HomeMy WebLinkAboutWQ0021768_Permit (Issuance)_20020925N,N1 A 7'6;9
pG
Michael F. Easley, Governor
William G. Ross Jr., Secretary
7 North Carolina Department of Environment and Natural Resources
-i
Alan W. Klimek, P.E., Director
Division of Water Quality
September 25, 2002
BOB GREBACK, TOWN MANAGER
TOWN OF LILLINGTON
106 WEST FRONT STREET
LILLINGTON, NC 27546
Subject: Permit No. W00021768
Town of Lillington
Lillington-Shawtown Elementary School
Wastewater Collection System Extension
Harnett County
Dear Mr. Greback:
In accordance with your application received August 30, 2002, we are forwarding herewith
Permit No. W00021768, dated September 25, 2002, to the Town of Lillington for the construction and
operation of the subject wastewater collection system extension. This permit shall be effective from the
date of issuance until rescinded and shall be subject to the conditions and limitations as specified
therein. This cover letter shall be considered a part of this permit and is therefore incorporated therein
by reference.
Please pay particular attention to Permit Condition 3 which requires that the wastewater
collection facilities be properly operated and maintained in accordance with 15A NCAC 2H .0227 or any
individual system -wide collection system permit issued to the Permittee.
Permitting of this project does not constitute an acceptance of any part of the project that does
not meet 15A NCAC 2H .0200; the Division of Water Quality's (Division) Gravity Sewer Minimum
Design Criteria adopted February 12, 1996 as applicable; and the Division's Minimum Design Criteria
for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable,
unless specifically mentioned herein. Division approval is based on acceptance of the certification
provided by a North Carolina -licensed Professional Engineer in the application. It shall be the
Permittee's responsibility to ensure that the as -constructed project meets the appropriate design criteria
and rules. Failure to comply may result in penalties in accordance with North Carolina General Statute
§143-215.6A through §143-215.6C, construction of additional or replacement wastewater collection
facilities, and/or referral of the North Carolina -licensed Professional Engineer to the licensing board.
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North
Carolina as amended, and other applicable Laws, Rules, and Regulations, permission is hereby
granted to the Town of Lillington for the construction and operation of approximately 1,255 linear feet of
8-inch gravity sewer to serve 750 students as part of the Lillington-Shawtown Elementary School
project, and the discharge of 9,000 gallons per day of collected domestic wastewater into the Harnett
County existing sewerage system, pursuant to the application received August 30, 2002 and in
conformity with 15A NCAC 2H .0200; the Division's Gravity Sewer Minimum Design Criteria adopted
February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting
Non -Discharge Permitting Unit
1617 Mail Service Center, Raleigh, NC 27699-1617
DENR Customer Service Center
An Equal Opportunity Action Employer
Internet http://h2o.enr.state.nc.us/ndpu
Telephone (919) 733-5083 Fax (919) 715-6048
Telephone 1 (800) 623-7748
50% recycled/10% post -consumer paper
of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting data
subsequently filed and approved by the Department of Environment and Natural Resources and
considered a part of this permit.
The sewage and wastewater collected by this system shall be treated in the Harnett County
Wastewater Treatment Facility (Permit No. NC0021636) prior to being discharged into the receiving
stream.
This permit shall become voidable unless the agreement between Town of Lillington and
Harnett County for the collection and final treatment of wastewater is in full force and effect.
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the
right to request an adjudicatory hearing upon written request within 30 days following receipt of this
permit. This request must be in the form of a written petition, conforming to Chapter 150E of North
Carolina General Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service
Center, Raleigh, NC 27699-6714. Unless such demands are made, this permit shall be final and
binding.
If you need additional information concerning this matter, please contact Kristin E. Miguez at
(919) 733-5083 extension 524.
Sincerely,
for Alan W. Klimek, P.E.
cc: Harnett County Health Department
Fayetteville Regional Office, Water Quality Section (WWTF Permit No. NC0021636)
The Rose Group
Harnett County (PO Box 1119, Lillington, NC 27546)
Central Files
NPDU Files
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
RALEIGH
WASTEWATER COLLECTION SYSTEM EXTENSION PERMIT
This permit shall be effective from the date of issuance until rescinded and shall be subject to the
following specified conditions and limitations:
1. This permit shall become voidable unless the wastewater collection facilities are constructed in
accordance with the conditions of this permit; 15A NCAC 2H .0200; the Division of Water Quality's
(Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the
Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force
Mains adopted June 1, 2000 as applicable; and other supporting materials unless specifically
mentioned herein.
2. This permit shall be effective only with respect to the nature and volume of wastes described in the
application and other supporting data.
3. The wastewater collection facilities shall be properly maintained and operated at all times. The
Permittee shall maintain compliance with an individual system -wide collection system permit for the
operation and maintenance of these facilities as required by 15A NCAC 2H .0227. If an individual
permit is not required, the following performance criteria shall be met as provided in 15A NCAC 2H
.0227:
a. The sewer system shall be effectively maintained and operated at all times to prevent
discharge to land or surface waters, and any contravention of the groundwater standards in
15A NCAC 2L .0200 or the surface water standards in 15A NCAC 2B .0200.
b. A map of the sewer system shall be developed prior to January 1, 2004 and shall be actively
maintained.
c. An operation and maintenance plan shall be developed and implemented.
d. Pump stations that are not connected to a telemetry system shall be inspected every day (i.e.
365 days per year). Pump stations that are connected to a telemetry system shall be
inspected at least once per week.
e. High -priority sewer lines shall be inspected at least once per every six-month period of time.
f. A general observation of the entire sewer system shall be conducted at least once per year.
g. Inspection and maintenance records shall be maintained for a period of at least three years.
h. Overflows and bypasses shall be reported to the appropriate Division regional office in
accordance with 15A NCAC 2B .0506(a), and public notice shall be provided as required by
North Carolina General Statute §143-215.1C.
1
4
4. This permit shall not be transferable. In the event there is a desire for the wastewater collection
facilities to change ownership, or there is a name change of the Permittee, a formal permit request
shall be submitted to the Division accompanied by documentation from the parties involved, 'and
other supporting materials as may be appropriate. The approval of this request shall be
considered on its merits and may or may not be approved.
5. Construction of the gravity sewers, pump stations, and force mains shall be scheduled so as not to
interrupt service by the existing utilities nor result in an overflow or bypass discharge of wastewater
to the surface waters of the State.
6. Upon completion of construction and prior to operation of these permitted facilities, a certification, a
copy of the construction record drawings, as well as supporting design calculations for any pump
stations permitted as part of this project shall be received from a North Carolina -licensed
Professional Engineer certifying that the facilities have been installed in accordance with this
permit; 15A NCAC 2H .0200; the Division's Gravity Sewer Design Criteria adopted February 12,
1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump
Station and Force Main adopted June 1, 2000 as applicable; and other supporting materials. If this
project is to be completed in phases and partially certified, you shall retain the responsibility to
track further construction approved under the same permit, and shall provide a final certificate of
completion once the entire project has been completed. A copy of the construction record
drawings, indicating the facilities constructed in the phase being certified, shall be submitted with
each partial certification. Mail the Engineer's Certification, one copy of the "Construction Record
Drawings", and one copy of the supporting design calculations to the Non -Discharge Permitting
Unit, 1617 Mail Service Center, Raleigh, NC 27699-1617.
7. A copy of the construction record drawings shall be maintained on file by the Permittee for the life
of the wastewater collection facilities.
8. Failure to abide by the conditions and limitations contained in this permit; 15A NCAC 2H .0200; the
Division's Gravity Sewer Design Criteria adopted February 12, 1996 as applicable; the Division's
Minimum Design Criteria for the Fast -Track Permitting of Pump Station and Force Mains adopted
June 1, 2000 as applicable; and other supporting materials may subject the Permittee to an
enforcement action by the Division, in accordance with North Carolina General Statutes §143-
215.6A through §143-215.6C.
9. In the event that the wastewater collection facilities fail to perform satisfactorily, including the
creation of nuisance conditions, the Permittee shall take immediate corrective action, including
those as may be required by this Division, such as the construction of additional or replacement
facilities.
10. The issuance of this permit shall not exempt the Permittee from complying with any and all
statutes, rules, regulations, or ordinances that may be imposed by other government agencies
(local, state and federal) which have jurisdiction, including but not limited to applicable river buffer
rules in 15A NCAC 2B .0200, erosion and sedimentation control requirements in 15A NCAC Ch. 4
and under the Division's General Permit NCG010000, and any requirements pertaining to wetlands
under 15A NCAC 2B .0200 and 15A NCAC 2H .0500.
11. Noncompliance Notification:
The Permittee shall report by telephone to the Fayetteville Regional Office, telephone number
(910) 486-1541, as soon as possible, but in no case more than 24 hours or on the next working
day, following the occurrence or first knowledge of the occurrence of either of the following:
a. Any process unit failure, due to known or unknown reasons, that renders the facility incapable
of adequate wastewater transport, such as mechanical or electrical failures of pumps, line
blockage or breakage, etc.; or
2
b. Any failure of a pumping station or sewer line resulting in a by-pass directly to receiving waters
without treatment of all or any portion of the influent to such station or facility.
Persons reporting such occurrences by telephone shall also file a written report in letter form within
five days following first knowledge of the occurrence. This report must outline the actions taken or
proposed to be taken to ensure that the problem does not recur.
Permit issued this the twenty-fifth day of September, 2002
NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION
for Alan W. Klimek, P.E., Didctor
Division of Water Quality
By Authority of the Environmental Management Commission
Permit Number WQ0021768
3
Permit No. W00021768
September 25, 2002
ENGINEER'S CERTIFICATION
Partial Final
I, , as a duly registered Professional Engineer in the State of North
Carolina, having been authorized to observe (periodically, weekly, full time) the construction of the
project, for the
Project Name Location and County
Permittee hereby state that, to the best of my abilities, due care and diligence was used in the
observation of the construction such that the construction was observed to be built within substantial
compliance of this permit; 15A NCAC 2H .0200; the Division of Water Quality's (Division) Gravity Sewer
Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design
Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as
applicable; and other supporting materials.
North Carolina Professional Engineer's seal, signature, and date:
The above Engineer's Certification shall be completed and submitted to the address below with one
copy of the "Construction Record Drawings" of the wastewater collection system extension as well as
supporting design calculations for any pump stations permitted as part of this project. This project shall
not be considered complete nor allowed to operate until this Engineer's Certification and all required
supporting documentation have been received by the Division. Any wastewater flow made tributary to
the wastewater collection system extension prior to completion of this Engineer's Certification shall be
considered a violation of the permit and shall subject the Permittee to appropriate enforcement actions.
NORTH CAROLINA DIVISION OF WATER QUALITY
WATER QUALITY SECTION
NON -DISCHARGE PERMITTING UNIT
1617 MAIL SERVICE CENTER
RALEIGH, NORTH CAROLINA 27699-1617
4
PROCEDURE 4 REQUEST FORM
DIVISION OF WATER QUALITY
NON -DISCHARGE PERMITTING UNIT
TO:
FROM:
Application Number:
County:
Applicant:
Project Name:
Project Type:
Receiving Facility:
Receiving Facility Permit:
Flow Volume (GPD):
Flow Type:
Engineer:
September 9, 2002
Kitty Kramer, Fayetteville Regional Office
Kristin E. Miguez, Non -Discharge Permitting Unit
919-733-5083 x 524
919-715-6048 (Fax)
kristin.miguez@ncmail.net
WQ0021768
Harnett
Town of Lillington
Lillington-Shawtown Elementary School
Fast Track / Wastewater Collection System Extension
Harnett County Public Utilities
NC0021636
9,000
DOM COM IND
The Rose Group
SOC Project? El YES X NO
Approval: X YES ❑ NO
Comments:
Regional Office Signature: Kitty Kramer Date: September 10. 2002,
FRO P4s
Subject: FRO P4s
Date: Tue, 10 Sep 2002 08:42:13 -0400
From: Kitty Kramer <Kitty.Kramer@ncmail.net>
To: "kristin.miguez@ncmail.net" <kristin.miguez@ncmail.net>,
Barbara Scantling <Barbara.Scantling@ncmail.net>,
Kitty Kramer <Kitty.Kramer@ncmail.net>
Good Morning Kristin
Are both of these projects DOMESTIC flow? I could not tell if that was
indicated on the two request forms.
Thanks Kitty
September 9, 2002.doc
Name: September 9, 2002.doc
Type: Microsoft Word Document (application/msword)
Encoding: base64
Download Status: Not downloaded with message
1 of 1 9/10/2002 8:44 AM
Re: FRO P4s
•
Subject: Re: FRO P4s
Date: Tue, 10 Sep 2002 09:30:44 -0400
From: Kristin Miguez <kristin.miguez@ncmail.net>
Organization: NCDENR Divison of Water Quality
To: Kitty Kramer <Kitty.Kramer@ncmail.net>
yes, both are domestic. i forgot to make that indication
Kitty Kramer wrote:
> Good Morning Kristin
> Are both of these projects DOMESTIC flow?
> indicated on the two request forms.
> Thanks Kitty
on the form!
I could not tell if that was
> September 9, 2002.doc
Name:
Type:
Encoding:
Download Status:
September 9, 2002.doc
Microsoft Word Document (application/msword)
base64
Not downloaded with message
Kristin E. Miguez <kristin.miguez(ancmail.net>
Environmental Technician V
Non -Discharge Permitting Unit
NC DENR-Division of Water Quality
1 of 1
9/10/2002 10:08 AM
NC0021636
viE: Harnett County Public Utilities - North Harnett Regional WWTP
CITY: Lillington
COUNTY:
Harnett
PERIOD ENDING MONTH:
6 - 2002
REGION: Fayetteville
DMR 12 Month Calculated
PAGE 3 OF 4
pir
01034
ug/1
Chromium, Total
(as Cr)
01042
ug/1
Copper, Total
(as Cu)
01051
ug/1
Lead, Total (as
Pb)
01067
ug/1
Nickel, Total
(as Ni)
:1092
ug/1
Zinc, Total (as
Zn)
31616
#/100m1
Coliform, Fecal
MF, M-FC
Broth,44.5C
31616
mpn/100m1
Coliform, Fecal
MF, M-FC
Broth,44.5C
50050
mgd
Flow, in
conduit or thru
treatment plant
7-01
2.8
0.5239
8-01
2.3
0.719 Violation
9-01
4.5
0.4957
10-01
4.4
0.3689
11 - 01
8.211677
0.349667
12-01
6.164447
0.337806
1 - 02
8.651953
0.527194
2-02
6.520692
0.516786
3-02
37.259031
0.477065
4 02
40.399651
0.452767
5-02
10.288285
0.388065
6-02
11.504299
0.313767
i,SS`
4-5 ;" 1
Zo @ �-
(� l C , T)
PERMIT NUMBER: NC0021636
FACILITY NAME: Harnett County Publ,c utilities - North Hamett Regional WWTP
CITY: Lillington COUNTY: Harnett
50060
mg/1
Chlorine, Total
Residual
50060
up/1
Chlorine, Total
Residual
TGE6C
pass/fail
P/F STAT 24hr
Acu Pimephales
7-01
14.615
1
8-01
17.333
9-01
18.333
10-01
19.333
1
11 - 01
18.333333
12-01
17.5
1 - 02
14
1
2-02
14.166667
3-02
5.833333
4-02
10
1
5-02
16.25
6-02
12.5
PERIOD ENDING MONTH: 6 - 2002 DMR 12 Month Calculated
PAGE 4 OF 4
REGION: Fayetteville
r-
PERMIT NUMBER: NC0021636
FACILITY NAME: Harnett County Public Utilities - North Hamett Regional WWTP
CITY: Lillington COUNTY: Harnett
OUTFALL: 001
EFFLUENT
PERIOD ENDING MONTH: 6 - 2002
REGION: Fayetteville
DMR 12 Month Calculated
PAGE 1 OF 4
00010
deg c
Temperature,
Water Deg.
Centigrade
00095
umhos/cm
Specific
Conductance
00300
mg/1
DO, Oxygen,
Dissolved
00310
lbs/day
BOD, 5-Day (20
Deg. C)
00310
mg/1
BOD, 5-Day (20
Deg. C)
00340
mg/1
COD, Oxygen
Demand, Chem.
(High Level)
00400
su
pH
00500
mg/1
Solids, Total
7 - 01
120
12
24.48
9.24
11.35
6.89 - 7.3
8 - 01
120
12
24.58
7.47
7.05
6.98 - 7.51
9 - 01
120
12
22.36
7.06
8.97
7.05 - 7.45
120
12
10-01
18.3
8.51
14.16 Violation
7.05 - 7.38
11 01
1`0
24
16.916667
9.208333
12.076923
7.22 - 7.57
12-01
120
24
14.833333
9.333333
19.416667
7.1 - 7.35
1 02
121)
21
12.76
9.513333
16.046667
6.8 - 8.25
2-02
120
24
12.916667
9.516667
7.791667
6.57 - 7.11
3 - 02
120
24
14.916667
9.708333
5.716667
6.91 - 7.22
4 - 02
120
12
18.538462
9.092308
7.133333
7 - 7.27
5 - 02
120
12
20.366667
8.2625
5.86
6.78 - 7.41
6 - 02
120
12
22.875
7.741667
6.166667
6.4 - 7.47
PERMIT NUMBER: NC0021636
FACILITY NAME: Harnett County Public Utilities - North Hamett Regional WWTP
CITY: Lillington COUNTY: Harnett
PERIOD ENDING MONTH: 6 - 2002
REGION: Fayetteville
DMR 12 Month Calculated
PAGE 2 OF 4
00530
lbs/day
Solids, Total
Suspended
00530
mg/1
Solids, Total
Suspended
00545
ml/1
Solids,
Settleable
00600
mg/1
Nitrogen, Total
(as N)
00610
mg/1
Nitrogen,
Ammonia Total
(as N)
00665
mg/1
Phosphorus,
Total (as P)
01027
mg/1
Cadmium, Total
(as Cd)
01027
ug/1
Cadmium, Total
(as Cd)
7 01
360
30
2
0.002
5.5
13.66
0
0.65
8-01
360
30
2
0.002
6.2
0
9 01
360
30
2
0.002
3.7
0.04
10 01
360
30
2
0 202
4.2
16.25
0
1.24
11 - 01
360
30
4
0.002
5.058333
0.1535
12 - 01
360
30
4
0.002
6.225
0
1 02
360
30
4
0.002
7.686667
2.14
1.024867
1.83
2-02
360
30
4
0002
4.583333
0.629833
3 02
360
30
4
0 002
1.625
0.336333
4 02
360
30
2
0.002
2.191667
9.61
0
1.44
5 - 02
360
30
2
0.002
3.62
0.096467
6 - 02
360
30
2
0.002
1.733333
0.19475