SUBJECT: Compliance Inspection Report
Freemason WTP
NPDES WW Permit No. NC0007552
Chowan County
Dear Mr. Gooden:
The North Carolina Division of Water Resources conducted an inspection of the Freemason WTP on
11/02/2021. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0007552. The findings and comments
noted during this inspection are provided in the enclosed copy of the inspection report entitled
"Compliance Inspection Report".
If you should have any questions, please do not hesitate to contact me with the Water
Quality Regional Operations Section in the Washington Regional Office at 252-946-6481 or via email at
robert.e.bullock@ncdenr.gov.
Cc: Laserfiche
Sincerely,
Robbie Bullock, Environmental Specialist II
Water Quality Regional Operations Section
Washington Regional Office
Division of Water Resources, NCDEQ
DE
North Carolina Department of Envlronmental Quality I Dlvlslon of Waler Resources
Washington Regional Office 1 943 Washington Square Mall I Washington, North Carolina 27889
252.946.6481
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection
1 IN I 2 IL I 3 I NC0007552 111 121 21/11/02 117
Type
181 O I
11111111111
Inspector Fac Type
191 S I 201 I
Lu
21111111 111111111111111111 I I IIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
671 I 70I3 I 711 1 72 I N I 73I I 74 71
I I
I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Freemason WTP
W Freemason St
Edenton NC 27932
Entry Time/Date
11:OOAM 21/11/02
Permit Effective Date
18/08/01
Exit Time/Date
12:OOPM 21/11/02
Permit Expiration Date
23/07/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Anne -Marie Knighton,PO Box 300 Edenton NC 279320300/Town
Manager/252-482-7352/2524827377 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Facility Site Review Effluent/Receiving Wate Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Robert E Bullock DWR/WARO WQ/252-948-3843/ 11/3/2021
``
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
3I
NPDES yr/mo/day
NC0007552 111 121 21 /11 /02
117
Inspection Type
18 [j
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The review period for this inspection was April 2017 through October 2021. Two Notice of
Deficiencies were issued over the review period.
Grab samples are taken as required in the NPDES permit. The facility currently only samples the
cation exchange softeners. Effluent samples need to be representative of the actual discharge and
include the pressure vessels (PurolitePlus/9218) and the cation exchange softeners.
The facility is currently reporting flow from one backwash on the DMR. Total daily discharge needs to
be reported on the DMR.
During the recent upgrade Mag Meters were installed to measure effluent flow. Effluent flow meters
are required to be calibrated annually with a maximum deviation of 10%.
The NPDES permit has a Chloride limit of 230 mg/I that will become effective on August 1, 2022. A
review of the DMR's showed that the facility currently cannot meet the Chloride limit of 230 mg/I. The
effluent discharge will need to be meet permitted limits of 230 mg/I by August 1, 2022.
Page# 2
Permit: NC0007552
Inspection Date: 11/02/2021
Owner - Facility: Freemason WTP
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable El El El
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new El ❑ ❑
application?
Is the facility as described in the permit? • El El El
# Are there any special conditions for the permit? • El El El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment: The current permit is set to expire on July 31, 2023
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? • ❑ ❑ ❑
Are all other parameters(excluding field parameters) performed by a certified lab? • ❑ ❑ ❑
# Is the facility using a contract lab? • El ❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 • ❑ ❑ ❑
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? El ❑ • ❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? El El • El
Comment: PH, Temperature, Chlorine and Dissolved Oxygen analysis is contracted with JLA Labs
with all other samples sent to Environment 1 for analysis.
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? • ❑ ❑ ❑
Is all required information readily available, complete and current? • ❑ ❑ ❑
Are all records maintained for 3 years (lab. reg. required 5 years)? • ❑ ❑ ❑
Are analytical results consistent with data reported on DMRs? • ❑ ❑ ❑
Is the chain -of -custody complete? ■ ❑ ❑ ❑
Dates, times and location of sampling ❑
Name of individual performing the sampling ❑
Results of analysis and calibration ❑
Page# 3
Permit: NC0007552
Inspection Date: 11/02/2021
Owner - Facility: Freemason WTP
Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Dates of analysis ❑
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
• ❑ ❑ ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
▪ ❑ ❑ ❑
❑ ❑ • ❑
Comment: The July 2021 DMR was spot checked for accuracy. The facility is currently reporting
flow from one backwash on the DMR. Total daily discharge needs to be reported on the
DMR.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
• ❑ ❑ ❑
❑ • ❑ ❑
▪ ❑ ❑ ❑
❑ ❑ • ❑
Comment: During the recent upgrade Mag Meters were installed to measure effluent flow. Effluent
flow meters are required to be calibrated annually with a maximum deviation of 10%.
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ • ❑ ❑
Is sample collected below all treatment units? ❑ • ❑ ❑
Is proper volume collected? • ❑ ❑ ❑
Is the tubing clean? ❑ ❑ • ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 • ❑ ❑ ❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • ❑ ❑ ❑
representative)?
Page# 4
Permit: NC0007552
Inspection Date: 11/02/2021
Owner - Facility: Freemason WTP
Inspection Type: Compliance Evaluation
Effluent Sampling Yes No NA NE
Comment: Grab samples are taken as required in the NPDES permit. The facility currently only
samples the cation exchange softeners. Effluent samples need to be representative of
the actual discharge and include the pressure vessels (PurolitePlus/9218) and the
cation exchange softeners.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: No adverse conditions were noticed on the day of inspection
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ • ❑
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, MODE
and sampling location)?
Comment:
Page# 5