HomeMy WebLinkAboutNC0081825_Technical Assistance Report_20061106November 6, 2006
Frankie Roberts
Town of Ansonville
PO Box 106
Ansonville, N.C. 28007
Subject: Technical Assistance Report
NPDES Number NC0081825
-Anson-County
Dear Mr. Roberts,
Michael F. Easley, Govemor
William G. Ross Jr., Secretary
North Carolina Department of Environment and Natural Resources
Alan W. Klimek, P.E., Director
Division of Waier Quality
r
This is to document that technical assistance has been given regarding the operation of the
Ansonville Wastewater Treatment Facility on October 25, 2006. This technical assistance was
conducted by telephone to give recommendations in regard to fecal coliform violations. As always
you are to be commended for calling for assistance when needed, in order to protect water quality
and the permittee from assessed civil penalties. See the attached technical assistance summary for
details that were'discussed.
If youhave questions concerning this report or if this office can be of additional assistance, please
contact me at 910-433-3309.
Sincerely,
Don Register
Wastewater Treatment Consultant
Cc: Jerry Rimmer, Technical Assistance Supervisor
FRO files.
No thCarolina
Naturally
North Carolina Division of Water Quality 225 Green Street — Suite 714 Fayetteville, NC 28301-5043 Phone (910) 433-3300 Customer Service
Internet: ncwaterquality.org FAX (910) 486-0707 1-87-7-623-6748
An Equal Opportunity/Affirmative Action Employer— 50% Recycled/10% Post Consumer Paper
United States Environmental Protection Agency _
EPA Washington, D.C. 20460:
Water Compliance Inspection Report
'Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A:- National Data System Coding (i.e:, PCS)
Transaction Code , NPDES yr/mo/day Inspection
1 I NI 2 I GI 31 NC0081825 111 121 06/10/25: _ 117
Type Inspector Fac Type
181 DI " 191 sI . 20I I
1I11 l.J1111166
Remarks
2111l1 III1111I 11II 111111.11.111111111111
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
671 2.0 169 701 I 711 1 .t 721 NI 731 1 174 751 1 -I 1 1 1 1 1 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Ansonville WWTP; .
NCSR• 1627
Ansonville NC 28007 i
It
Entry Time/Date
09.00 AM. 06/10/25
-
Permit Effective Date
-
04/02/01
,Exit Time/Date
;09:30 AM 06/10/25
Permit Expiration Date
09/01/31 •
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) -
.///
William H. Waddell/ORC/704-694-5293/
Other Facility Data
1 1
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Daniel Lane Wilson,PO Box 106 Ansonville NC 28007//704-826-6404/ No
Section'C: Areas Evaluated During Inspection (Check only those areas evaluated)
Other
Section D: Summary•ofFinding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Don Resister FRO WQ//910-433-3300 Ext.709/
4111 /1/- 03 -,06
Imo►,
Signature of Man gement Q A Re iewer Agency/Office/Phone and Fax Numbers Date
Wt'7 11—(-DL
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page # 1
r
NPDES yr/molday Inspection Type
NC0081825 I11 121 06/1.0/25 I17 181DI
(dont.) 1
' -Section D: Summary of Finding/Comments (Attach additional sheetsofnarrative and .checklists as necessary)
Ansonville WWTP operator Frankie Roberts called by telephone to report a weekly Max violationfor fecal.
coliform. I suggested to him 'to sample as early in the week as possible in order to_have time to collect
additional samples if necessary to better the average to meet compliance. In addition I 'recommended that
he make-surethat he has an adequate chlorine residual of (0.5-0.7 mg/I) before collecting a fecal sample.
Unusually high total suspended solids can also cause inadequate disinfection, resulting in high fecal
coliform counts. If you have any questions please call me @ 910-433-3309, Don Register
.t