Division of Water Quality
August 5, 2003
SUBJECT: July 22, 2003 Compliance Evaluation Inspection -
Town of Troy
Troy WWTP
Permit No: NC0028916
Montgomery County
Dear Mr. Walls:
Enclosed please find a copy of the Compliance Evaluation Inspection form from the inspection conducted
on July 22, 2003. The Compliance Evaluation Inspection was conducted by Belinda S Henson of the
Fayetteville Regional Office. The facility was found to be in Compliance with permit NC0028916. The
cooperation of Mr. Stephen Jarman, Grade III ORC was appreciated. As a reminder preservation of the
Waters of the State can only be acquired through consistent NPDES permit compliance.
Please refer to the enclosed inspection report for'additional observations and comments. If you or your staff
have any questions, please call me at 910-486-1541.
Sincerely,
4.
Belinda S Henson
Environmental Chemist
cc: Stephen Bryan Jarman, ORC
Central Files
Fayetteville Files
AtA
Ni f)El dyt
NCDENR Division of Water Quality 225 Green Street -Suite 714 Fayetteville, NC 28301-50431 (910)486-1541 Telephone
(910)486-0707 Fax
Customer Service1 877 623-7748
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection
1 DI 2': Li3I NC0028916 111 12 1 03/07/22 1 17
Type Inspector Fac Type
18 I 19 I t 20 LJ
�J
Remarks
21111111IIII111111111111111111111111111111111111166
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ----------------------Reserved---------- --------
67 I 2 .5 169 70 lJ 1, I 71 t �, tyl 72 1,,, LJ t 731
L 174 751I 111 180
11
Section B: FacilityliData
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Troy WWTP
650 Glen Road
Troy NC 27371
Entry Time/Date
10:15 AM 03/07/22
Permit Effective Date
01/02/01
Exit Time/Date
03:00 PM 03/07/22
Permit Expiration Date
04/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Stephen Bryan Jarman/ORC/910-572-5196/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
E Gray `r:alls,444,North Main St Troy NC 27371//910-572-3661/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The contract company Meritech, Inc operated this facility at the time of the inspection. As of August 1,
2003, the Town will begin operation of the wastewater treatment plant.
A manual bar screen and a rotameter are used to remove trash and debris at the headworks of the plant.
The rotameter operates by an ultrasonic sensor that senses the flow depth and automatically operates.
A11 screenings are disposed of through the Uwharrie Environmental Landfill.
(cont.)
The grit removal system appeared to be
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
ci
.wry 4. c Belinda S Henson � � .� • ✓ r��'G1`'' FRO WQ//910-468-1541/910-486-0707 �-5 -b3
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
3I
NPDES
NC0028916
11 12
yr/mo/day
03/07/22
117
Inspection Type
18 Lc j
(cont.) 1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
operational. It is operated twice a day. All, grit is .disposed of through the Uwharrie Environmental
Landfill.
Caustic is added to the influent for pH adjustment. Candor Hosiery is moving some of their operation to
the Town of Robbins facility which has caused a decrease in facility influent pH as per staff.
The ORC for this facility is Stephen Jarman, Grade III operator and Pat Merritt is the Backup Operator.
**AS A REMINDER THE NEW ORC AND BACKUP OPERATOR MUST COMPLETE AN APPLICATION AND SUBMIT TO TECHNICAL
TRAINING AND CERTIFICATION UNIT IN RALEIGH AND CC THE FAYETTEVILLE REGIONAL OFFICE.**
The influent composite sampler refrigerator temperature was 3.5 degrees Celsius. The acceptable
temperature range of samples during storage and for stored sample extracts, is 1.0 to 4.4 degrees
Celsius. Ref: Federal Register, July 1, 1995; 40 CFR 136; Table II.'
The oxidation ditches appeared to be operating efficiently. The ditches operate in series. An anoxic
zone is used to reduce nitrogen and phosphorus. The facility analyzes Mixed Liquor Suspended Solids
(MLSS) on.a monthly basis. The most recent results are approximately 3500 mg/L.
1
The clarifiers sludge depths were the following: Clarifier 41: 1 foot with a tank depth of mil feet and
Clarifier f2: 1.5 feet with a tank depth of 11 feet.
The'facility has completed installation of the UV. system for disinfection and has been on line for
approximately one month. The facility continues to add chlorine until the UV system testing has been
completed. The UV system has 2 banks with 4 bulbs per bank. The system is self cleaning which injects
a soap•cleaner and then wipers are activated. The cleaning occurs every 4 hours. Grease balls are
manually removed from the effluent before it reaches the UV system. Grease balls are removed by a net
and placed on a tray and disposed of through the county landfill. Plans are to utilize chlorine gas as a
backup system for disinfection. Plans are to relocate the effluent flow from the UV system and to
directly discharge to the stream and bypass the chlorine contact tank.
The effluent appeared to be free of solids.
The effluent composite sampler refrigerator temperature was 0.5 degrees Celsius. The tubing was clean
and adequately maintained.
The effluent flow meter Milltronics OCM III was calibrated July 16, 2003 by facility staff.
The digester appeared to be operating adequately. The sludge holding tank appeared to have less than 1
foot in it. A land application event had occurred recently and the contract company Synagro had
basically emptied the tank. The facility normally wastes 50-60 inches/week which is approximately 48,000
gallons. Biosolids are land applied under permit # WQ0001240.
Two lagoons are located on site. The largest lagoon is used as a equalizing lagoon for high flows. The
smaller lagoon is no longer utilized and the Town is in the process of filling it in.
The following NPDES permit required parameters are analyzed by facility staff: pH, Temperature,
Dissolved Oxygen and Chlorine Residual under field parameter certification # 136. All other required
parameters are analyzed by Meritech, Inc.
Laboratory records were reviewed for the month February 2003 and compared to Discharge Monitoring Reports
(DMR). All records reviewed appeared to be accurate.
A compliance evaluation for the period April 2002 through April 2003 did not reveal any monthly
violations. The facility should be commended for their continued compliance of their NPDES permit.
3
NPDES
NC0028916
11 12
yr/mo/day
03/07/22
117
Inspection Type
18i„i •
(cont.) 2
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The ORC log was reviewed and appeared to be adequate.
The facility continues progressing with their SCADA system which will further assist with daily
operations.
rcegivnai FIGI4-•---
_ `�
lame of site to be Inspected: To "3 r1 04 I ir'� y Date: - � ��.� �.
Inspector: 3eJ.;rin1.a: 5. G/enrsor
JPDES #: /1/CrC) 0 '�.$ `I i L, Region: 'ro y e,
, Circle the parameter or parameters performed at this site.
'ield certification # (if applicable): 1?)
tesidual Chlo r in Settleable Solids p' D Conductivity, Temperatur
I. Instrumentation:
Does the facility have the equipment necessary to analyze field parameters as circled above?
A pH meter
A Residual Chlorine meter Yes
es•�
;. DO meter
t, A Cone for settleable solids Yes No
5. A thermometer or meter that measures temperature. Yes
No
No 4CCuyyt ET 5
No .04? a o:o 0
No Y5- 5 S
3. Conductivity meter
III. Calibration/Analysis:
1. Is the pH meter calibrated with a 2 buffers and
checked with a third buffer each day of use?
2. For Total Residual Chlorine, is a check standard :Yei
analyzed each day of use?
3. Is the air calibration of the DO meter performed es
each day of use?
4. For Settleable Solids, is 1 liter of sample Yes
settled for 1 hour?
Yes No
5. Is the temperature measuring device calibrated
annually against a certified thermometer?
6. For Conductivity, is a calibration standard
analyzed each day of use?
Yes
No
No
No
No
No
No
IV. Documentation:
1. Is the date and time that the sample was collected documented?&e7 No
2. Is the sample site documented? Ye `) No
3. Is the sample collector documented? cYes) No
4. Is the analysis date and time documented? C No
5. Did the analyst sign the documentation? Yes No
6. Is record of calibration documented? qes� No
7. For Settleable,Solids, is sample volume_ and
1 hour time settling time documented? Yes
8. For Temperature, is the annual calibration of
the measuring device documented? S'
Comments:
No
Please submit a copy of this completed form to the Laboratory Certification Program.
DWQ Lab Certification
Chemistry Lab•
Courier # 52-01-01
FIELD INSPECTOR CHECKLIST REV: 04/23/2002
Section 0: 54mm2ry or in ings/Cor ments
Brief Facility Description:
A .84 MGD WWTP consisting of the following: dow equalization.mechanical bar screen, grit
removal, dual oxidation ditches, dual secondary clarification, sludge digester, sludge holding,
tank, UV di*infection and chloringtion/dechlorination(back-up).
FACILITY SITE REVIEW
es No N/A 1. Treatment units properly operated and maintained.
es No N/A 2. Standby power or other equivalent provision provided.
SsP No N/A 3. Adequate alarm system for power or equipment failure available.
4. Sludge disposal procedures appropriate:
No N/A a. Disposal of sludge according to regulations
j7 No N/A b. State approval for sludge disposal received.
No N/A 5. Sufficient sludge disposed of to maintain treatment process equilibrium.
&e ~ No N/A 6. The ORC and Backup Operator are officially designated with
NCDENR/DWQ Training and Certification Unit.
7e- No N/A 7. Adequate spare parts and supplies inventory maintained.
es) No N/A 8. Plant has general safety structures such as rails around or covers over
tanks, pits, or wells.
No N/A 9. Plant is generally clean, free from open trash areas.
10. Screening:
.el No N/A a. Manual
• No N/A b. Mechanical
Yes 'oD N/A c. Buildup of debris
No N/A d. Screenings properly disposed of.
11. Grit Removal:
Yes N N/A a. Excessive organic content in the grit chamber
Yes 6Is) N/A b. Excessive odors
c� No N/A c. Grit properly disposed of.
Page 2
12. Primary clarifier:.
Yes No a. Excessive gas bubbles
Yes No �/A b. Black and odorous wastewater
Yes No N/A c. Poor suspended solids 'removed ,
Yes No N/A d. Excessive buildup of solids in center well of circular clarifier
Yes No N/A e. Weirs level
Yes No N/A f. Weir blockage
Yes No N/A g. Evidence of short circuiting
Yes No N/A h. Lack of adequate scum removal
Yes No N/A i. Excessive floating sludge
Yes No N/A j. Broken sludge scraper.
13. Trickling Filter:
Yes No ei a. Trickling filter ponding(indicating clogged media)
Yes No N/A b. Leak at center column of trickling filter's distribution arms
Yes No `. N/A c. = Uneven distribution of flow 'on trickling filter surface
Yes No N/A d. Uneven or discolored growth
Yes No N/A e. Excessive sloughing of growth
Yes No N/A f Odor
Yes No N/A g. Clogging of trickling filter's distribution arm orifices
Yes No N/A h. Filter flies, worms,or snails; - -
14. Activated. Sludge Basins/Oxidation Ditches:
Yes N/A a. Dead spots
Yes No tN/ ' ' b. Failure of surface aerators
Yes @' N/A c. Air rising in clumps
Yes Eta' N/A d. Dark foam or bad color
Yes N/A e. Thick billows of white, sudsy foam
Yes No la ff. Air rising unevenly
Yes No ( g. Excessive air leaks in compressed air piping.
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
15. Stabilization Ponds/Lagoons:
a. Excessive weeds including duckweed in stabilization ponds
b. Dead fish or aquatic organisms
c. Buildup of solids around influent pipe
d. Excessive scum on surface.
Page 3
Yes (15} N/A
Yes o") N/A
Yes N/A
Yes o N/A
Yes N/A
Yes 'OE- N/A
No N/A
Yes N/A
Yes J N/A
Yes CTo JN/A
16. Secondary Clarifier:
Excessive gas bubbles on surface
Level overflow weirs
Weir blockage
Evidence of short circuiting
Excessive buildup of solids in center well of circular clarifier
Pin floc in overflow
Effective scum rake
Floating sludge on surface
Excessive high sludge blanket
Clogged sludge withdrawal ports, on secondary clarifier.
17.
Yes No Nit
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes iSO N/A
Yes N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
No N/A
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
Filtration:
a. Filter surface clogging
b. Short filter run
c. Gravel displacement of filter media
d. Loss of filter media during backwashing
e. Recycled filter backwash water in excess of 5 percent
f. Formation of mudballs in filter media.
18. Chlorination Unit:
a. Sludge buildup in contact chamber
b. Gas bubbles
c. Floating scum and/or solids
d. Adequate ventilation of chlorine feeding room and storage area
e. NIOSH-approved 30 minute air pack
f. All standing chlorine cylinders chained in place
g. All personnel trained in the use of chlorine
h. Proper chlorine feed, storage, and reserve supply.
19. Ultraviolet radiation disinfection present and in use.
20.
Yes No N/A
Yes No N/A
Yes No N/A
Yes to N/A
Yes N/A
Yes No N/A
Yes No N/A
Dechlorination:
a. Proper storage of sulfur dioxide cylinders
b. Adequate ventilation of sulfur dioxide feeding room
c. Automatic sulfur dioxide feed or feedback control operating
properly.
21. Aerobic Digester:
a. Excessive foaming in tank
b. Noxious odor
c. Mechanical aeration failure
d. Clogging of diffusers.
Page 4
Yes No
Yes No N/A
Yes N/A
Yes N/A
Yes e N/A
Yes N/A
Yes No N/A
N/A
Yet No N/A
Yes No A`'
Yes No N/A
Yes No N/A
Yes No N/A
22. Anaerobic Digester:
a. Floating cover tilting
b. Gas burner operative
23. Sludge Drying and/or disposal:
a. Poor sludge distribution on drying beds
b. Vegetation in drying beds
c. Dry sludge remaining in drying beds
d. Dry sludge stored on site
e. Filtrate from sludge drying beds returned to front of plant
f. Sludge disposal through county landfill.
g. Sludge -land applied.
24. Filter Press:
a. High level of solids in filtrate from filter presses or vacuum filters
b. Thin filter cake caused by poor dewatering
c. Sludge buildup on belts and/or rollers of filter press
d. Excessive moisture in belt filter press sludge cake.
25. Polishing Ponds or Tanks:
Yes No a. Objectionable odor, excessive foam, floating solids, or oil sheens on
Yes No N/A
Yes No N/A
Y) No N/A
Yes . o' N/A
Yes No N/A
W No N/A
Yeg No N/A
fes?No N/A
Yes �c'e N/A
Yes No
Yes_.;g6% N/A
s No N/A
b.
c.
water surface
Solids or scum accumulations in tank or at side of pond
Evidence of bypassed polishing ponds or tanks because of low
capacity.
26. Plant Effluent:
a. Excessive suspended solids, turbidity, foam, grease, scum, color, and
other macroscopic particulate matter present
b. Potential toxicity (dead fish, dead plant at discharge)
c. Outfall discharge line easily accessible.
27. Flow Measurement:
Proper placement of flow measurement device
Flow meter calibrated
Buildup of solids in flume or weir
Broken or cracked flume or weir
Clogged or broken stilling wells
Weir plate edge corroded or damaged
Flow measurement error less than 10%.
a.
b.
c.
d.
e.
f.
g.
Page 5
No N/A
C.61,§) No N/A
'e! No N/A
Yes No N/A
28. Sampling:
a. Sampling and analysis completed on parameters specified by permit
b. Composite sample temperatures maintained at 4 degrees Celsius or
less (but above freezing) during sampling
c. Contract laboratory used for sample analysis
d. Effluent composite samples obtained are flow proportional.
RECORDKEEPING AND REPORTING
e7 No N/A 1. Records and reports maintained as required by permit.
es' No N/A 2. All required information available, complete, and current.
Ye ' No N/A 3. Records maintained for 3 years and all sludge records maintained for 5
years.
es No N/A 4. Analytical results consistent with data reported on DMRs.
5. Sampling and analyses data adequate and include:
es ?No N/A a. Dates, times, and location of sampling
No N/A b. Name of individual performing sampling
No N/A c. Results of analyses and calibration
No. N/A d. Dates of analyses
es, No N/A e. Name of person performing analyses.
6. Monitoring records adequate and include:
Yes No N/A a. Monitoring charts kept for 3 years
VD No N/A b. Flowmeter calibration records kept for 3 years.
Yes No N/A 7. The pH meter is calibrated daily with two buffers and checked with a
third buffer and properly documented.
Yes1 No N/A 8. Expiration dates of pH buffers adequate.
Yes No N/A 9 All thermometers used in NPDES permit reporting is calibrated
annually with an NIST certified thermometer or a traceable
thermometer annually and documented.
Ye o N/A 10. The following NPDES permit required parameters are analyzed on site:
pH, Temperature, Dissolved Oxygen and Chlorine Residual.
Page 6
Yes No N/A
Yes No
Yes No (N/—)
No
Yes No
(Yes No
Yes No
N/A
N/A
N/A
Yes No Q'
e� No N/A
Yes No
es No N/A
Yes) No N/A
Yes No N/A 20.
Yes No N/A 21.
Yes No N/A
CY) No N/A
Yes . No N/A 24.
11. The NPDES permit required parameter Total Chlorine Residual is
analyzed by approved method.
12. BOD incubator temperature maintained at 20 +/- 1 Degrees Celsius
and the temperature maintained in a log for every day of operation.
13. Fecal coliform incubator maintained at 44.5 +/- 0.2 Degree Celsius and
the temperature maintained in a log for every day of operation.
14. Plant records adequate and include:
a. O & M Manual
b. "As -built" engineering drawings
c. Schedules and dates of equipment maintenance repairs
d. Equipment data cards.
15. Permittee is meeting compliance schedule.
16. DMRs complete and include all NPDES permit required parameters.
17. The facility has a permitted flow greater than 5 MGD and is required
to operate seven days per week 24 hours a day.
18. ORC visitation logs available and current.
19. ORC certified at a level equal to orgreater than the classification of
the wastewater facility.
Backup Operator certified at one level less than the classification of
the wastewater facility or greater.
Current copy of the complete NPDES permit on site.
22. Facility description verified as contained in NPDES permit.
23. Facility analyzes process control parameters for example: MLSS,
MCRT, Settleable Solids and others that are applicable.
Industrial Waste Surveys (IWS) sent to all possible Significant
Industrial Users (SIUs) within the last five years (especially new
industries).
Revised 7/16/01
by Belinda Henson