HomeMy WebLinkAboutNC0076783_Inspection_20050603Michael F. Easley, Governor
William G. Ross Jr., Secretary
North Carolina Department of Environment and Natural Resources
Alan W. Klimek, P.E. Director
Division of Water Quality
June 3, 2005
Mick J Noland, PE
PWC/Fayetteville
PO Box 1089
Fayetteville NC 28302
SUBJECT: June 3, 2005 Compliance Evaluation Inspection
PWC/Fayetteville
Hoffer WTP
Permit No: NC0076783
Cumberland County
Dear Mr. Noland, PE:
Enclosed please fmd a copy of the Compliance Evaluation Inspection form from the inspection conducted
on June 3, 2005. The Compliance Evaluation Inspection was. conducted by Chad Turlington of the
Fayetteville Regional Office. The facility was found to be in Compliance with permit NC0076783.
Please refer to the enclosed inspection report for additional observations and comments. If you or your staff
have any questions, please call me at (910) 486-1541 ext. 724.
Sincerely,
Olaf,/
c.
Chad Turlington
Environmental Technician
cc: Jeffery L Carlisle, ORC
Central Files
Fayetteville Files
1617 Mail Service Center Raleigh, NC 27699-1617 (919) 733-7015
Customer Service 1 800 623-7748
T
AGDENit
United States Environmental Protection Agency
EPA Washington, D.C.20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection,Type
1 121j 2 U 3 I NC0076783 111 121 05/06/03 117
Inspector FacType
18 U 19 U 20 LI
Remarks
21IIIIIIIIIIIIIIIIIIII•IIIIIIIIIIIIIIIIIIIIIIIIIII66
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---- -Reserved- ----
67 I 2.0 169 70 LI , 71 LI 72 IA 731 1174 75,I I I I I I 1180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Hoffer WTP
508 Hoffer Dr
Fayetteville NC 28301
Entry Time/Date
09:30 AM 05/06/03
Permit Effective Date
02/01/01
Exit Time/Date
12:30 PM 05/06/03
Perrnit Expiration Date
06/10/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Jeffery L Carlisle/ORC/910-223-4710/
Other Facility Data
.
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Mick J Noland, PE,PO Box 1089 Fayetteville NC 28302//910-223-4733/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit � Flow Measurement • Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Chad Turlington FRO.WQ///
6 4/W:g*C) & 13/5
ad
iture anage nt Q eviewer Agency/Office/Phone and Fax Numbers Date
Belind S Hen on 910-486-1541 Ext.727/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
NPDES
NC0076783
111 121
yr/mo/day
05/06/03
117
Inspection Type
18u
(cont.) 1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
DMR's for the months of June 2004 to March 2005 were reviewed. One permit violation was found for the month of
November 2004. Samples for iron and aluminum were inadvertently not taken. Records were accurately and very
neatly maintained. The wastewater at this facility is primarily filter backwash water from this facility as
well as from the Glenville WTP. Wastewater from both facilities is pumped into an equalization basin.
Wastewater from the equaliztion basin then has polymer added to aid in settling. Two to three percent of the
wastewater is then pumped to the Cross Creek WWTP with the remainder going to one of two clarifiers. At the
time of this inspection one of the clarifiers was down for service. The supernatant water is then pumped to
,a 10 acre lagoon where more settling can occur. Upon leaving this lagoon the water is discharged into the Cape
Fear River. The outfall was easily accessible and the effluent was clear.
•
Permit Yes No NA NF
(If the present permit expires in 6 months or less). Has the permittee submitted a new application? 0 0 • 0
Is the facility as described in the permit? • ❑ ❑ ❑
Are there any special conditions for the permit? ❑ • ❑ ❑
Is access to the plant site restricted to the general public? .000
Is the inspector granted access to all areas for inspection? U ❑ ❑ 0
Comment:
Operations & Maintenance Yes No NA NF
Is the plant generally clean with acceptable housekeeping? 11000
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge Judge, ❑ ❑ • ❑
and other that are applicable?
Comment:
aboratory Yes No NA NF
Are field parameters performed by certified personnel or laboratory? U 000
Are all other parameters(excluding field parameters) performed by a certified lab? 11000
Is the facility using a contract lab? ❑ • ❑ ❑
Is proper temperature set for sample storage (kept at 1.0 to 4.4 degrees Celsius)? 0 " 0 0 •
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? 0 0 • 0
Incubator (BOD) set to 20.0 degrees Celsius +/-1.0 degrees? 0 0 • 0
Comment:
Record Keeping Yes No NA NF
Are records kept and maintained as required by the permit? 1 ❑ ❑ ❑
Is all required information readily available, complete and current? • ❑ ❑ ❑
Are all records maintained for 3 years (lab. reg. required 5 years)? 1 ❑ ❑ ❑
Are analytical results consistent with data reported on DMRs? 1 ❑ ❑ ❑
Is the chain -of -custody complete? • ❑ ❑ ❑
O&M Manual 0
As built Engineering drawings ❑
Schedules and dates of equipment maintenance and repairs ❑
Dates, times and location of sampling •
Name of individual performing the sampling •
Results of analysis and calibration •
Dates of analysis •
Name of person performing analyses •
Transported COCs •
Are DMRs complete: do they include all permit parameters? 1 ❑ ❑ ❑
Has -the facility submitted its annual compliance report to users and DWQ? ❑ ❑ 110
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift? 111000
Is the ORC visitation log available and current? • 0 0 0 •
Is the ORC certifiedat grade equal to or higher than the facility classification? • ❑ .❑ 0
Is the backup operator certified at one grade less or greater than the facility classification? • 0 0 0
Is a copy of the current NPDES permit available on site? 1 ❑ ❑ ❑
Facility has copy of previous year's Annual Report on file for review? 00.0
Comment:
Fffluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? 1 ❑ ❑ ❑
Fffluent Pipe
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Yes No NA NF
■ O O O
O 0.0