HomeMy WebLinkAboutNC0041246_Compliance Evaluation Inspection_20211028ROY COOPER
GwenTor
ELIZ ABETH 5, BISER
scollop
S. DANIEL SMITH
D recta'
Mr. Randy Putnam
Maintenance Director
P.O. Box 400
Lincolnton, NC 28092
Dear Mr. Putnam:
NORTH CAROLINA
Environmental Quality
October 28, 2021
Subject: Compliance Evaluation Inspection
West Lincoln High School WWTP
NPDES Permit No. NC0041246
Lincoln County
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted
at the subject facility on October 19, 2021, by Ori Tuvia. Please advise the staff involved with this
NPDES Permit by forwarding a copy of the enclosed report.
The report should be self-explanatory; however, should you have any questions
concerning this report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at
ori.tuvia@ncdenr.gov.
Cc: NPDES, MRO Files (Laserfiche)
Sincerely,
DocuSigned by:
for
F161FB69A2D84A3...
W. Corey Basinger
Regional Supervisor
Mooresville Regional Office
Division of Water Resources
North Carolina Drpartrncnt of Erriranmcnial Quality I Dirisbon of Watcr Rcsourccs
Pitooresirillt.Fregionai office 1610 £avt Center Avenue. State 30] 1 Mooresville, North CaratIna 29115
70.4.663.16.11
United States Environmental Protection Agency
E PA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code
1 IN I 2 IL
21 1 1 1 1
NPDES yr/mo/day Inspection
I 3 I NC0041246 111 121 21/10/19 117
Type
1810I
I I 1 1 1
Inspector Fac Type
1 9 I S I 2011
1 1 1 1 1 11 1 1 1 I I I 1 1 1 1 1 1 I I I I I
1 11
1 1 1 I 1 r6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
67I1.0 I 70I4 I 71IN I 72 I N I 73I 1 74 751
I I 1
I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
West Lincoln High School
172 Shoal Rd
Lincolnton NC 28092
Entry Time/Date
09:45AM 21/10/19
Permit Effective Date
21/07/01
Exit Time/Date
10:15AM 21/10/19
Permit Expiration Date
25/07/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Jonathan David Gragg/ORC/828-396-4444/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Randy A Putnam,PO Box 400 Lincolnton NC 280920400//704-732-5561/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and
OriATuvia
Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers
Date
10/28/2021
—DocuSigned by:
—_ DWR/MRO WQ/704-663-1699/
`— BB057A2DE017498..
Signature of ManAgarai,ehgpviewer
Andrew Pitner,4*.4414/
Agency/Office/Phone and Fax Numbers Date
H P+ r•BWR/MRO WQ/704-663-1699 Ext.2180/ 10.28.21
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
NPDES yr/mo/day
31 NC0041246 111 121 21/10/19
I17
Inspection Type
18 [j
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page# 2
Permit: NC0041246
Inspection Date: 10/19/2021
Owner - Facility: West Lincoln High School
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new El El ❑
application?
Is the facility as described in the permit? • El El El
# Are there any special conditions for the permit? El • El El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • El El El
Comment: The subject permit expires on 7/31/2025
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
•
• ❑ ❑ ❑
• ❑ • ❑
❑ ❑ • ❑
▪ ❑ ❑ ❑
Comment: The records reviewed during the inspection were organized and well maintained.
DMRs, COCs, and calibration logs were reviewed for the period April 2021 through
October 2021.
Page# 3
Permit: NC0041246
Inspection Date: 10/19/2021
Owner - Facility: West Lincoln High School
Inspection Type: Compliance Evaluation
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Comment: Water Tech Labs (#50) performs all necessary analyses
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ ❑ • ❑
Is sample collected below all treatment units? • ❑ ❑ ❑
Is proper volume collected? • ❑ El El
Is the tubing clean? El ❑ • ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 ❑ El • ❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • El El El
representative)?
Comment: The subject permit requires grab sampling.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • El El El
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑•❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The facility appeared well maintained and operated at the time of the inspection.
Lincoln County Schools performs all maintenance at the facility.
Bar Screens Yes No NA NE
Type of bar screen
a.Manual •
b.Mechanical El
Are the bars adequately screening debris? El El • El
Is the screen free of excessive debris? El El • El
Is disposal of screening in compliance? ❑ El • ❑
Is the unit in good condition? El El • El
Page# 4
Permit: NC0041246
Inspection Date: 10/19/2021
Owner - Facility: West Lincoln High School
Inspection Type: Compliance Evaluation
Bar Screens Yes No NA NE
Comment: Bag filters are used to remove grit and debris.
Septic Tank
(If pumps are used) Is an audible and visual alarm operational?
Is septic tank pumped on a schedule?
Are pumps or syphons operating properly?
Are high and low water alarms operating properly?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The septic tank is pumped on an annual basis by Stanley Environmental Solutions.
Sand Filters (Low rate)
(If pumps are used) Is an audible and visible alarm Present and operational?
Is the distribution box level and watertight?
Is sand filter free of ponding?
Is the sand filter effluent re -circulated at a valid ratio?
# Is the sand filter surface free of algae or excessive vegetation?
# Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1)
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: The flow meter was last calibrated on March 11, 2021 by Clear Water Inc.
Disinfection - UV
Are extra UV bulbs available on site?
Are UV bulbs clean?
Is UV intensity adequate?
Is transmittance at or above designed level?
Is there a backup system on site?
Is effluent clear and free of solids?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ •
• ❑ ❑ ❑
Page# 5
Permit: NC0041246
Inspection Date: 10/19/2021
Owner - Facility: West Lincoln High School
Inspection Type: Compliance Evaluation
Disinfection - UV
Pump Station - Effluent
Is the pump wet well free of bypass lines or structures?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
Comment:
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: The Effluent pipe was not examined during the inspection
Yes No NA NE
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
❑ ❑ ❑ •
Page# 6