HomeMy WebLinkAboutNC0028916_Inspection_20060601Vvn L-aolcr,
;r►� '^.,.. RQ William G. Ross Jr., Secretary
North Carolina Department of Environment and Natural Resources
r• Alan W. Klimek, P.E. Director
Division of Water Quality
June 1, 2006
Mr. E. Gray Walls
Town of Troy
444 N Main St
Troy NC 27371
SUBJECT: May 23, 2006 Compliance Evaluation Inspection
Town of Troy
Troy WWTP
Permit No: NC0028916
Montgomery County
Dear Mr. Walls:
Enclosed please find a copy of the Compliance Evaluation Inspection form from the inspection conducted
on May 23, 2006. The Compliance Evaluation Inspection was conducted by Belinda S. Henson of the
Fayetteville Regional Office. The facility was found to be in Compliance with permit NC0028916. The
cooperation of Mr. Joseph Shields, Grade III ORC was appreciated. As a reminderpreservation of the
Waters of the State can only be acquired through consistent NPDES permit compliance
Please refer to the enclosed inspection report for additional observations and comments. If you or your staff
have any questions, please call me at 910-486-1541 Ext.726.
Sincerely,
te,6,,,,,,zpo
Belinda S. Henson
Regional Supervisor
Surface Water Protection Section
cc: Joseph Edward Shields, ORC
Central Files
P ay` e r.emii raviir`
N[DENii.
NCDENR Division of Water Quality 225 Green Street -Suite 714 Fayetteville, NC 28301-50431 (910)486-1541 Telephone
(910)486-0707 Fax
Customer Service 1 877 623-7748
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection
1 I NI 2 1 51 31 NC0028916 1 11 121 06/05/23 1 17
Type Inspector Fac Type
181 cI 191 S1 20� 11
Remarks
211111111111I111111111111.11111111111111111111111166
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---- ----Reserved --
671 1 69 701 31 711 NI 721 NI "HI" 79 1 1 1 1 1 1 1 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Troy WWTP
650 Glen Rd
Troy NC 27371
Entry Time/Date
10:00 AM 06/05/23
Permit Effective Date
04/08/01
Exit Time/Date
01:00 PM 06/05/23
Permit Expiration Date
09/06/30
Name(s) of Onsite Representative(s)/Tltles(s)/Phone and Fax Number(s)
///
Joseph Edward Shields/ORC/910-572-3661/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
E. Gray Walls,444 N Main St Troy NC 27371//910-572-7841/9105723663
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review • Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date ,
Belinda S Henson XiFRO WQ//910-466-1541 Ext.726/ )- O
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page # 1
NPDES yr/mo/day Inspection Type
31 NC0028916 i11 12I 06/05/23 I17 18ICI
(cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The following NPDES permit required parameters are analyzed by facility staff:.pH, Temperature, Dissolved
Oxygen and Residual Chlorine under field parameter. certification #5350 All,other required parameters are
analyzed by Meritech, Inc. Laboratory records were reviewed forthe months April 2005, July 2005 and
December 2005 and compared to Discharge Monitoring Reports (DMRs). All records reviewed appeared to
be accurate. A compliance evaluation for the period January 2005 to March 2006 did not reveal any
violations. The facility did report during the inspection that for the month of April 2006 the following
violations were noted: BOD-weekly (14.6 mg/L result--10.5 mg/L limit) & monthly (7.2 mg/L result--7.0 rrig/L
limit, NH3 weekly (9.9 mg/L result--6.0 rng/L limit). The facility had an aerator down during this period when
the violations occurred and they did contact FRO.
Page # 2
Permit: NC0028916 Owner -Facility: TroyWWfP
Inspection Date: 05/23/2006 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? ■ n n n
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge ■ n n n
Judge, and other that are applicable?
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new application? ■ n n n
Is the facility as described in the permit? • n n ❑
# Are there any special conditions for the permit? 0 0 • n
Is access to the plant site restricted to the general public? • .n n n
Is the inspector granted access to all areas for inspection? • n n n
Comment:
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? ■ n n n
Is all required information readily available, complete and current? ■ n ❑ ❑
Are all records maintained for 3 years (lab. reg. required 5 years)? • n n n
Are analytical results consistent with data reported on DMRs? • n n n
Is the chain -of -custody complete? • n n
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration •
Dates of analysis •
Name of person performing analyses
Transported COCs
Are DMRs-complete: do they include all permit parameters? ■ n n n
Has the facility submitted its annual compliance report to users and DWQ? ■ Finn
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift? n ❑ • n
Is the ORC visitation log available and current? ■ n ❑ ❑
Is the ORC certified at grade equal to or higher than the facility classification? ■
nnn
Is the backup operator certified at one grade less or greater than the facility classification? ■ n n n
Is a copy of the current NPDES permit available on site? ■ n n n
Page # 3
Permit: NC0028916 Owner - Facility: Troy VwVTP
Inspection Date: 05/23/2006 Inspection Type: Compliance Evaluation
Record Keeping
Facility has copy of previous year's Annual Report on file for review?
Comment:
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Flow Measurement - Influent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment:
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Comment: All sludge is land applied on an annual basis. Sludge.is pumped to the
smaller digester and then to the larger one which they have added a brush aerator.
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Yes No NA NE
■ nnn
Yes No NA NE
nnn■
n nn■
nnn■
Yes No NA NE
■ ❑ ❑ ❑
■ nnn
■ nnn
n nn■
Yes No NA NE
n n■n
■ nnn
■ nnn
■ nnn
Yes No NA NE
■ ❑ ❑ ❑
■ El -nn
■ nnn
Erin ❑
■ nnn
Yes No NA NE
nn■n
n n■n
Page # 4
Permit: NC0028916 Owner- Facility: Troy VWVTP
Inspection Date: 05/23/2006 Inspection Type: Compliance Evaluation
Solids Handling Equipment
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Comment:
Pump_Station -_Effluent
Is the pump wet well free of bypass lines or structures?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
Comment:
Pump Station - Influent
Is the pump wet well free of bypass lines or structures?
Is the wet well free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
Comment: Two influent pumps were operational. The alarm system calls Gray for
pump failure and Joe for power failure.
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Yes No NA NE
nn■n
n n■n
n n■n
n n■n
n n■n
Yes No NA NE
n n.n
n n■n
n n ■ n
n n■n
n n■n
n n■n
Yes No NA NE
■ non
■ nnn
■ nnn
■ nnn
■ nnn
■ nnn
■ nnn
Yes No NA NE
n
■
■ nnn
■ nnn
Page # 5
Permit: NC0028916 Owner - Facility: Troy VWVfP
Inspection Date: 05/23/2006 Inspection Type: Compliance Evaluation
Bar Screens
Is disposal of screening incompliance?
Is the unit in good condition?
Comment: Facility has a new Jones and Adwood low flow bar screen with 1/4 inch
spacing. Screen pushes water out and debris is pushed into a dumpster that is
disposed of monthly into the Uwharrie landfill. Bar screen operates on a float system.
Grit Removal
Type of grit removal
a.Manual
b.Mechanical
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Comment: Grit removal system operates every 3 hours based on a timer. Al grit is
disposed of into the county landfill.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately %4 of the sidewall depth)
Comment: New stainless steel weirs had been placed in #2 clarifier with plans to
replace those in the other the following week. The sludge depths were 1 1/2 feet in #1
with a tank depth of 12 feet and 2 1/2 feet in #2.
Oxidation Ditches
Are the aerators operational?
Are the aerators free of excessive solids build up?
Yes No NA NE
■ nnn
■ nnn
Yes No NA NE
n
■
■ nnn
■ nnn
■ nnn
Yes No NA NE
. nnn
■ nnn
■ nnn
■ nnn
■ nnn
• nnn
■ nn.n
■ nnn
■ nnn
■ nnn
■ nnn
Yes No NA NE
■ nnn
■ nnn
Page # 6
Permit: NC0028916 Owner- Facility: Troy WWTP
Inspection Date: 05/23/2006 Inspection Type: Compliance Evaluation
Oxidation Ditches
# Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Are settleometer results acceptable (> 30 minutes)?
Is the DO level acceptable?(1.0 to 3.0 mg/I)
Are settelometer results acceptable?(400 to 800 mi/I in 30 minutes)
Comment: The MLSS results are averaging 3500 mg/L.
Disinfection - UV
Are extra UV bulbs available on site?
Are UV bulbs clean?
Is UV intensity adequate?
Is transmittance at or above designed level?
Is there a backup system on site?
Is effluent clear and free of solids?
Comment: They have a backup disinfection system with chlorine. They have self
cleaning UV system. Transmittance is input and the intensity adjusts accordingly with
this system.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an_emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Comment: Generator was not tested at the time of the inspection.
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Yes No NA NE
■ nnn
■ nnn
■ nnn
■ nnn
■ nnn
■ nnil
Yes No NA NE
■ nnn
■ nnn
■ nnn
■ nnn
■ nnn
■ nnn
Yes No NA NE
■ nnn
■ nnn
■ nnn
n ■nn
n nn■
■ nnn
■ nnn
Yes No NA NE
■ nnn
■ nnn
■ nnn
Page # 7
Permit:'NC0028916 Owner: Facility: Troy VWVT'P
Inspection Date: 05/23/2006 Inspection Type: Compliance Evaluation
Pumps-RAS-WAS
Comment:
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
Is proper temperature set for sample storage (kept at 1.0 to 4.4 degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Comment: Meritech is the contract lab.
Influent Sampling
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
Is proper temperature set for sample storage (kept at 1.0 to 4.4 degrees Celsius)?
Is sampling performed according to the permit?
Comment:
Effluent Samplling
Is composite sampling flow proportional?
Is sample collected below all treatment units?.
Is proper volume collected?
Is the tubing clean?
Is proper temperature set for ample storage (kept at 1.0 to 4.4 degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type representative)?
Comment:
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free ofexcessive grease?
Are all pumps present?
Yes No NA NE
Yes No NA NE
■ nnn
onnn
■ nnn
■ nnn
n n■n
n nion
Yes No NA NE
n n■n
■ nnn
■ nnn
■ nnn
■ nnn
■ nnn
Yes No NA NE
n n■n
■ nnn
■ nnn
■ nnn
■ , n n n
■ nnn
Yes No NA NE
n n■n
■ nnn
■ nnn
■ nnn
Page # 8
Permit: NC0028916 Owner - Facility: Troy WWTP
Inspection Date: 05/23/2006 Inspection Type: Compliance Evaluation
Equalization Basins
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?.
# Is basin size/volume adequate?
Comment:
Yes No NA NE
■ nnn
■ nnn
■ nnn
■ nnn
Page # 9
;-
Regional Field Inspectors Check List for Field Parameters
Name of site to be inspected: TO
Field certification # (if applicable): ,f: 3.50
NPDES#:NC_ o.3 ci t
Region:
I. Circle the parameter or parameters performed at this site.
esidual Chlorin
Settleable Solids
II. Instrumentation:
Conductivity, Tmperature
A. Does the facility have the equipment necessary to analyze field parameters as circled above?
Yes No accu. rn t+'
1.
A pH meter
2. A Residual Chlorine meter
3. DO meter
4. A Cone for settleable solids
6. Conductivity meter
I11. Calibration/Analysis:
Yes5. A thermometer or meter that measures ternperature.
Yes
1. Is the pH meter calibrated with a 2 buffers and
checked with a thirdbuffer each day of use?
2. For Total Residual Chlorine, is a check standard
analyzed each day of use?
3. Is the aircalibration of the DO meter performed
each day of use?
4. For Settleable Solids, is 1 liter of sample
settled for 1 hour?
5. Is the temperature measuring device calibrated
annually against a certified thermometer?
6. For Conductivity, is a calibration standard
analyzed each day of use?
Yes -
Yes
Yes
No t 3 1" 5
No
No
No
No v 1 �� ao,0
IV. Documentation:
1. Is the date and time that the sample was collected documented? Yes
2. Is the sample` site documented?
3. Is the sample collector documented?
4. Is the analysis date and time documented?
5. Did the analyst sign the documentation?-
6. Is record of calibration documented?
7. For Settleable: Solids, is samplevolume and
1 hour time settling time documented?
8. For Temperature, is -the annual calibration of
the measuring device documented? .. .. -
Comments:
Yes
No
N
Please submit a copy of this completed form to the Laboratory Certification Program.
D.WQ Lab Certification
Chemistry Lab
Courier# 52-01-01
FIELD INSPECTOR CHECKLIST REV. 04/23/2002