Modified Permit No. WQ0033258
City of Conover
Bunker llill Iligh School Severs
Catawba County
Project No. I: -SRC-T-02-0I 39
In accordance with your permit application received July 22, 2008, and additional
ation received. by the Division of Water Quality (Division ve are forwarding herewith
No. WQ0033258 dated March 4, 2009, to the City of Conocr for the construction and
f'the subject wastewater collection system.
This Permit shall be
WQO0 33258 issued December
specified therein.
the
If any parts, requirements, o
request an adjudicator
mit. This request must be
2
he date of
and shall
uaztce until rescinded, shall void Permit No.
t to the conditions and limitations as
s containcd in t
upon written request with
the torn", of a written petiti
unacceptable, you have
days following receipt
conforming to Chapter
150B of North Carolina General Statutes, and fled with the Office of dministrative Hearings,
6714 Mail. Service Center, Raleigh, NC 27699-6714. Unless such demands are made this permit
shall be final and binding,
1: letion of construction and prior to operation of this lrertxtitted f tci1ity7 a
must be receiv`e.d from a professional engineer certifying that t1e permitted facility
nstalled in accordance with the approved plans and speciI cations. tail the
tne. t.T.onstruction C;'r( tlts & Loans Section, 1633 Mad Service (:'enter, Raleigh,
27699-1633. (Engineer's Certification form is attached.)
approved plans and spec".
forwardccl to vou,
Phone.
interne ,7
ne
NdirtitCarolina.
aurally
Mr, Donald l anean
March 4, 2009
Page 2
if ,ou reed additional in°iarmatirrn e
State Review Fn .ineer°,, at () 715-62
ink this matter please contact Anita F. Reed,
Seth Robertson, RE. . at (919) 715-6206.
e' Doug Chapman, 1'.l a; e ill ssuei<ates.
Catawba County 1 ka[t l epartment:
Wboos°esville Re Office, Surface'
Daniel M. Blaisdell, P,F.
Mark Hubbard, P..:
Don Evans
Anita 1. Reed, l.:.
S ( File
Sit
Co een 11. Sullins
. l 1
ie.ko y, N(' 2
ection (NC" 52)
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
RALEIGH
WASTEWATER COLLECTION PERMIT
In accordance with the provisions of Article 21 of Chapter 1.43, General Statutes of North
Carolina as amended, and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
City of Conover
Catawba County
FOR THE
construction and operation of a sewer system consisting of: a 186 GPM duplex submersible
pump station with audible and visual alarms, generator, and telemetry; approximately 7,980
linear feet of 6-inch force main; approximately 55 linear feet of 18-inch gravity sewer and
17,794 linear feet of 8-inch gravity sewer; 65 4-foot diameter manholes and nine (9) 5400t.
diameter manholes as part of the Bunker Hill High School Area Sewers Project and the discharge
of 8,400 GPI) of collected ‘vastewater from Oxford Middle School into the Northeast WWIP
(NC0024252) sewerage system pursuant to the application received on July 22, 2008, and
subsequent additional information received by the Division, and in conformity with the project
plans, specifications, and other supporting data subsequently filed and approved by the
Department of Environment and Natural Resources and considered a part of this permit.
This permit also grants permission for the:
construction and operation of a sewer system consisting of: approximately 2,753 linear .fcct of 8-
inch gravity sewer and 16 4-foot diameter manholes as part of the Bunker Hill High School Area
Sewers Project and the discharge of 22,350 GPD of collected wastewater serving Bunker Hill
High School and Riverbend Middle School into the Northeast WWTP (NC0024252) sewerage
system pursuant to the application received on October 30, 2008, and subsequent additional
information received by the Division, and in conformity with the project plan.s, specifications,
and other supporting data subsequently filed and approved by the Department of 1.-nvironment
and Natural Resources and considered a part of this permit.
This permit shall he effective from the date of issuance until rescinded, shall void Permit No.
WQ0033258 issued December 8, 2008, and shall he subject to the following specified conditions
and limitations:This permit shall become voidable unless the facilities. are constructed in
accordance with the conditions of this permit.. the approved plans and specifications, and other
supporting data,
City of Conover
March 4, 2009
Modified Permit No. WQ0033258
Page 2
This permit is effective only with respect to the nature and 'volume of wastes described in the
application and other supporting data.
2. The wastewater collection facilities. shall he properly maintained and operated at all times.
The Permittee shall maintain compliance with an individual system -wide collection system
permit for the operation and maintenance of these facilities as required by 15A NCAC 21'
.0400. Ilan individual permit is not required, the following performance criteriashall be met
as provided in 15.A NCAC 2-1 .0400:
(a) The sewer system shall be effectively maintained and operated at all times to prevent
discharge to land or surface waters, and to prevent any contravention of' groundwater
standards or surface water standards.
(b) A map of the sewer system shall be developed and actively maintained.
(c) An operation and maintenance plan including pump station inspection frequency,
preventative maintenance schedule, spare parts inventory and overflow response shall.
be developed and implemented..
(d) Pump stations that are not connected to a telemetry system (i,e., remote alarm system)
shall be inspected by the permittee or its representative every day (i.e., 365 days per
year). Pump stations that are connected to a telemetry system shall be inspected at
least once per week,
tligh-priority sewers shall he inspected by the permittee or its representative at least
once every six -months and inspections are documented.
(I) A general observation by the permittee or its representative of the entire sewer system
shall be conducted at least once per year.
(g) Overflows and bypasses shall he reported to the appropriate Division regional office
in accordance with 15A NCAC 02B .0506(a), and, public notice shall be provided as
required by G.S. 143-21.5.1C.
(h) A Grease Control Program shall be established as follows:
(i) For publicly owned collection systems, the Grease Control Program shall
include at least hi -annual distribution of educational materials for both
commercial and residential users and the legal means to require grease
interceptors for new construction and retrofit, if necessary, of grease
interceptors at existing establishments.. The plan shall also include legal mcans
tor inspections of the grease interceptors, enforcement for violators and the
legal means to control grease entering the system froni other public and
private satellite sewer systems.
(ii) For privately owned collection systems, the Grease Control Program shall
include at least bi-annual distribution of grease education materials to users of
the collection system by the permittee or its representative.
Grease education materials shall be distributed more often than required in
Parts (i) and (ii) of this Subparagraph if necessary to prevent grease -related
sanitary sewer overflows.
(i) Right-of-ways and easements shall be maintained in the full easement width for
personnel and equipment accessibility.
PrCity of Conover
March 4, 2009
Modified Permit No. WQ0033258
Page 3
(1) Documentation shall be kept for Subparagraphs (a) through (i for a minimum of
three years with exception of the map, which shall be maintained for the life of the
system.
The sewage and wastewater collected by this system shall be treated in the Northeast W
(NC0024252) sewerage system prior to being discharged into the receiving stream.
This permit is not transferable. In the event
ere is a ll'nlittec, desire
a formal l�le9 lit recluest��ml� tllhe
ownership, or there is a name change of the er
on
om
submitted to the Division accompanied by an applicatione,docul neat tiovalro this request
involved, and other supporting materials as may be appropriate,.
v�ill be considered on its merits and may or may not he approved.
Construction of the sewers, pump station(s) and fo
interrupt service by the existing utilities nor resul
wastewater to the surface waters of the State.
7. A copy of 'thc approved. plans and specificat
for the life ofthe wastewater collection. facilit
g. tipon completion of construction and prier to operation of this peltuitted fact
certification must he received from a pral engineer certifying drat the pen
racilit y has been installed in aecord.ancc with this permit, oved torbeacr n' fete in plans and
spec d cations, and other supporting nl.aterials. if this protect is l
and partially certified, you shall retain the responsibility to track further construction
approved under the same permit, and ~hall provide a final certificate of completion once the
1 l � Service a ,e �, Center, ll�: i fh. North Carolina 27699-1633.' `�' Loans
Raleigh, entire project has been completed. Mail the Certification to the Construction Grants (Engineers
Section, 1 C� ��.� Mail 5e� � tc.e �
Certifi.catlon F 7rrn is attached.)
allure to abide by the condit
Permit tee to an enforcement
General Statute 143-215,6A to 143-21
r".
10. The issrranc.
statutes
hulTe
15A NCAC
requireIllents
11. 'Fife Pen
of this per
regulations,
l federa
15A NCAC.
apter 4 and
g
1.11 provide
:he pump
Station Reliabilit
ainshall be scheduled so as not to
n overflow or bypass. discharge of
be maintained on file by the Pe
nitattclns contained i
the i
pt the Permit -tee from complytllg
at Iztay be unposed by other governrnen
ction, including but not limited to applica
'osion and sedimentation control reeluiremei
`s General Permit NCG010000, and any
5A NCAC 213 .0200 and 15A NCAC 211 .0500
�titlil and force main the lalllc virlg items:
"la
uhject the
C'ar'olina
City of Conover
March 4, 2009
Modified Permit No. WQ0033258
Page 4
Pump stations, except when exempted by Subparagraph (j)(2) of 15A NCAC
021.0.305, shall be designed with multiple pumps such that peak flow can be
pumped with the largest pump out of service.
A standby power source or pump is required at all pump stations except for
those pump stations subject. to Subparagraph (j)(2) of 15A NCAC 021.0305.
Controls shall he provided to automatically activate the standby source and
signal an alarm condition.
(iii) As an alternative to Part (ii) for purnp stations with an average daily design
flow less than 1.5,000 gallons per day as calculated using 15A NCAC
021.0114,
a portable power source or pumping capabilitymay he utilized, It shall be
demonstrated to the Division that the portable source is owned or contracted
by the pennittee and is compatible with the station. If the portable power
source or pump is dedicated to multiple pump stations, an evaluation of all the
pump stations' storage capacities and the rotation schedule of the portable
power source or pump, including travel timeframes, shall be provided in the
case of a multiple station power outage.
(iv) As an alternative to Part (ii) for pump or vacuum stations connecting a single
building to an alternative sewer system, wet well storage requirements shall be
documented to provide 24-hours worth of wastewater storage or, exceed the
greatest power outage over the last three years or the documented response
time toreplace a .failed pump, whichever is greater. Documentation shall he
required pursuant to the permit application..
(v) All pump stations designed for two pumps or more shall have a telemetry
system to provide remote notification of a problem condition to include power
failure and high water alarm.
(vi) High water audio and visual alarm.
(h) Pump stations shall have a permanent weatherproof sign stating the pump station
identifier, 24-hour cinerge.ncy number and instructions to call in case of emergency.
Simplex pump or 'vacuum stations serving a single-family residence shall have a
placard or sticker placed inside the control panel with a 24-hour emergency contact
number.
(c) Screened vents for all wet wells.
(d) The public shall be restricted access to the site and equipment.
to. Air relief valves shall he provided at all high points along force mains where the
vertical distance exceeds ten feet.
P. in th.e event that the facilities fail to perform satisfactorily, including the creation of nuisance
conditions, the Permince shall take immediate corrective action, including those that may be
required by this Division, such as the construction of additional or replacetnent wastewater
collection thcilities
13. The facilities shall he constructed in accordance with the requirements of the North Carolina
Sedimentation Pollution Control Act.
prCity of Conover
March 4, 2009
Modified Permit No. WQ0033258
Page 5
14. If applicable, thc Operational Agreement between the Permittee and the Environmental
Management. Commission is incorporated herein by reference and is made a condition of this
Permit. Noncompliance with the terms of th.e Operational Agreement may subject the
Permittee to an enforcement action by the Division in accordance with North Carolina
General Statute 143-215„6A to 143-215.6C. A copy of the Articles of Incorporation,
Declarations, and Bylaws that have been properly tiled shall be submitted with the engineers
certification prior to operation.
15. Any abandoning of the existing facilities must be done in accordance with the requirements
of the Division's Mooresville Regional Office.
16.. Noncompliance Notification:
The Permittee shall verbally report to a water quality staff member at the Mooresville
Regional Office, telephone number (704) 663-'1.699, as soon as possible, but in no case more
than 24 hours or on the next working day following the occurrence or first knowledge of the
occurrence of either of the following:
(a) Any process unit failure, due to known or unknown reasons, that render the facility
incapable of adequate wastewater transport such as mechanical or electrical failures
of pumps, line blockage or breakage, etc.
(b) Any failure of a pumping station or sewer line resulting in a by-pass directly to
receiving waters ‘yithout treatment of all or any portion of the influent to such station
or facility.
Voice mail messages or faxed information is permissible but this shall not be considered as
the initial verbal report Overflows and spills occurring outside normal business hours may
also be reported to the Division of 1.'",rnergeney Management at telephone number (800) 858-
0368 or (919) 733-3300. Persons reporting any of the above occurrences shall file a spill
reportby completing Part 1 of Form CS-SSO (or the tnost current Division approved form),
within five days following first knowledge of the occurrence. This report shall outline the
actions taken or proposed to ensure that the problem does not recur. Per Condition1(2), Part
II of Form CS-SSO (or the most current Division approved form) can also be completed to
show that the SSO was beyond control.
Permit issued this the 4th Day of March 2009
111 CAROLINA ENVIRONMENTAL MANAGEMENT CO
'oleen 11. Sullins, Director
Division of Water Qualiiv
By Authority of the Environmental Management Commission
Modified .Permit No. WQ0033258
City of Conover
Modified Permit No. WQ0033258
Project No. E-SRG-T-02-0139
Bunker Hill High School Sewers
Issued March 4, 2009
ENGINEWS CERTIFICATION
as a duly registered Professional Engineer in the
State of North Carolina, having been authorized to observe (periodically/weekly/full time) the
construction of the Bunker Hill High School sewer collection system serving Bunker Hill High
School, Oxford Middle School, and Riverbend Middle School, located in Catawba County,
hereby state that to the best of my abilities, due care and diligence was used in the observation of
the following construction:
construction of a sewer system consisting of: a 186 GPM duplex submersible pump station with
audible and visual alarms, generator, and telemetry; approximately 55 linear feet of18-inch
gravity sewer, 7,980 linear feet of 6-inch force main; approximately 17,794 linear feet of 8-inch
gravity sewer; 65 4-foot diameter manholes, and nine (9) 5-foot diameter manholes as part of the
Bunker Hill High School Area Sewers Project pursuant to the application received on July 22,
2008, and subsequent additional information received by the Division, and in conformity with
the project plans, specifications, and other supporting data subsequently filed and approved by
the Department of Environment and Natural Resources and considered a part of this permit.
certify that the construction of the above referenced project was observed to be built withi „
substantial compliance and intent of the approved plans and specifications.
Signature Registration No,
Date
Mail this Certification to: DENR/DWQ
Construction Grants & Loans Section
1633 Mail Service Center
Raleigh, North Carolina 27699-1633.
Note: If the .wastewater collection permit was issued to a private entity under an
Operational Agreement with the Environmental Management Commission, then a
copy of the Articles of Incorporation, Declarations, and Bylaws that have been
properly filed with the applicable County's Register of Deeds shall be submitted
with this certification.
NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water Quality
Beverly Eaves Perdue Coleen H. Sullins
Governor Director
Mr. Donald Duncan, City Manager
City of Conover
P.0. Box 549
Conover, North Carolina 28613
March 4, 2009
ti It. 77 1 75 777 r't
thrtt Ct. 7_777777
DWQ-Surface Wafer
SUBJECT: City of Conover
Bunker Hill High School Sewers
Approval of the Plans and Specifications
Project No. E-SRG-T-02-0139
Dear Mr. Duncan:
The review for completeness and adequacy of the project construction plans and
specifications has been concluded by the Construction Grants & Loans Section of the North
Carolina Division of Water Quality. Therefore, said plan documents are hereby approved with
eligibility for State funding determined as follows:
'Eligible
construction of a 186 GPM duplex submersible pump station with audible and visual
alarms, generator, and telemetry; approximately 7,980 linear feet of 6-inch force main;
approximately 55 linear feet of18-inch gravity sewer, 1.7,794 linear feet of 8-inch gravity
sewer; 65 4-foot diameter manholes, nine (9) 5-foot diameter manholes; abandoning of
the existing WWTP at Bunker Hill High School; removal and replacement of pavement,
roadways, driveways and curbs, sedimentation and erosion control devices, and
associated appurtenances necessary for the installation of a complete system within and
up to the existing right-of-way
Non Eligible
construction of approximately 2,753 linear feet of 8-inch gravity sewer and 16 4-foot
diameter manholes serving Bunker Hill High School as part of the Bunker Hill 'High
School Athletic Field Sewers and any installation of sewer service laterals outside the
right-of-way.
1633 Matt Service Centet. Raje. North Cattoltee. 27699,1633.
Location 27726 Capital. B6,17 Rateigh, North Garottna 27604
Phone: 919-733-6900 I FAX: 9.19.-715-6229 `.; Customer Service: 11877762376748
Internet vtnooknokatrtittayory
An Etwal Opitottonity Alticronve Lroplo'iw
One
NorthCar:
.latura
Mr. Duncan
March 4, 2009
Page Number 2
Issuance of this,approval letter does not imply availability of funding. You are encouraged
not to advertise for bids Until you have received the funding offer. In the event that received bids
exceed the amount established through the funding offer, and local funds are not adequate to
award contract(s), it will be necessary to consider all alternatives including, redesign,
re -advertising, and rebidding.
Neither the„,State Ayr Federal Government, nor any of its departments, agencies or
employees is or will he a party to the invitation to bids, addenda, any resulting contracts or
contract negotiations/changes.
In accordance with the Federal Regulations, the Recipient is required to assure compliance
with the OSHA safety regulations on the subject project. In complying with this regulatory
responsibility, the Recipient should, by letter, invite the Bureau Chief, Education Training and
Technical Assistance, Unit, NC OSHA Division, 1101 Mail Service Center, Raleigh, NC 27699-
1101 at (9.19) 807-2890, to participate in the "'reconstruction Conference to assure that proper
emphasis is given on understanding and adhering to the OSHA regulations.
It is the responsibility of the Recipient and the Consulting Engineer to insure that the
project plan documents are in compliance with Amended N. C. G. S. 133-3 (ratified July 13,
1993). The administrative review and approval of these plans and specifications, and any
subsequent addenda or change order, do not imply approval of a restrictive specification for
bidding purposes; nor is it an authorization for noncompetitive procurement actions.
Any addenda to he issued for subject projeci. plans and specifications must be submitted by
the Recipient such that adequate time is allowed for review/approval action by the State, and for
subsequent bidder action prior to receipt of bids,
lt is mandatory for project facilities to be constructed in accordance with the North
Carolina Sedimentation Pollution Control Act, andwhen applicable, the North Carolina Darn
Safety Act. .111 addition, the specifications must clearly state what the contractors' responsibilities
shall he in complying with these Acts.
While rejection of all bids is possible, such action may be taken only with prior State
concurrence, and only for good cause.
The Recipient will comply with the utilization of minority businesses in accordance with
GS 143-128.
Attached is a form (Project Bid Information), which is to be completed within 21 days
after bids have been received, and submitted to the State for review. It must he accompanied by
the documents indicated on the form. Upon review- and approval of this information, the State
Will authorize the Recipient to make the proposed award,
Mr. Duncan
March 4, 2009
Page Number 3
Prior to enter'
applicable projec
Discharge Permit.
into any contracts) for construction, the recipient must have obtained all
its from the State, including an Authorization to Construct and/or Non -
Two (2) copies of any change order must be promptly submitted. by the Recipien
State. If additional information is requested by the State, a response is required within two (2)
weeks,. or the change order will be returned without further or final action.
One (1) set of the final approved plans and specifications will be forwarded to you. One
set of plans and specifications identical to the approved set must be available at the project.
at all times.
:o the
Upon completion of the project construction, the Recipient shall submit a letter confirming
that the project has been constructed in accordance with the plans and specifications approved. by
the State. "As -built." plans will need to be submitted with any changes clearly documented on
the plans if the above confirmation cannot be made.
If there are any questions concerning this matter, please do not hesitate to contact
Seth Robertson, P.F., at (919) 715-6206.
Sincerely,
Attachment
AR:sr
isdell, P.L. Sec
'rants l . Lo a
cc: Doug C 1 al trtar , P.E. McGill Associates, P.O. l ox 113t , Hickory, NC:' 286 )3
WQ Mooresville Regional Office
A Bureau. Chief, Wanda. Lagoe
isdell, P.I.
Mark Iubbard, P.E.
Shamim hoer'
Anita E. Reed, P.E.
C I G
SRG
City of Conover
Modified Permit No. WQ0033258
Project No. E-SRC►-T-02-0139
Bunker Hill High School Sewers
Issued March 4, 2009
ENGINEER'S CERTIFICATION
I, •,,, Ine- 4 �, as a duly registered. Professional Engineer in the
State of North Carolini, having been authorized to observe (periodically/weekly/full time) the
construction of the Bunker Hill High School sewer collection system serving Bunker Hill High
School, Oxford Middle School, and Riverbend Middle School, located in Catawba County,
hereby state that to the best of my abilities, due care and diligence was used in the observation of
tyre following construction:
13,1844 LF et 1- ,k,.$1 44k. t cwc ,(z7)
construction of a sewer system cot sisting of:
as part of the
Bunker Hill High School Area Sewers Project pursuant to the application received on July 22,
2008, and subsequent additional information received by the Division, and in conformity with
the project plans, specifications, and other supporting data subsequently filed and approved by
the Department of Environment and Natural Resources and considered a part of this permit.
I certify that the construction of the above referenced project was observed to be build within
substantial compliance and intent of the approved plans and specifications.
Signature
Date
ation No. 0
Mail this Certification to: DENRIDWQ
Construction Grants & Loans Section
1633 Mail Service Center
Raleigh, North Carolina 27699-1633.
Note: if the wastewater collection permit was issued to a private entity under an
Operational Agreement with the Environmental Management Commission, then a
copy of the Articles of Incorporation, Declarations, and Bylaws that have been
properly filed with the applicable County's. Register of Deeds shall be submitted
with this certification.