicable; and other supporting materials unless specifically
mentioned herein.
2. This permit shall be effective only with respect to the nature and volume of wastes described in the
application and other supporting data.
3. The wastewater collection facilities shall be properly maintained and operated at all times. The
Permittee shall maintain compliance with an individual system -wide collection system permit for the
operation and maintenance of these facilities as required by 15A NCAC 2H .0227. If an individual
permit is not required, the following performance criteria shall be met as provided in 15A NCAC 2H
.0227:
a. The sewer system shall be effectively maintained and operated at ail times to prevent
discharge to land or surface waters, and any contravention of the groundwater standards in
15A NCAC 2L .0200 or the surface water standards in 15A NCAC 2B .0200.
b. A map of the sewer system shall be developed and shall be actively maintained.
c. An operation and maintenance plan shall be developed and implemented.
d. Pump stations that are not connected to a telemetry system shall be inspected every day (i.e.
365 days per year). Pump stations that are connected to a telemetry system shall be
inspected at least once per week.
e. High -priority sewer lines shall be inspected at least once per every six-month period of time.
f. A general observation of the entire sewer system shall be conducted at least once per year.
g. Inspection and maintenance records shall be maintained for a period.of at least three years.
h. Overflows and bypasses shall be reported to the appropriate Division regional office in
accordance with 15A NCAC 26 .0506(a), and public notice shall be provided as required by
North Carolina General Statute §143-215.1C.
1
v
permit shall not be transferable. In the event there is a desire for the wastewater collection
facilities to change ownership, or there is a name change of the Permittee, a formal permit request
shall be submitted to the Division accompanied by documentation from the parties involved, and
other supporting materials as may be appropriate. The approval of this request shall be
considered on its merits and may or may not be approved.
5. Construction of the gravity sewers, pump stations, and force mains shall be scheduled so as not to
interrupt service by the existing utilities nor result in an overflow or bypass discharge of wastewater
to the surface waters of the State..
6. Per 15A NCAC 2H .0220, upon completion of construction and prior to operation of these
permitted facilities, the completed Engineering Certification form attached to this permit shall be
submitted with the required supporting documents to the address provided on the form. A complete
certification is one where the form_ is fully executed and the supporting documents are provided as
applicable.
7. A copy of the construction record drawings shall be maintained on file by the Permittee for the life
of the wastewater collection facilities.
8. Failure to abide by the conditions and limitations contained in this permit; 15A NCAC 2H .0200; the
Division's Gravity Sewer Design Criteria adopted February 12, 1996 as applicable; the Division's
Minimum Design Criteria for the Fast -Track Permitting of Pump Station and Force Mains adopted
June 1, 2000 as applicable; and other supporting materials may subject the Permittee to an
enforcement action by the Division, in accordance with North Carolina General Statutes §143-
215.6A through §143-215.6C.
9. In the event that the wastewater collection facilities fail to perform satisfactorily, including the
creation of nuisance conditions, the Permittee shall take immediate corrective action, including
those as may be required by this Division, such as the construction of additional or replacement
facilities.
10. The issuance of this permit shall not exempt the Permittee from complying with any and all
statutes, rules, regulations, or ordinances that may be imposed by other government agencies
(local, state and federal) which have jurisdiction, including but not limited to applicable river buffer
rules in 15A NCAC 2B .0200, erosion and sedimentation control requirements in 15A NCAC Ch. 4
and under the Division's General Permit NCG010000, and any requirements pertaining to wetlands
under 15A NCAC 2B .0200 and 15A NCAC 2H .0500.
11. Noncompliance Notification:
The Permittee shall verbally report to a Division of Water Quality employee at the Mooresville
Regional Office, telephone number (704) 663-1699, as soon as possible, but in no case more than
24 hours or on the next working day, following the occurrence or first knowledge of the occurrence
of either of the following:
a. Any process unit failure, due to known or unknown reasons, that renders the facility incapable
of adequate wastewater transport, such as mechanical or electrical failures of pumps, line
blockage or breakage, etc.; or
b. Any failure of a pumping station or sewer line resulting in a by-pass directly to receiving waters
without treatment of all or any portion of the influent to such station or facility.
2
Voice mail messages or faxed information is permissible, but shall not be considered as the
initial verbal report. Overflows and spills occurring outside normal business hours may also be
reported to the Division of Emergency Management at telephone number (800) 858-0368 or
(919) 733-3300. Persons reporting any of the above occurrences shall file a spill report by
completing Part I of Form CS-SSO (or the most current Division approved form), within five days
following first knowledge of the occurrence. This report shall outline the actions taken or
proposed to ensure that the problem does not recur. Part II of Form CS-SSO (or the most
current Division approved form) can also be completed to show that the SSO was beyond
control.
12. This permit shall be for the construction of the wastewater collection facilities only. No flow
shall be made tributary to the subject facilities until permit modification application is submitted
(with the appropriate fee), a modified permit is issued, and the Engineer's Certification is received
and approved by the Division.
Permit issued this the 15'h day of July, 2005.
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
/ . y.
for Alan W. Klime , P.E., Director
Division of Water Quality
By Authority of the Environmental Management Commission
Permit Number WQ0029042
3
Fast Track Engineering Certification
Permit No. WQ0029042
July 15, 2005
Complete and submit this form to the permit issuing regional office with the following:
• One copy of the project record drawings (plan & profile views of sewer lines) of the wastewater collection
system extension
• Supporting design calculations (selected pumps, system curve, operating point, available storage if portable
generator(s) or storage greater than longest past three year outage reliability option selected) for any pump
stations permitted as part of this project
• Changes to the project should be clearly identified on the record drawings or in written summary form. Permit
modifications are required for any changes resulting in non-compliance with this permit, regulations or
minimum design criteria.
This project shall not be considered complete nor allowed to operate until this Engineer's Certification and all
required supporting documentation have been received by the Division. Therefore, it is highly recommended
that this certification be sent in a manner that provides proof of receipt by the Division.
ENGINEER'S CERTIFICATION
❑ Partial D Final
I, , as a duly registered Professional Engineer in the State of North Carolina, having
been authorized to observe (❑ periodically, ❑ weekly, ❑ full time) the construction of the Fair Haven Off -site
Trunk Sewer Project, Union County project for the Permittee hereby state that, to the best of my abilities, due care
and diligence was used in the observation of the construction such that the construction was observed to be built
within substantial compliance of this permit; 15A NCAC 2H .0200; the Division of Water Quality's (Division)
Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design
Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and
other supporting materials.
North Carolina Professional Engineer's
seal, signature, and date:
SEND THIS FORM & SUPPORTING DOCUMENTATION
WITH REQUIRED ATTACHMENTS TO THE FOLLOWING ADDRESS
MOORESVILLE REGIONAL OFFICE
SURFACE WATER PROTECTION
• 610 EAST CENTER AVENUE, SUITE 301
MOORESVILLE NC 28115
The Permittee is responsible for tracking all partial certifications up until a final certification is received. Any
wastewater flow made tributary to the wastewater collection system extension prior to completion of this
Engineer's Certification shall be considered a violation of the permit and shall subject the Permittee to appropriate
enforcement actions.
-TRACK APPLICATION for GRAVITY SEWERS, PUMP STATIONS, AND FORCE MAINS
PAGE 3
USE THE TAB KEY TO MOVE FROM FIELD TO FIELD! Application Number:(to be completed by DWQ) O' ?qc'J-
.
.--1c.
7
-
IlL 4
,Z!.. "
Z
i1. Owner
1a. Union County Department of Public Works
i Full Legal Name (company, municipality, HOA, utility, etc.)
I1b. Christie Putnam, PE, Interim Director, Union County Department of PublicWorks
Signing Official Name and Title (Please review 15A NCAC 2H .0206(b) for authorized signing officials!)
The legal entity who will own this
system
is:
0 Private Partnership ❑ Corporation
■ Individual 0 Federal ■ Municipality
4 State/County
■ Other (specify):
1 d. 400 North Church Street ile. Monroe
Mailing Address ,
City
:1f. NC
lg. 28112-4804
- State
1 h. 704-296-4210 i. 704-296-4232
I Zip Code
1 j.
ice:;
'. r
_ ,.'2a.
''d
11
3 Telephone Facsimile E-mail
2. Project (Facility) Information:
Fair Haven Off -Site Trunk Sewer 2b. Union County
Brief Project Name (permit will refer to this name) i Coupty Where Project is Located
Q, ,, -`3.
Q'-3a.
,.
Contact Person: •
Charlie O'Cain, PE, Deputy Director
= Name and Affiliation of Someone Who Can Answer Questions About this Application
3b. 704-296-4210 3c. o'cain at�co.union.nc.us
_
Phone Number ? E-mail
'
-Z
H; .
(of an existing permit) If Modification, Permit No.:
1. Project is ® New • Modification
For modifications, attach a separate
phase, changing line sizelength,
duplicate project information in
sheet
etc.).
B(7) and
clearly explaining
Only include
B(10-11) that
the reason for the modification (i.e. adding another
the modified information in this permit application - do not
has already been included in the original permit.
B(3))
(go to Item 2(a))
2. Owner is El Public (skip to Item
• Private
2a. If private, applicant will be: 12b.
❑ Retaining Ownership (i.e. store, church, single office, etc.) or 1
❑ Leasing units (lots, townhomes, etc. - skip to Item B(3))
❑ Selling units (lots, townhomes, etc. - go to Item B(2b))
If sold, facilities
❑ Public Utility
owned by a (must choose one)
(Instruction III)
Assoc./Developer (Instruction IV)
,;
• Homeowner
3. Union County
Owner of Wastewater Treatment Facility (WVVfF) Treating Wastewater From This Project .
'4a.
1L. ,
.-Z
Twelve Mile Creek WARP 4b. NC0085359
Name of WWTF i VWVTF Permit No.
5a. Union County
5b. 24" Gravity SewerE[Gravity
• Force Main
pc. WQ0019570
Owner of Downstream Sewer
Receiving Sewer Size
I Permit Number of Downstream Sewer (if known)
.
The origin of this wastewater is (check all that apply):
_.'6.
''
LL- -
a=, '
10
• Car Wash
Home
(specify):
% Domestic/Commercial
. Residential Subdivision
■ Apartments/Condominiums
• Mobile Home Park
■ Institution
0 Hospital
% Industrial
• School
■ Church
• Restaurant
IN Nursing
%Other (specify):
IN Office
0 Other
7. Volume of wastewater to be allocated
for this particular project:
allocations
0 gallons per day
*Do not include previously permitted
,
8. If the permitted flow is zero, indicate
why:
be permitted
in
of existing
in subsequent permits
Permit No.
that connect to this line
expected
►� Interceptor Line - Flow will
❑ Flow has already been allocated
❑ Rehabilitation or replacement
sewer with no new flow
FTA 02/03 - Rev. 3 04/05
ST-TRACK APPLICATION for GRAVITY SEWERS, PUMP STATIONS, AND FORCE MAINS PAGE 4
3
• ` 9. Provide the wastewater flow calculations used in determining the permitted flow in accordance with 15A NCAC 2H
.0219(1) for Item 13(7) or the design flow for line or pump station sizing if zero flow in the space below. Values other than
that in 15A NCAC 2H .0219(1)(1-2) must be supported with actual water or wastewater use data in accordance with 15A
NCAC 2H .0219(1)(3).
•
Interceptor line.
10. Summary of Sewer Lines to be Permitted (attach additional sheets if necessary)
S
Size (inches) € Length (feet) Gravity or Force Main
s ; (use the pull down menu)
18 800
Gravity
€
r
•W
-1
Z. ; .
L I
r F
Z ENTER TOTAL LINE LENGTH IN MILES;
/
.
Lii11.° Summary of Pump Stations to be Permitted(attach additional sheets as necessary)
Z i Location !D
— • (self chosen - as shown on
Qplans for cross-reference)
r
* }
e‘
i Power Reliability Option
Design Flow Operational Point I (1- dual line feed; 2- permanent generator w/ATS; 3-
(MGD) GPM a_TDH portable generator wltelemetry; 4-wet well storage)
I
i
U. i
Z
l—
112. Does the sewer system comply with the Minimum Design Criteria for the Fast Track Permitting of Pump Stations and Force
Mains (latest version), the Gravity Sewer Minimum Design Criteria (latest version) and 15A NCAC 2H .0200 as applicable?
w i ® Yes ❑ No If no, please reference the pertinent minimum design criteria or regulation and indicate why a
a ' variance is requested. SUBMIT TWO COPIES OF PLANS, SPECIFICATIONS OR CALCULATIONS
PERTINENT TO THE VARIANCE WITH YOUR APPLICATION
m
i
13. Have the following permits/certifications
Wetland/Stream Crossings
Sedimentation and Erosion
- Stormwater?
been submitted for approval?
- General Permit or 401 Certification? 0 Yes • No ►1 N/A
Control Plan? • Yes ❑ No 0 N/A
® N/A
• Yes 0 No
' ' 114. Does this project involve aerial lines or siphons? Check if yes: •
These lines wilLbe considered.hiahnrioritv.and_must be ohecked_Qnse_exenLstLmantbs
15. Does this project have gravity sewer lines designed at minimum slopes?
= Be aware that the Division Mil not accept installed fines more than t 0% flatter than the minimum slope. Lines installed outside this tolerance should be
corrected prior to submitting the final engineering certification..
FTA 02/03 - Rev. 3 04/05
`TRACK APPLICATION for GRAVITY SEWERS, PUMP STATIONS, AND FORCE MAINS PAGE 5
;2a. Jay D. Banks, PE
Professional Engineer Name
2b. McKim & Creed
Engineering Firm
2c. 8020 Tower Point Drive
Mailing Address
2d. Charlotte
City
,2g.
Telephone
2e. NC 2f. 28227
State Zip
704 841-2588 .2h. 704-841-2567 2i. jbanks@mckimcreed.com
Facsimile E-mail
1. Use the Division's guidance document entitled, "DETERMINING STREAM CLASSIFICATIONS FOR FORM FTA 02/03
(FAST -TRACK SEWER SYSTEMS)" to collect and record the stream classification data below (attach additional sheets as
necessary). This document is available from our web site or by contacting the appropriate Division of Water Quality
regional office (see instructions for addresses) OR indicate the following:
El A Stream Classification is not needed because all parts of the project are at least 100 feet away from any down slope
waterbody; AND,
❑ A Stream Classification is not needed because the design does not depend on wet well storage as a power reliability
option for any pump station near a Class C down slope waterbody.
Location ID on Map
(self chosen - as shown on Name of
map for cross-reference) l Waterbody
1_
See Attached IN. Fork Crooked CK.'
Waterbody Stream Waterbody
County River Basin 3 Index Classification
Union Yadkin 13-17-20-1 i C
I
Submit the 8.5" x 11" COLOR topographic map as required in Instruction VI
regardless of whether a classification is provided!
Applicant's Certification:
1, Christie Putnam, PE, attest that this application for Fair Haven Off -Site Trunk Sewer
has been reviewed by me and is accurate and complete to the best of my knowledge. l understand that if all required
parts of this application are not completed and that if all required supporting documentation and attachments are not
included, this application package is subject to being returned as incomplete. Note: In accordance with North Carolina
General Statutes 143-215.6A and 143-215.68, any person who knowingly makes any false statement, representation, or
ification in any application shall be guilty of a Class 2 misdemeanor which may include a fine not to exceed $10,000
civil penalties up to 5,000 per violation.
Signing Official Signature
2. Professional Engineer's Certification:
Date
I attest that this application for Fair Haven Off -Site Trunk Sewer has been reviewed by me
and is accurate, complete and consistent with the information in the engineering plans, calculations, and all other
supporting documentation to the best of my knowledge. 1 further attest that to the best of my knowledge the proposed
design has been prepared in accordance with the applicable regulations, Gravity Sewer Minimum Design Criteria for
Gravity Sewers adopted February 12, 1996, and the Minimum Design Criteria for the Fast -Track Permitting of Pump
Stations and Force Mains adopted June 1, 2000 and the watershed classification in accordance with Division guidance.
Although certain portions of this submittal package may have been developed by other professionals, inclusion of these
materials under my signature and seal signifies that 1 have reviewed this material and have judged it to be consistent with
the proposed design. Note: In accordance with NC General Statutes 143-215.6A and 143-215.68, any person who
knowingly makes any false statement, representation, or certification in any application shall be guilty of a Class 2
misdemeanor which may include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation.
` twiterr�ii-
• • • SEAL •
'407
••. G1 ••
•••.
•.....,g �c
�4y D. BAN :%
6124 OS
Seal, Signature & Date
•
FTA 02/03 - Rev. 3 04/05
Name: MATTHEWS
Date: 3/812005
Scale: 1 inch equals 2000 feet
080 ° 39' 0.00"` 080' 38' 0 00"
Location' 035°06'01.6" N 080°38'52.4" W
Caption: Fair Haven Off -Site Trunk Sewer
Copyright (C) 1 97, Maptech, Inc,
Program Category
NULL
Permit Type
Primary Reviewer
Permitted Flow
Facility
Facility Name
Central Files: APS_ SWP_
07/15/05
Permit Tracking Slip
Status Project Type
Version Permit Classification
Permit Contact Affiliation
Major/Minor Region
Location Address County
Owner
Facility Contact Affiliation
Owner Name
Dates/Events
Scheduled
Orig Issue App Received Draft Initiated Issuance
Outfail
Owner Type
Owner Affiliation
Public Notice Issue
Effective Expiration
Waterbody Name Stream Index Number
Current Class Subbasin
UNION COUNTY PUBLIC WORKS
400 N. Church Street
Monroe, NC 28112-4804
704/296-4210
Fax 704/296-4232
To: NC Department of Environment and Natural Resources
Mooresville Regional Office
610 East Center Avenue
Suite 301
Mooresville, N.C. 28115
Attention:
;1'V� TTAL
U0 6N':;:' - _ ,:nttl. OFFICE
VED
Regarding: Sanitary Sewer to serve Fairhaven Offsite Trunk Sewer
We are sending you: ❑ Copy of letter ['Plans ❑ Prints ❑ Shop Drawings
Other
JUN 3 0 2005
_ • Dam f 05
Copies
Date
No.
Description
1
6/24/05
Original Non Discharge Permit Application
1
6/24/05
Copy of Non Discharge Permit Application
1
6/17/05
20305
Check for $400.00 (Application Fee)
k
These are transmitted as checked below:
® For approval ❑ For your use ❑ As requested ❑ For review and comments
Remarks:
Signed:
Received by: Date:
(..)F'� =F,g• Michael F. Easley, Governor
Wiliam G. Ross Jr., Secretary
C North Carolina Department of Environment and Natural Resources
O -c
June 27, 2006
Union County Public Works
400 North Church Street
Monroe, North Carolina 28112-4804
SUBJECT: Sun Valley Commons
Permit No. WQ0029042
Wastewater Collection System Extension
Final Engineering Certification
Dear Permittee:
Alan W. Klimek, P.E., Director
Division of Water Quality
The Division received a final engineering certification for the subject project on June 19, 2006. A full
review of the certification materials may or may not be conducted. It is assumed that receipt'of
this certification indicates compliance with all regulations, design criteria and the permit. Please be
reminded that the Permittee is responsible for keeping a copy of the final record drawings for the
life of the project. If you have not received a copy, please contact your consultant immediately to
obtain a copy.
You are receiving this letter because the Division has you listed as the responsible party. If this
permitted system is no longer owned by you, please complete Form PNOCF-S as this permit is not
automatically transferable. Form PNOCF-S can be downloaded from
http://h2o.enr.sfafe.nc.us/ndpu/ndpuaor. s.html#Sewer.
If you have any questions concerning this document or the completion of Form PNOCF-S (if
necessary), please contact Ms. Dee Browder at the letterhead address or via E-mail at
dee.browder@ncmail.net. •
kl t D. Rex Gleason, P.E.
Surface Water Protection Regional Supervisor
Enclosure
Cc: John H. Ross {no enclosures)
Surface Water Protection Section Central Files (certification page only)
NorthCaroiina
!atllra116'
Pretreatment, Emergency Response and Collection Systems Unit Internet http://h2o.enr.nc.state.us/ndpu
1617 Mail Service Center, Raleigh, NC 27699-1617 An Equal opportunity Action Employer
Telephone (919) 733-5083 Fax (919) 733-0059 50% recyced/10% post -consumer paper
Pr,
Track Engineering Certification
Permit No. WQ0029042 MODIFICATION
February 14, 2006
Complete and submit this form to the permit issuing regional office with the following:
• One copy of the project record drawings (plan & profile views of sewer lines) of the wastewater collection
system extension
• Supporting design calculations (selected pumps, system curve, operating point, available storage if portable
generator(s) or storage greater than longest past three year outage reliability option selected) for any pump
stations permitted as part of this project
• Changes to the project should be clearly identified on the record drawings or in written summary form. Permit
modifications are required for any chances resulting in non-compliance with this permit, regulations or
minimum design criteria.
This project 'shall not be considered complete nor allowed to operate until this Engineer's Certification and all
required supporting documentation have been received by the Division. Therefore, it is highly recommended
that this certification be sent in a manner that provides proof of receipt by the Division.
ENGINEER'S CERTIFICATION
❑ Partial C] Final
I, TS& \E"\.1D53 , as a duly registered Professional Engineer in the State of North Carolina, having
been authorized to observe (j periodically, ❑ weekly, ❑ full time) the construction of the Sun Valley Commons
Sewer Extension, Union County project for the Permittee hereby state that, to the best of my abilities, due care
and diligence was used in the observation of the construction such that the construction was observed to be built
within substantial compliance of this permit; 15A NCAC 2H .0200; the Division of Water Quality's (Division)
Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design
Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and
other supporting materials.
North Carolina Professional Engineer's
seal, signature, and date:
SEND THIS FORM & SUPPORTING DOCUMENTATION
WITH REQUIRED ATTACHMENTS TO THE FOLLOWING ADDRESS
MOORESVILLE REGIONAL OFFICE
SURFACE WATER PROTECTION
610 EAST CENTER AVENUE, SUITE 301
MOORESVILLE NC 28115
The Permittee is responsible for tracking aii partial certifications up until a final certification is received. Any
wastewater flow made tributary to the wastewater collection system extension prior to completion of this
Engineer's Certification shall be considered a violation of the permit and shall subject the Permittee to appropriate
enforcement actions.
C
UNION COUNTY PUBLIC WORKS gj°'��
400 N. Church Street
Monroe, NC 28112-4804 p,`"
704/296-4210
Fax 704/296-4232 TRA NSMI T TA L
To: Mooresville Regional Office
Water Quality
610 East Center Ave. Suite 301
Mooresville NC 28115
Attention: Dee Browder
Date: 6/16/06
Regarding: Record Drawings and Engineer's Certification for Sewer to serve Sun Valley Commons
(Final Certification)
We are sending you: ❑ Copy of letter ® Plans ❑ Prints ❑ Shop Drawings
® Other
Copies
Date
No.
Description
1
6/12/06
Record Drawings
1
6/12/06
Engineers Certification for Sewer (W00029042 Modification)
''. wdD NATURAL. r 2":URCES
OQREStis LL t ..,._:u, 14 I.. i:rrtL
r..:1 ' a
,i,. ."
l'''i JUN ' c 200'..
These are transmitted as checked below:
❑ For approval ® For your use ❑ As requested ❑ For review arggunfits a SECTIolvi
Remarks:
Signed:
Received by: Date: