Loading...
HomeMy WebLinkAboutNC0081957_Regional Office Historical File Pre 2018Water Resources ENVIRONMENTAL QUALITY C' O 0, - FJR- overnpr MICHAEL S. REd Secretary LINDA CULPEPPER Interim Director 21 February 2018 Mark J. Gross, VP of Operations Cube Yadkin Generation, LLC Post Office Box 575 Badin, North Carolina 28009 SUBJECT: Compliance Evaluation Inspection Falls, Narrows, Tuckertown Powerhouses NPDES Permit NC0076775, NC0081957, NCO081949 Stanly County, NC Dear Mr. Gross: On February 15, 2018, Mr. Roberto Scheller of this Office conducted inspections at the subject facilities. These inspections were conducted as Compliance Evaluation Inspections (CEI) to insure compliance with permit requirements and conditions. We wish to thank you and your staff for their assistance regarding these inspections. The enclosed reports should be self-explanatory; however, should you have any questions, please do not hesitate to contact me or Roberto Scheller at (704) 235-2204 or roberto.scheller@ncdenr.gov. Sincerely, W. Corey Basinger, Regional Supervisor Water Quality Regional Operations Section Division of Water Resources, NCDEQ Enclosure: Inspection Reports cc: MSC 1617 — Central File Basement File State of North Carolina I Environmental Quality I Water Resources I Water Quality Regional Operations Mooresville Regional Office) 610 East Center Avenue, Suite 3011 Mooresville, North Carolina 28115 704 663 1699 United States Environmental Protection Agency Form Approved. EPA Washington, D.C.20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 15 1 3 I NCO076775 111 121 18/02/15 I17 18 I C I 19 1 s I 201 1 211IIIII IIIIIIIIIII IIIIIII I IIIIII IIIIIIIIIII f6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 CIA -----Reserved--- -- 72 1 �, 1 731 I 174 75I III I I I I80 67 70 1 71 itI JI L l� J I Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 10:30AM 1 B/02/15 14l03/01 Falls Powerhouse 49156 Falls Rd Exit Time/Date Permit Expiration Date Badin NC 28009 11:05AM 18/02/15 19/01/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data /// Beverly P Whitley/ORC/704-422-5614/ Name, Address of Responsible OfficialfTitle/Phone and Fax Number Contacted Mark J Gross, PO Box 576 Badin NC 280090576//704-422-5774/7044225776 No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance Records/Reports Self -Monitoring Program Facility Site Review Effluent/Receiving Waters Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date erto Scheller MRO WQ//252-946-6481/ Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date W. Corey Basinger MRO WQ//704-235-2194/ EPA Form 3560-3 (Rev 9- 4) Previous editions are obsolete. Page# NPDES yr/mo/day Inspection Type NCO076775 I11 121 18/02/15 117 18 JCJ Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) 1 Page# 2 Permit: NCO076775 Owner - Facility: Falls Powerhouse Inspection Date: 02/15/2018 Inspection Type: compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ 0 ❑ application? Is the facility as described in the permit? E ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ ❑ 0 ❑ Is access to the plant site restricted to the general public? N ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: The current NPDES permit for Falls Powerhouse (NC0076775) became effective on March 1, 2014 and expires at midnight on Jaunuary 31, 2019. Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? N ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ E' ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? N ❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? E ❑ ❑ ❑ # Is the facility using a contract lab? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑ 0 ❑ Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ E ❑ Incubator (80D) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ N ❑ Comment: Field parameters for pH and temperature are performed under field certification #5122. - Testing of Oil and Grease is sent out to Test America for analysis. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? N ❑ ❑ ❑ Is all required information readily available, complete and current? E ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? 0 ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? E ❑ ❑ ❑ Is the chain -of -custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Page# 3 Permit: NCO076775 Owner - Facility: Falls Powerhouse Inspection Date: 02/1512018 Inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? 0 ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ 0 ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ M ❑ on each shift? Is the ORC visitation log available and current? 0 ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? M ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? ❑ ❑ M ❑ Is a copy of the current NPDES permit available on site? i ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ 0 ❑ Comment: ORC keeps visitation log on -site. Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? ❑ ❑ 0 ❑ Is flow meter calibrated annually? ❑ ❑ 0 ❑ Is the flow meter operational? ❑ ❑ 0 ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ ❑ Comment: Flows for outfalls #001. 002. 003. 004. 005. and #007 are estimated as reouired in Part I (A of current permit. Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? ❑ ❑ M ❑ Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ 0 ❑ Comment: No foam or oil sheen was noted at points of discharge. Page# 4 United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN i 2 15 I 3 I NCO081949 I11 121 18/02/15 I17 18 i C i 19 i G i 201 I 2111111] 11111.11111111111111111111 11111111111 f6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA --- Reserved-- I I 72 I �, I 73 � 74 751 1. 1 1 1 1 I 180 67 70 i, i 71 J J L J ty Data Section B: Facility Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 12:16PM 18/02/15 14/03/01 Tuckertown Powerhouse 711 Tuckertown Rd Exit Time/Date Permit Expiration Date New London NC 28127 12:36PM 18/02/15 19/01/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Beverly P Whitley/ORC/704-422-5614/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Mark J Gross, PO Box 576 Badin NC 280090576//704-422-5774/7044225776 No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance Records/Reports Facility Site Review Effluent/Receiving Waters Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Robert Scheller MRO WQ//252-946-6481/ pp Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date W. Corey Basinger MRO WQ//704-235-2194/ EPA Forn 3560-3 (Rev 9-94) Previous editions are obsolete Akz- Z i Page# NPDES yr/mo/day Inspection Type 1 31 NCO081949 I11 121 18/02/15 117 18 JCJ Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) r ti Page# 2 Permit: NCO081949 Owner -Facility: Tuckertown Powerhouse Inspection Date: 02/15/2018 Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ 00 application? Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? 0 ❑ ❑ ❑ Is access to the plant site restricted to the general public? M ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? S ❑ ❑ ❑ Comment: The current NPDES permit #NC0081949 for Tuckertown Powerhouse was issued on March 1 2014 and expires on midnight January 31, 2019. Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? M ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ N ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: Records reviewed were well organized and maintained. Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑ # Is the facility using a contract lab? N ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑ ❑ Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ 0 ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ 0 ❑ Comment: Effluent samples are collected on annual basis by qrab method. Analyses for pH_ and temperature are conducted under field certification #5122. Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? ❑ ❑ 0 ❑ Is flow meter calibrated annually? ❑ ❑ 0 ❑ Is the flow meter operational? ❑ ❑ M ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ 0 ❑ Comment: Flow is estimated and reported annual. Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? ■ ❑ ❑ ❑ Page# 3 Permit: NC0081949 Inspection Date: 02/15/2018 Owner - Facility: Tuckertown Powerhouse Inspection Type: Compliance Evaluation Effluent Pipe Are the receiving water free of foam other than trace amounts and other debris? If effluent (diffuser pipes are required) are they operating properly? Comment: There was no foam of oil sheens from discharge noted at time of inspection. Yes No NA NE ❑ ❑ ❑ ❑ ❑ M ❑ Page# 4 United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN I 2 15 I 3 I NCO081957 I11 121 18/01,15 I17 18 I C I 19 1 G I 201 I 21111111 1111111111111111111111111 11111111111 f6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA----------Reserved-- -- 67 701z 1 71 itI JI I 72 1 �, 1 731 1 174 751 1 1 1 1 1 I 180 L_J LJ I I Section 8: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 11:17AM 18/01/15 14/03/01 Narrows Powerhouse 37720 Pine St Exit Time/Date Permit Expiration Date Badin NC 28009 11:50AM 18/01/15 19/01/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Beverly P Whitley/ORC/704-422-5614/ i Name, Address of Responsible Official title/Phone and Fax Number . Contacted Mark J Gross, PO Box 576 Badin NC 280090576/l104-422-5774/7044225776 No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance Records/Reports Self -Monitoring Program Facility Site Review Effluent/Receiving Waters Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date MRO WQ//252-946-6481/ 4herloller (n Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date W. Corey Basinger MRO WQ//704-235-2194/ EPA III Form 3560-3 (Rev 9-94) Previous editions are obsolete.,C . • ,a� �. 1111G will c �'I Page# NPDES yr/mo/day Inspection Type 31 NCO081957 I11 121 18/01/15 117 18 ICI Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) 1 Page# 2 Permit: NCO081957 Owner -Facility: Narrows Powerhouse Inspection Date: 01/15/2018 Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ 00 application? Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ ❑ M, ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? ❑ ❑ ❑ Comment: The current NPDES (NC0081957) permit for Narrows Powerhouse was issued on March 1, 2014 and expires at midnight on January 31 2019. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? ■ ❑ ❑ ❑ Is all required information readily available, complete and current? M ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? M ❑ ❑ ❑ Are analytical results consistent -with data reported on DMRs? 0 ❑ ❑ ❑ Is the chain -of -custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑0 ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 2417 with a certified operator ❑ ❑ M ❑ on each shift? Is the ORC visitation log available and current? 0 ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? 0 ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? M ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? M ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ 0 ❑ Comment: Records reviewed during inspection were well organized and maintained. Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? M ❑ ❑ ❑ Page# 3 Permit NC0081957 Owner - Facility: Narrows Powerhouse Inspection Date: 01/15/2018 Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ 0 ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: Facility discharqes once -through coolinq water via outfalls # 001. 002. 005. 006. 007. Sum drain discharges via out fall #003. Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑ # Is the facility using a contract lab? 0 ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ■ ❑ ❑ ❑ Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ ■ ❑ ❑ ❑ ■ ❑ Comment: Field analyses for pH and temperature are conducted under field laboratory certification #5122. Test America performs analyses for Oil and Grease. Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? ❑ ❑ M ❑ Is flow meter calibrated annually? ❑ ❑ M ❑ Is the flow meter operational? ❑ ❑ M ❑ (If units are separated) Does the chart recorder match the flow meter? ❑ ❑ 0 ❑ Comment: Flow is estimated as required in the current permit Part I (A.) Page# 4 Water Resources ENVIRONMENTAL QUALITY August 25, 2016 Mark Gross Alcoa Power Generating Inc Yadkin Division PO Box 576 Badin, NC 28009-0576 Subject: NPDES Electronic Reporting Requirements Narrows Powerhouse NPDES Permit Number: NCO081957 Dear NPDES Permittee: PAT MCCRORY Governor DONALD R. VAN DER VAART Secretary S. JAY ZIMMERMAN Director RECEIVEDINCDENRIDWR AUG 2 9 2016 WQROS MOORESVILLE REGIONAL OFFICE The U.S. Environmental Protection Agency (EPA) recently published the National Pollutant Discharge Elimination System (NPDES) Electronic Reporting Rule. The rule requires NPDES regulated facilities to report information electronically, instead of filing written paper reports. The rule does not change what information is required from facilities. It only changes the method by which information is provided (i.e., electronic rather than paper -based). EPA is phasing in the requirements of the rule over a 5-year period. The two phases of the rule, and their key milestones, are: • Phase 1—Starting on December 21, 2016, regulated entities that are required to submit Discharge Monitoring Reports (DMRs) will begin submitting these reports electronically. If you are currently reporting your DMR data electronically using eDMR, then you simply need to continue reporting in the same way as you are now. The key change is that, starting on December 21, 2016, electronic reporting of DMRs will be required, instead of voluntary. • Phase 2—Starting on December 21, 2020, regulated entities that are required to submit certain other NPDES reports will begin submitting these reports electronically. Reports covered in the second phase include Notices of Intent to discharge in compliance with an NPDES general permit, Sewer Overflow/Bypass Event Reports, and a number of other NPDES program reports. Incorporating Electronic Reporting Requirements into NPDES Permits The NPDES Electronic Reporting Rule requires authorized NPDES programs to incorporate electronic reporting requirements into NPDES permits beginning December 21, 2015. Under the new rule, the electronic reporting process supersedes the paper reporting process. According to our files, your NPDES permit became effective after November 2013, and should contain the requirement to electronically report your Discharge Monitoring Reports using NC DWR's eDMR system. In addition to requiring permittees to report information electronically, the rule also requires permittees to identify the initial recipient for the NPDES electronic reporting data [see 40 CFR 122.41(1)(9)]. Initial State of North Carolina I Environmental Quality I Water Resources 1617 Mail Service Center I Raleigh, North Carolina 27699-1617 919 807 6300 recipient of electronic NPDES information from NPDES-regulated facilities (initial recipient) means the entity (EPA or the state authorized by EPA to implement the NPDES program) that is the designated entity for receiving electronic NPDES Data [see 40 CFR 127.2(b)]. Permittees are required to electronically submit the required NPDES information to the appropriate initial recipient, as determined by EPA. By July 18, 2016, EPA must identify and publish on its web site and in the Federal Register a listing of initial recipients by state and by NPDES data group. Once available, you can use EPA's web site to find out or determine the initial recipient of your electronic submission. NC DWR has submitted a request to EPA to be the initial recipient for the following NPDES data groups: 1. Discharge Monitoring Reports; 2. General Permit Reports [Notices of Intent to discharge (NOls); Notices of Termination (NOTs)]; 3. Pretreatment Program Reports; and 4. Sewer Overflow/Bypass Event Reports EPA's web site will also link to the appropriate electronic reporting tool for each type of electronic submission for each state. Instructions on how to access and use the appropriate electronic reporting tool will be available as well. For more information on EPA's NPDES Electronic Reporting Rule, visit http://www2.epa.gov/compliance/final-national-pollutant-discharge-elimination-system-npdes- electronic-reporting-rule. For more information on electronic reporting to NC DWR, visit http://deg.nc.gov/about/divisions/water-resources/edmr/npdes-electronic-reporting or contact Vanessa Manuel at 919-807-6392 or via email at Vanessa.Manuel@ncdenr.gov. Sincerely, Jeffre4j O. P&vf for S. Jay Zimmerman, P.G. Cc: NPDES File Central Files I�orl�ie Re�ior��,i[�ffiee�/ W�ater�Qua,IityaProgram ct- q. WaterResources GNVIR04MGN7.AL QUALITY June 7, 2016 Mr. Mark Gross Alcoa Power Generating, Inc. P.O. Box 576 Badin, NC 28009 PAT MCCRORY ri'='='N DDLDER VAART Scentoy S. JAY ZIMMERMAN 7.'rlmcvor Subject: Compliance Evaluation Inspection Narrows Powerhouse NPDES Permit No. NCO081957 Stanly County Dear Mr. Gross: Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted at the subject facility on June 6, 2016 by Ori Tuvia. Beverly Whitley's cooperation during the site visit was much appreciated. Please advise the staff involved with this NPDES Permit by forwarding a copy of the enclosed report. The report should be self-explanatory; however, should you have any questions concerning this report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at ori.tUvia@ncdenr.gov. Cc: NPDES Unit MRO Files Sincerely, Ori Tuvia, Environmental Engineer Mooresville Regional Office Division of Water Resources, DEQ Mooresville Regional Office Location: 610 East Center Ave., Suite 301 Mooresville, NC 28115 Phone: (704) 663-1699 \ Fax (704) 663-6040 \ Customer Service:1-877-623-6748 United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (Le'., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 IN 1 2 15 1 3 I NC0081957 I11 121 16/06/06 117 18 LCJ 19 1 s I 20I I 2111 1 1 1 1 1 1 1 1 11 1.I 1 l i I I I I 1 1 1 I I l i l l l I I I l it I l �l l 166 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved 67 70 id I 71 iLti J1 72 i ti i 731 I 174 751 I I I I I I I80 L_I L_I I I I Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Numbed 09:20AM 16/06/06 14/03/01 Narrows Powerhouse NCSR 1704 Exit Time/Date. Permit Expiration Date Badin NC 28009 12:25PM 16/06/06 19/01/31 Names) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Beverly P Whitley/ORC/704-422-5614/ Michael Ramon Mears/ORCf704-422-5627/ Name, Address of Responsible Officialfritle/Phone and Fax Number Contacted Mark J Gross,PO Box 576 Badin NC 280090576/1704-422-5774/7044225776 No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance . Records/Reports Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Ori A Tuvia MRO WQ/f704-663-1699/ G%//6 Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date W. Corey Basinger MRO WQ//704-235-2194/ .EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# NPDES yr/mo/day Inspection Type 1 31 NCo061 s57 I11 121 16/06/06 117 18 ICI Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) Page# 2 Permit: NCO081957 Owner -Facility: Narrows Powerhouse Inspection Date: 06/06/2016 Inspection Type: Compliance Evaluation Permit Yes No NA NE (if the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ 0 ❑ application? Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ M ❑ ❑ Is access to the plant site restricted to the general public? ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: The subject permit expires on 1/31/2019 Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? M❑ ❑ ❑ Are all records. maintained for 3 years (lab. reg. required 5 years)? 0 ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? ❑ ❑ ❑ Is the chain -of -custody complete? ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs_ complete: do they include all permit parameters? M ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? '❑ ❑ ❑ (If the facility is = or'> 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ ❑ on each shift?: Is the ORC, visitation log available and current? .❑ ❑ El Is the ORC certified at grade equal to or higher than the facility classification? ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the -facility cla§sification? 0 ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? M ❑ ❑ ❑ Facility has copy of previous year's Annual Reporton file for review? ❑ ❑ M, ❑ Comment: The records reviewed during the inspection were organized and well maintained. Discharge Monitoring Reports (annual monitoring requirements) were reviewed for 2014 and 2015. Laboratory Yes No NA NE Are .field parameters performed by certified personnel or laboratory? 0 ❑ ❑ ❑ Page# 3 Permit: NCO081957 Owner -Facility: Narrows Powerhouse Inspection Date: 06/06/2016 Inspection Type: compliance Evaluation - Laboratory Yes. No NA NE Are all other parameters(excluding field parameters) performed by a certified lab? 0 ❑ ❑ ❑ # Is the facility using a contract lab? ❑ ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees M ❑ ❑ ❑ Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ ❑ Incubator (BOD) set'to 20.0.degrees Celsius +/-1.0 degrees? ❑ ❑ 0 ❑ Comment: On -site field analyses (PH and temperature) are performed under Alcoa's field laboratory certification #5122. Test America has also been contracted to perform the effluent oil & grease analyses for Outfall 003. The pH meter appeared to be properly calibrated and documented. Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ ❑ Is sample_ collected below all treatment units? Is proper volume collected? Is the tubing clean? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type representative)? Comment: The subject permit requires effluent grab samples. Flow Measurement - Effluent # Is flow meter used for reporting? Is flow, meter calibrated annually? Is the flow meter operational?� (If units are separated) Does the chart recorder match the flow meter? ■ ❑ ❑ ❑ ■ ❑ ❑ ❑ ❑ ❑ M ❑ ❑. ❑ ❑ 0 [I'll ❑ Yes No NA NE E3.0 ❑ ❑ ❑ M ❑ ❑ ❑ ■ ❑ ❑ ❑ K ❑ Comment: Flow measurements are based on calculations that include pipe diameter, pipe volume and duration of discharge. In addition, facility -staff have installed flow meters at Units #1 and #2 Effluent Pipe Yes No NA NE Is right of way to the outfall properly,maintained? ❑ El El Are the receiving water free of foam other than trace amounts and other debris? ❑ ❑ ❑ If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ M ❑ Comment: No oil sheens or foam were observed in the effluent/receiving stream. Page# 4 Permit: NCO081957 Owner -Facility: Narrows Powerhouse Inspection Date: 06/06/2016 Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? M ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ 0 ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The facility appeared to be properly operated and well maintained. Detailed records are maintained on -site regarding the annual sump cleaning events and the weekly tailrace and floor sump/rope skimmer inspections. The rope/skimmer system is equipped with a oil/water detection system and a twenty-four (24) hour dispatch/notification system. All recovered oil is transported to a storage tank (off -site) for ultimate disposal by a contracted company. Page# 5 Pat McCrory Governor A14, L *A 1 [1 NCDENR North Carolina Department of Environment and Natural Resources Division of Water Resources Water Quality Programs Thomas A. Reeder Director August 28, 2013 Mr. Mark J. Gross Alcoa Power Generating, Inc. Post Office Box 576 Badin, North Carolina 28009 Subject: Compliance Evaluation Inspection Narrows Powerhouse NPDES Permit No. NCO081957 Stanly County Dear Mr. Gross: John E. Skvarla, III Secretary Enclosed is a copy of the Compliance Evaluation Inspection Report for the inspection conducted at the subject facility on August 20, 2013 by Mr. Wes Bell of this Office. Please inform the facility's Operator -in - Responsible (ORC) of our findings by forwarding a copy of the enclosed report. The report should be self-explanatory; however, should you have any questions concerning this report, please do not hesitate to contact Mr. Bell at (704) 235-2192 or at wes.bell2ncdeningov. Sincerely, 4�,-( Michael L. Parker Regional Supervisor Surface Water Protection Section Enclosure: Inspection Report cc: Stanly County Health Department W. Mooresville Regional Office Location: 610 East Center Ave., Suite 301 Mooresville, NC 28115 Phone: (704) 663-16991 Fax: (704) 663-60401 Customer Service: 1-877-623-6748 Internet: www.ncwatergtiality.org One NorthCarolina NahilrallY An Eaual Cnoortunity 1 Affirmative Action Emolover— 30% Recvcled110% Post Consumer paper United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance InspPrAgon Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 INI 2 15 I 31 NCO081957 111 121 13/08/20 117 18I C I 19I S I 20I II Remarks 21I1111111IIIIIIIIIIII IIIIIIIIIIIIIIII IIII1111M6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA---------------- -Reserved----- — - — 67I 1.0 169 70141 711 N I 721 N I 73I I 174 751 I I I I I I 180 u _I Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 10:45 AM 13/08/20 09/10/01 Narrows Powerhouse Exit Time/Date Permit Expiration Date NCSR 1704 Badin NC 28009 11:50 PM 13/08/20 14/01/31 Name(s) of Onsite Representative (s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Beverly P Whitley/ORC/704-422-5614/ Mike Mears//704-422-5637 / Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Mark J Gross,PO Box 576 Badin NC 280090576NP Hydro No Ope ratio ns/704-422-5774/7044225776 Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance Records/Reports Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters Laboratory Section D: Summary of Find in /Comments Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Wes Bell MRO WQ//704-663 1699 Ext.2192/ / r � j Si nature of Management Q A Re imewer Agency/Office/Phone and Fax Numbers ate I Marcia Aflocco MRO WQH704-663-1699 Ext.2204/ EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page # 1 NPDES yr/mo/day Inspection Type NCO081957 I11 12I 13/08/20 117 18I CI Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) Page # 2 Permit: NCO081957 Owner - Facility: Narrows Powerhouse Inspection Date: 08/20/2013 Inspection Type: Compliance Evaluation (If the present permit expires in 6 months or less). Has the permittee submitted a new application? ■ n n n Is the facility as described in the permit? ■. n n n # Are there any special conditions for the permit? ❑ ❑ ■ n Is access to the plant site restricted to the general public? ■ n n n Is the inspector granted access to all areas for inspection? ■ n n n Comment: The subject permit expires on 1/31/2014. The Division received the permit renewal package on 7/16/2013. The last compliance evaluation inspection was performed on 5/7/2010. Record Keeping Yes No NA Nt Are records kept and maintained as required by the permit? ■ n n n Is all required information readily available, complete and current? ■ n n n Are all records maintained for 3 years (lab. reg. required 5 years)? ■ n n n Are analytical results consistent with data reported on DMRs? ■ n In n Is the chain -of -custody complete? ■ n n n Dates, times and location of sampling ■ Name of individual performing the sampling ■ Results of analysis and calibration ■ Dates of analysis ■ Name of person performing analyses ■ Transported COCs ■ Are DMRs complete: do they include all permit parameters? ■ n n n Has the facility submitted its annual compliance report to users and DWQ? n n ■ n (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift? n n ■ Is the ORC visitation log available and current? ■ n n n Is the ORC certified at grade equal to or higher than the facility classification? ■ n n n Is the backup operator certified at one grade less or greater than the facility classification? ■ n n n Is a copy of the current NPDES permit available on site? ■ In In n Facility has copy of previous year's Annual Report on file for review? n n ■ n Page # 3 Permit: NCO081957 Inspection Date: 08/20/2013 Record Keeping Owner - Facility: Narrows Powerhouse Inspection Type: Compliance Evaluation Comment: The records reviewed during the inspection were organized and well maintained. Discharge Monitoring Reports (annual monitoring requirements) were reviewed for 2012 and 2013. A daily pH limit violation (<6.0 s.u.) was reported for Outfall 002 in January 2013; however, the additional effluent pH monitoring results performed at this outfall during the preceding months (February 2013 and March 2013) were all compliant. This Office has previously addressed the above -noted pH violation. Laboratory Are field parameters performed by certified personnel or laboratory? Are all other parameters(excluding field parameters) performed by a certified lab? # Is the facility using a contract lab? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? Comment: On -site field analyses (pH and temperature) are performed under Alcoa's field laboratory certification #5122. Test America has also been contracted to perform the effluent oil & grease analyses for Outfall 003. The pH meter appeared to be properly calibrated and documented. Effluent Sampling Is composite sampling flow proportional? Is sample collected below all treatment units? Is proper volume collected? Is the tubing clean? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type representative)? Comment: The subject permit requires effluent grab samples. Operations & Maintenance Is the plant generally clean with acceptable housekeeping? C Yes No NA NE Yes No NA NE ■ n n n ■nnn ■nnn ■nnn nn■n nn■n .I - Yes No NA NE ■nnn Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge ❑ n ■ ❑ Judge, and other that are applicable? Page # 4 Permit: NCO081957 Inspection Date: 08/20/2013 Operations & Maintenance Owner - Facility: Narrows Powerhouse Inspection Type: Compliance Evaluation Comment: The facility appeared to be properly operated and well maintained. Detailed records are maintained on -site regarding the annual sump cleaning events and the weekly tailrace and floor sump/rope skimmer inspections. The rope/skimmer system is equipped with a oil/water detection system and a twenty-four (24) hour dispatch/notification system. All recovered oil is transported to a storage tank (off -site) for ultimate disposal by a contracted company. KfA .IC Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? ❑ ❑ ■ Is flow meter calibrated annually? ❑ Q ■ n Is the flow meter operational? n n ■ n (If units are separated) Does the chart recorder match the flow meter? n n ■ n Comment: Flow measurements are based on calculations that include pipe diameter, pipe volume, and duration of discharge. In addition, facility staff have installed flow meters at Units #1 and #2. Effluent Pipe Yes No NA NE Is right of way to the outfall properly maintained? ■ ❑ 0 11 Are the receiving water free of foam other than trace amounts and other debris? ■ ❑ 0 ❑ If effluent (diffuser pipes are required) are they operating properly? Q 0 ■ 0 Comment: No oil sheens or foam were observed in, the effluent/receiving stream. Page # 5 Collection System SS® 24-Hour Notification Collection System: Number and Name WQCS#- ,op/0U Incident Number from BIMS 201500 Incident Reviewed (Date): Incident Action Taken: BPJ NOV 2015-DV DV-2015- a Ono aaaammammanaMONO amman®ameaaa®aammmma®ammaeaaaaaammaKogan mmaaamaammn" Spill Date Reported Date .l 'o, Time am/ pm Time am/ pm Reported To SWP Staff or EM Staff / Reported By �� �� 1 U >'-�A Address of Spill County Cause of.Spill �1L !�-? - - l Total Estimated Gallons -4 ' 4'" z::e Stream Fish h Kill. Yes Phone Est. Gal to Stream No Number Species. Non Required Information arid other comments relating to SSO incident: Response time minutes Zone Map Quad North Carolina Emergency Management - EM43 Reporting Page 1 of 4 EM43 Reporting EM Level: NCEM Edited: Include in Report: 4 Yes Yes Taken by: Date/Time Reported: Date/Time Occurred: Michael Bennett 11/19/2015 11:21:47 11/19/2015 11:13:47 Reported by: Agency: Phone: NRC USCG County: City: Area: Stanly Badin 11 Street Address: Zip Code: 37720 Pine street EVENT TYPE Type: HazMat Animal Disease Event Type: Bomb Threat Event Type: Complaint Event Type: Fire Event Type: FNF Event Type: FNF Class: HazMat Event Type: HazMat Class: HazMat Mode: Hydraulic Oil Petroleum Fixed Facility Homeland Security Event: Non-FNF Event: Non-FNF Event Type: Other Event Type: SAR Type: Transportation Event Type: Wastewater Event Type: Weather Event Type: Weather Event Name: WMD Event Type: State Resource Request https://www.nesparta.net/eoc7/boards/board.aspx?tableid=275&viewid=1011 &label=EM... 11 /20/2015 North Carolina Emergency Management - EM43 Reporting Page 2 of 4 r Event Description: NRC forwarded a report from the Alcoa Power Generating Inc. that 1 gallon of hydraulic oil released from a crane into Badin Lake due to an unknown cause. Pads were deployed. US EPA, USCG, and NC DEQ DWQ notified by NRC. NCEM on -call area coordinator notified by NCEOC. NRC1133835 11192015.pdf Deaths: Injuries: 0 0 Responsible Party: Alcoa Power Generating Inc. Point of Contact: Mark Gross Latitude: 00.000000 RRT Request: RRT Approved: Evacuation: Radius: 0 0 Responsible Party Phone: 704-517-8364 Point of Contact Phone: 704-517-8364 Longitude: -00.000000 RRT Team Number: RRT Mission Number: https://www.nesparta.net/eoc7/boardsiboard.aspx?tableid=275&viewid=1011 &label=EM... 11 /20/2015 North Carolina Emergency Management - EM43 Reporting Page 4 of 4 LEMC: I:293 CHealth: PWRK: AC: Advised ENV MGMT: WATER: Advised CAP: DOT: Notes: 1135 - emailed J. Ramsey - mb 1232 - J. Ramsey ackn - mb Filename: Filename: Filename: Filename: Filename: Filename: Filename: Filename: Filename: NOTIFICATIONS SO: LFD: Sewer: Other Local Agencies: SHP/SWP: DRP: Other State Agencies: ATTACHMENTS https://www.ncsparta.net/eoc7/boardsiboard.aspx?tableid=275&viewid=1011 &label=EM... 11 /20/2015 AA Incident Report # 1133835 INCIDENT DESCRIPTION *Report taken by: E4 JONATHAN KARIAM at 11:13 on 19-NOV-15 Incident Type: FIXED Incident Cause: UNKNOWN Affected Area: BADIN LAKE Incident occurred on 19-NOV-15 at 00:01 local incident time. Affected Medium: WATER BADIN LAKE REPORTING PARTY Name: NARK GROSS Organization: ALCOA POWER GENERATING INC Address: 37720 PINE ST BADIN, NC PRIMARY Phone: (704)5178364 Type of Organization: PRIVATE ENTERPRISE SUSPECTED RESPONSIBLE PARTY Name: NARK GROSS Organization: ALCOA POWER GENERATING INC Address: 37720 PINE ST BADIN, NC PRIMARY Phone: (704)5178364 INCIDENT LOCATION 37720 PINE ST County: STANLY City: BADIN State: NC RELEASED MATERIAL(S) CHRIS Code: OHY Official Material Name: HYDRAULIC OIL Also Known As: HYDRAULIC OIL (NO -SHEEN 32) Qty Released: 1 GALLON(S) Qty in Water: 1 GALLON(S) DESCRIPTION OF INCIDENT CALLER STATED A CRANE LEAKED OIL FROM ON TOP OF THE DAM INTO THE WATER BELOW. SENSITIVE INFORMATION INCIDENT DETAILS Package: N/A Building ID: Type of Fixed Object: POWER PLANT Power Generating Facility: UNKNOWN Generating Capacity: Type of Fuel: NPDES: NPDES Compliance: UNKNOWN ---WATER INFORMATION --- Body of Water: BADIN LAKE Tributary of: Nearest River Mile Marker: Water Supply Contaminated: UNKNOWN IMPACT Fire Involved: NO Fire Extinguished: UNKNOWN INJURIES: NO Hospitalized: Empl/Crew: Passenger: FATALITIES: NO Empl/Crew: Passenger: Occupant: EVACUATIONS:NO Who Evacuated: Radius/Area: Damages: NO Hours Direction of Closure Type Description of Closure Closed Closure N Air: N Major Road: Artery:N N Waterway: N Track: Environmental Impact: UNKNOWN Media Interest: UNKNOWN Community Impact due to Material: REMEDIAL ACTIONS PADS DEPLOYED. Release Secured: YES Release Rate: Estimated Release Duration: WEATHER Weather: RAINY, °F ADDITIONAL AGENCIES NOTIFIED Federal: State/Local: State/Local On Scene: State Agency Number: NOTIFICATIONS BY NRC CENTERS FOR DISEASE CONTROL (GRASP) 19-NOV-15 11:17 (770)4887100 DHS NOC (NOC) 19-NOV-15 11:17 (202)2828114 DHS I&A STATE AND LOCAL PRGM OFFICE (RALEIGH, NC FUSION CENTER) 19-NOV-15 11:17 (202)5575179 DHS SOUTH CAROLINA FUSION CENTER (LE SENSITIVE ADVISORS & LIASON PROGRA 19-NOV-15 11:17 (866)4728477 DOT CRISIS MANAGEMENT CENTER (MAIN OFFICE) 19-NOV-15 11:17 (202)3661863 U.S. EPA IV (MAIN OFFICE) (404)6504955 U.S. EPA IV (NC/SC INCIDENTS) 19-NOV-15 11:17 (404)6504955 U.S. EPA IV (DUTY OSC) 19-NOV-15 11:17 (404)6504955 NC DEPT OF EMERGENCY MGMT (MAIN OFFICE) 19-NOV-15 11:17 (800)8580368 NC OCCUPATIONAL ENVMTL EPIDEMIOLOGY (COMMAND CENTER) 19-NOV-15 11:17 (919)7075950 NC PUBLIC HEALTH PREPARE AND RESPNS (PHPR COMMAND CENTER) 19-NOV-15 11:17 (919)7150919 NATIONAL INFRASTRUCTURE COORD CTR (MAIN OFFICE) 19-NOV-15 11:17 (202)2829201 NOAA RPTS FOR NC (MAIN OFFICE) 19-NOV-15 11:17 (206)5264911 NATIONAL RESPONSE CENTER HQ (AUTOMATIC REPORTS) 19-NOV-15 11:17 (202)2671136 DOI FOR REGION 4 (MAIN OFFICE) 19-NOV-15 11:17 (404)3314524 SEAHAWK IOC (INTER -AGENCY OPERATIONS CENTER) 19-NOV-15 11:17 (803)2060971 STATE OF NORTH CAROLINA DENR (MAIN OFFICE) 19-NOV-15 11:17 (919)8076300 TSA OFFICE OF SECURITY OPERATIONS (SURFACE COMPLIANCE BRANCH SE REGION) 19-NOV-15 11:17 (904)9804075 USCG DISTRICT 5 (D5 DRAT) 19-NOV-15 11:17 (757)3986231 USCG DISTRICTS (INTEL CHIEF) 19-NOV-15 11:17 (757)3986655 ADDITIONAL INFORMATION I MAY 21 2013 OfJ 643i71ME"I.-I, ILE E ;._GJO'efaL 0d F1p'_ May.17, 2013 Mr. Michael L. Parker Regional Supervisor — Surface Water Protection NC DENR — Division of Water Quality Mooresville Regional Office 610 East Center Avenue, Suite 301 Mooresville, NC 28115 Re. NOV-2013-LV-0253 Dear Mr. Parker, APGI Yadkin Division Highway 740 PO Box 576 Badin, NC 28009 This letter is in response to the above -referenced NOV and the telephone conversation you had with Henk van der Meyden on April 22, 2013. Alcoa Power Generating, Inc. (APGI) is providing additional information to support our original claim that the pH sample collected on January 25, 2013 was not representative of the discharge from Outfall 002; that the reported pH value resulted from a blockage and stagnant water in the sampling line; and, that no discharge of actual low pH water occurred. We had previously indicated in our February 15, 2013 correspondence to the Mooresville Regional Office that this is what likely occurred, and, with additional sampling, have in our view since confirmed it. The pH reading in question was the only measurement taken in January and at the time of the DMR preparation, there was insufficient information to conclusively refute the result. Therefore, the result was reported and included in the DMR for January. As part of the follow- up investigation into the incident, and to ensure that the annual sampling requirement for Outfall 002 was satisfied, weekly pH readings were obtained in February and March. These results have been reported on DMRs submitted to the DWQ and clearly indicate that the pH values of the subsequent sampling from Outfall 002 are in compliance with the permit limits. Supporting pages from the two DMR reports are attached to this letter. Outfall 002 merely conveys Yadkin River water that is used as cooling water for the generator. There are no additives or processes that can affect the pH of this water before it is discharged. The design of the Narrows Powerhouse makes it physically impossible to safely collect a sample directly from the Outfall 002 discharge. Therefore, the pH measurement in question was of water, not from the actual discharge at Outfall 002, but from a closed end sample line. Prior to collecting the sample, the sample line was not purged, and therefore, the sample that was collected was of stagnant water that had built up in the sample line. For the subsequent pH sampling, the sample line was purged. This ensured that the sample collected represented what was actually being discharged. Again, all of the pH results from this subsequent sampling were compliant with the pH limits in the permit. This confirmed for us that the sample collected on January 25, 2013 was not representative of what was actually discharged at Outfall 002, and N therefore, no violation had actually occurred. Accordingly, we respectfully request that the above -referenced NOV be rescinded. We appreciate your consideration of this matter. If you have any questions or comments regarding this matter, please contact me at (704) 422-5774 or Henk van der Meyden at (843) 572-5361. Sincerely, T4 I " Mark vJ.s 11 attachments CC. Henk van der Meyden 3 s p TPDESPEWITNO.:NC0081957 DISCHARGE NO.: 002 M_O_NT_H_i YEAR ACILITYNAME YADKIN -NARROWS POWERHOUSE February j 2013 'OUNTY. STANLY ;CLASS: GRADE I PH YSICAL/ CHEMICAL )PERATOR IN RESPONSIBLE CHARGE. Beverly Whitley I (Signature of Operator in Responsible Charge) DATE I �By SSIGNAIURF, ICERTIFY THATIHIS REPORTIS IACCURATEAND COMPLEEETO THEBESTOFMY KNO WLEDGE OPER- ATOR OPER- ATOR ORC 50050 00030 00400 ARRIVAL TIME ON EFFL. DATE TIME ON SITE SITE FLOW TEMP pH HRS HRS Y/N MGD Celsius Units o 02 03 04 05 7 06 08 o 10 12 -3. 7.3 1413. -16 ... 0.2 '6.6 16 IN Iffiff"T M, LEWT-MONTHLYAVG �F NPDES PERMIT NO.: NCO081957 DISCHARGE NO.: 002 _ MONTH ---YEAR FACILITYNAMR' YADKIN -NARROWS POWERHOUSE _ _ March 2013 COUNTY STANLY CLASS: GRADE 1 PHYSICAL/ CHEMICAL — OPERA TORINRESPONSIBLECHARGE: Beverly Whitley _--__ - - —--I ix _ .. - -- - -- --- ---. --- -- -- - - - -'- --- ---1 (Signature of Operator in Responsible Charge) DATE -- - - IBY THIS SIGNATURE, I CERTIFY THATTHIS REPORTIS I ACCURATEANDCOMPLEIETOTHEBESTOFMYKNOWLEDGE — — -� -----T---�---- ------- ------� 1 OPER- OPER 50050 00010 TEMP 00400 AT OR ATOR ORC ARRIVAL, TIME EFFL. FLOW pH --- DATE — TIME _ ON SITE _—.ON SITE HRS HRS Y/N MGD Celsius Units I 02 04 06 -� 0,7,�:,o, 7.3. ---, 08 10 1 12 14 09:50 0.2 Y 14.9 7.3 V 16 18 19 20 -- — 2-ig;Y.']5.7 , , .73 22 — 24,v F26 09:01 0.2 Y 16.9 7.1 c r30,,,_ n AVERAGE lAM 51 6.9 7.3 Mumum 14.9 7.1 LIlBT-MONTHLYAvG I N/AN/A G G6M'P/'6"B 6.0 ---- ---_-- �, LIMLT-DAILY,MAX N/A N/A 9.0 —_ r•'� wrjL NC®ENR North Carolina Department of Environment and Natural Resources Division of Water Quality Pat McCrory Charles Wakild, P.E. Governor Director April 17, 2013 Mr. Mark Gross Alcoa Power Generating, Inc. P.O. Box 576 Badin, North Carolina 28009 Subject: Notice of Violation — Effluent Limitation Tracking #: NOV-2013-LV-0253 Narrows Powerhouse WWTP NPDES Permit No. NCO081957 Stanly County Dear Mr. Gross: John E. Skvarla, III Secretary A review of the January 2013 self -monitoring report for the subject facility revealed a violation of the following parameter at Outfall 002: Date Parameter Reported Value Permit Limit 1/25/13 pH 5.1 SU 6.0 SU (Daily minimum) Remedial actions, if not already implemented, should be taken to correct any problems. Since the comments section on the January 2013 Discharge Monitoring Report provided an explanation for the noted effluent limit violation, a response to this notice is not required; however, should you have additional information concerning the violations or comments which you wish to present, please submit them to the attention of Ms. Marcia Allocco. If the violations are of a continuing nature, not related to operation and/or maintenance problems, and you anticipate remedial construction activities, then you may wish to consider applying for a Special Order by Consent. If you have questions concerning this matter, please do not hesitate to contact Ms. Allocco or me at (704) 663-1699. Sincerely, r g Michael L. Parker Surface Water Protection Regional Supervisor cc: Point Source Branch Mooresville Regional Office Location: 610 East Center Ave., Suite 301 Mooresville, NC 28115 Phone: (704) 663-16991 Fax: (704) 663-60401 Customer Service: 1-877-623-6748 Internet: hftp://poral.ncdenr.org/web/wq An Equal Opportunity', Affirmative Action Employer— 30% Recycled/10% Post Consumer paper NorthCarolina Nah(i "if I , FV MALCOA RECEIVED DIVISION OF l,N,,,TER QUALITY Alcoa Inc. APGI -Yadkin FEB 2 6 2013 Highway 740 PO Box 576 SINP, MOORESV9LLE REGIONAL OFFICE Badin, NC 28009 February 15, 2013 Certified Mail Receipt- 7009 0960 0000 3368 8506 North Carolina Department of Natural Resources Mooresville Regional Office -610 East Center Ave. Mooresville, NC 28115 ATTN: Mike Parker Re: Alcoa Power Generating, Inc. - NPDES Permit No. NCO081957 To Whom It May Concern: This submittal is to satisfy the five (5) day written notification requirement in our NPDES Permit (Part II Section E.6.). On 2013 January 25, a pH of 5.1 was measured in the discharge of Outfall 002 from the Narrows Powerhouse. This matter was discovered during the preparation of the DMR. Upon discovery this was immediately reported via telephone by Randall Kiser to Wes Bell in the NCDENR Mooresville Regional Office on February 13. At this time, and after interviewing the individual collecting the sample, we believe that the January measurement was not representative of the effluent being discharged, The Outfall 002 discharge is once -through cooling water and similar in nature and volume (>150,000 gpd) to the discharges of Outfalls 005 and 007. pH measurements taken at approximately the same time on the same day from these Outfalls showed values of 7.1 and 7.3, respectively. An additional pH measurement was taken on February 13, 2013 with a value of 7.32. The person collecting the measurement reported that the sampling line had very little flow and needed to be cleaned out before the sample could be collected. Stagnant water in the sampling line may have impacted the January measurement. APGI is working diligently to confirm the cause and solve the problem. We will be collecting additional pH measurements from this discharge over the next several weeks to confirm that this was indeed a non -representative sample. These results will be reported on future DMRs. In addition, standard procedures on collecting and reporting 56 Pr Alcoa Inc. APGI - Yadkin Highway 740 PO Box 576 Badin, NC 28009 of effluent measurements will be reviewed with the affected personnel, including the importance of immediate reporting. If you have any questions regarding this matter, please do not hesitate to contact me at 704 422 5774 or Henk van der Meyden at 843 572 5361. I certify, under penalty of law, that this document and all attachments were prepared _under my direction or supervision in accordance with a system -designed -to -assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. i am aware that there are significant penalties for submitting false information, including the possibility of fines and imprisonment for knowing violations. Sincerely, Mark J. Gross APGI cc: Henk van der Meyden, Alcoa — Mt. Holly Randall Kiser, Alcoa Inc. Pr to ALCOA February 15, 2013 RECEIVED /� I DIVISION OF WATER QUALITY FEB 2 0 2013 MOORESVILLE REGIONAL OFFICE North Carolina Department of Natural Resources Mooresville Regional Office 610 East Center Ave. Mooresville, NC 28115 ATTN: Mike Parker Re: Alcoa Inc. NPDES Permit No. NC0004308 To Whom It May Concern: Alcoa - Badin Works NC Hwy. 740 & NCSR 1719 Badin, NC 28009 USA Tel: 1 704 422 5774 Fax: 1 704 422 5776 Over Night Mail This submittal is to satisfy the five (5) day written notification requirement in our NPDES Permit (Part II Section E.6.). On 2013 February 11, we received analytical results from samples collected at Outfall 005 during the week of February 3rd. The results reported from the lab showed that the facility failed the chronic toxicity test. At this time, we are investigating the results with the lab to see if we can determine what caused the toxicity. On 2013 February 12, Randall Kiser of my staff verbally reported the information to the Mooresville Regional Office of the Department. We continue to investigate the issue and we will keep the Department apprised of any further findings and additional actions that we take to address this matter. Please do not hesitate to contact me at 704 422 5774 or Randall Kiser of my staff at 704 422 5685. North Carolina Department of Natural Resources Mooresville Regional Office February 15, 2013 Page 2 1 certify, under penalty of law, that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. 1 am aware that there are significant penalties for submitting false information, including the possibility of fines and imprisonment for knowing violations. Sincerely, )�l - - , 44trA Mark Gr s Plant Manager, Badin Works cc: Randall Kiser, Alcoa Inc. It I NCDENR North Carolina Department of Environment and Natural Resources Division of Water Quality Beverly Eaves Perdue Coleen H. Sullins Dee Freeman Governor Director Secretary May 20, 2010 Mr. Mark Gross Alcoa Power Generating, Inc. Post Office Box 576 Badin, North Carolina 28009 Subject: Compliance Sampling Inspection Narrows Powerhouse NPDES Permit No. NCO081957 Stanly County, NC Dear Mr. Gross: Enclosed is a copy of the Compliance Sampling Inspection Report for the inspection conducted at the subject facility on May 7, 2010 by Mr. Wes Bell of this Office. Please advise the facility's Operator -in -Responsible Charge by forwarding a copy of the enclosed report. The. report should be self-explanatory; however, should you have any questions concerning this report, please do not hesitate to contact Mr. Bell at (704) 663-1699. Sincerely, Marcia Allocco Acting Regional Supervisor Surface Water Protection Enclosure: Inspection Report cc: Stanly County Health Department Mooresville Regional Office Location: 610 East Center Ave., Suite 301 Mooresville, NC 28115 Phone: (704) 663-1699 \ Fax: (704) 663-6040 \ Customer Service:1-877-623-6748 Internet: http://portal.ncdenr.org/webtwq An Equal Opportunity \ Affirmative Action Employer _ 50% Recycled/10% Post Consumer paper One - NorthCarolina Aahav:`ly United States Environmental Protection Agency Form Approved. EPA Washington, D.C. 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 I NI 2 151 31 N00081957 111 121 10/05/07 117 181SI 191 SI 20I Remarks 2111IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII111116 Inspection Work Days Facility Self -Monitoring Evaluation Rating 131 QA ------------------------ — Reserved ------------ -------- 67 I 1.5 169 70 19 I 711 N I 72I N I 73 IW I 174 751 I I I I I Li 80 Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 02:05 PM 10/05/07 09/10/01 Narrows Powerhouse Exit Time/Date Permit Expiration bate NCSR 1704 Badin NC 28009 03:16 PM 10/05/07 14/01/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Beverly P Whitley/ORC/704-422-5614/ Mark J Gross//704-422-5637 /7044225776 Name, Address of Responsible Official/Title/Phone and Fax Number Mark J Gross,PO Box 576 Badin NC 280090576//704-422-5774/7044225776oected Yes Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit ■ Flow Measurement Operations & Maintenance ■ Records/Reports Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters Laboratory Section D: Summary of Finding/Comments Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Wesley N Bell `! 1 J MRO WQ//704-663-1699 Ext.2192/ ® .0 ., Sgnature of Management Q A l3pvieWer Agency/Office/Phone and Fax Numbers Date MRO WQ//704-663-1699 Ext.2204/ Marci Allocco EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page # 1 Permit: NC0081957 Owner — Facility: Narrows Powerhouse Inspection Date: 05/07/2010 Inspection Type: Compliance Sampling Reason for Visit: Routine Inspection Summary: Location pH Temperature Upstream* 6.85 24.1 °C Effluent (003) 6.50 19.1 °C Effluent (005) 6.29 21.4 °C Notes: * denotes location not required to be monitored by the Permit. Upstream sampling location was adjacent to dam. Page: 2 Permit: NCO081957 Owner - Facility: Narrows Powerhouse Inspection Date: 05/07/2010 Inspection Type: Compliance Sampling Permit (If the present permit expires in 6 months or less). Has the permittee submitted a new application? Is the facility as described in the permit? # Are there any special conditions for the permit? Is access to the plant site restricted to the general public? Is the inspector granted access to all areas for inspection? Comment: The subject permit expires on 1/31/14. Record Keeping Are records kept and maintained as required by the permit? Is all required information readily available, complete and current? Are all records maintained for 3 years (lab. reg. required 5 years)? Are analytical results consistent with data reported on DMRs? Is the chain -of -custody complete? Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? Has the facility submitted its annual compliance report to users and DWQ? (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift? Is the ORC visitation log available and current? Is the ORC certified at grade equal to or higher than the facility classification? Is the backup operator certified at one grade less or greater than the facility classification? Is a copy of the current NPDES permit available on site? Facility has copy of previous year's Annual Report on file for review? Yes No NA NE ■ n n n ■nnn n n n ■ ■nnn ■ n n n ■ ■ ■ ■ ■ ■ ■ n n n nn■n nn®n ■nnn ®nnn ■nnn ■ n n n nn®n Page # 3 Permit: NCO081957 Inspection Date: 05/07/2010 Owner -Facility: Narrows Powerhouse Inspection Type: Compliance Sampling --- I- KIA AIG Record Keeping Comment: The records reviewed during the inspection were organized and well maintained. The self -monitoring data for 2009 was reviewed and no effluent limit violations were reported and all monitoring frequencies were correct. The ORC and/or Backup ORC visitations should also be documented for each monthly DMR that is submitted in the future. Note: These visitations and maintenance activities (by the ORC and staff) have been properly documented in a log that is maintained on -site. Yes No NA NE Laboratory Are field parameters performed by certified personnel or laboratory? ■ n n n Are all other paramete rs(excluding field parameters) performed by a certified lab? ® n 00 ■nnn # Is the facility using a contract lab? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? nnn Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ ■ ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? n n ■ n Comment: On -site field analyses (pH and temperature) are performed under laboratory certification #5122 (Alcoa, Inc.). Test America, Inc. (Certification #269) has also been contracted to provide analytical support. The pH meter appeared to be properly calibrated (and documented). Yes No NA NE Effluent Sampling nn■n Is composite sampling flow proportional? Is sample collected below all treatment units? ■ 00 n ■ 00 n Is proper volume collected? nn■n Is the tubing clean? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? nn■n Is the facility sampling performed as required by the permit (frequency, sampling type representative)? ■ n n n Comment: The subject permit only requires effluent grab samples. Yes No NA NE Operations & Maintenance Is the plant generally clean with acceptable housekeeping? ■nnn Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge n n Judge, and other that are applicable? Comment: The facility appeared to be properly operated and well maintained. The oil/water separator is equipped with an oil detection/monitoring system (24-hour dispatch system) that notifies personnel of oil sheens 1/4" or greater. No biocides are added to the once -through cooling water and no chemical wheel pit cleaning is performed. Yes No NA NE Flow Measurement - Effluent Page # 4 Permit: NC0081957 Inspection Date: 05/07/2010 Flow Measurement - Effluent owner - Facility: Narrows Powerhouse Inspection Type: Compliance Sampling # Is flow meter used for reporting? Is flow meter calibrated annually? Is the flow meter operational? (If units are separated) Does the chart recorder match the flow meter? Comment: The reported flows are based on flow calculations (includes pipe diameter, pipe volume, and duration of discharge). Effluent Pipe Is right of way to the outfall properly maintained? Are the receiving water free of foam other than trace amounts and other debris? If effluent (diffuser pipes are required) are they operating properly? Comment: No oil sheens or floatable solids were observed in the receiving stream (below the permitted Outfalls). See "Summary" Section for the results of the on -site monitoring performed during the inspection. Page # 5 0 ALCOA 2008 January 04 NC Division of Water Quality 610 East Center Ave Mooresville, NC 28125 Attention: Mr. Rob Krebs Alcoa Primary Metals Alcoa Power Generating Inc. Yadkin Division 293 NC 740 Hwy PO Box 576 Badin, NC 28009-0576 USA CERTIFIED MAIL RETURN RECEIPT REQUESTED 4570 5241 RE: Annual Monitoring - Narrows Powerhouse - NCO081957 Dear Mr. Krebs, As a follow-up to our conversation with Mr. Mike Parker of your office yesterday, Alcoa Power Generating Inc is providing the Division of Water Quality with this follow-up letter to report an oversight related to the required annual monitoring required by our NPDES permit. The NPDES permit for the Narrows Powerhouse requires annual monitoring of temperature & pH for the non -contact cooling water discharges from the generators. The ORC planned on performing the monitoring during the fourth quarter of 2007, however, during the fourth quarter Narrows Unit #2 was taken down for an extended maintenance outage and the ORC was unable to perform the required monitoring for Outfall 006 during 2007. The remaining three units which are exactly like unit #2 were monitored as required and were determined to be in compliance with the permit. APGI will perform the required monitoring on unit #2 as soon as the unit is returned to service in the Spring of 2008. If you have any questions regarding this matter, please feel free to contact me at (704) 422 -5774. A .r Sincerely, R L iVE D Mark J. oss JAN - 8 2008 Vice President of Operations Alcoa Power Generating, Inc NC DENR MRO mernail Z. T. Gibson J. D. Morton - PGH m-Surface Water Protection W. L. McCaskill R. D. Dworek — PGH Legal B. P. Whitley 6documents'and settings\mccaswNocal settings\temporary internet fi1es\o1k3cb\narrow monitoring oversight 2007.doc Y-,�— 111A. Michael F. Easley, Gover r William G. Ross Jr., Secretary North Carolina Department of Environment and Natural Resources Alan W. Klimek, P.E. Director Division of Water Quality November 21, 2006 Mark Gross, Vice President of Operations Alcoa Power Generating, Inc. Post Office Box 576 Badin, North Carolina 28009-0576 Subject: Compliance Evaluation Inspection Narrows Powerhouse NPDES Permit No. NCO081957 Stanly County, N.C. Dear Mr. Gross: Enclosed is a copy of the Compliance Evaluation Inspection Report for the inspection conducted at the subject facility on November 16, 2006, by Mr. Wes Bell of this Office. Please advise the facility's Operator -in -Responsible Charge of our findings by forwarding a copy of the enclosed report. The report should be self-explanatory; however, should you have any questions concerning this report, please do not hesitate to contact Mr. Bell or me at (704) 663-1699 Sincerely, John Lesley Acting Regional Supervisor Surface Water Protection Enclosure cc: Stanly County Health Department WN NorthCarolina 4C®ENR naturally Mooresville Regional Office Division of Water Quality Phone 704-663-1699 Customer Service Internet: www.ncwateraualitv.org 610 East Center Ave, Suite 301 Mooresville, NC 28115 Fax 704-663-6040 1-877-623-6748 An Equal Opportunity/Affirmative Action Employer— 50% Recycled/10% Post Consumer Paper • United States Environmental Protection Agency Form Approved. E n ^ Washington, D.C. 20460 r/"1 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 I,,,l 2 15I 11 NCO081957 111 12106/11/16 117 18I CI 191 SI 20I I �J —J Remarks 21111111111111111111111111111111111111111111111U6 Inspection Work Days Facility Self -Monitoring Evaluation Rating 61 QA --------------------------- Reserved ---------------------- 67 I 1.517014 I 71I N I 72INI 73L 75I I I I I I I 180 Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) Narrows Powerhouse 11:56 AM 06/11/16 05/05/01 Exit Time/Date Permit Expiration Date NCSR 1704 Badin NC 28009 12:42 PM 06/11/16 09/01/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data Beverly P Whitley/ORC/704-422-5614/ . William L McCaskill//704-422-5639 / Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Mark J Gross,PO Box 576 Badin NC 280090576//704-422-5774/7044225776 No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenance Records/Reports Self -Monitoring Program Sludge Handling Disposal Facility Site Review ® Effluent/Receiving Waters Laboratory Section D: Summary of Find in /Comments Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Wesley N Bell MRO WQ//704-663-1699 Ext.231/ 7 Sign ture of Management Q P Rev' wer Agency/Office/Phone and Fax Numbers Date �j Marcia Allocco MRO WQ//704-235-2204/ EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page # 1 FF' Permit: NCO081957 Owner - Facility: Narrows Powerhouse Inspection Date: 11/16/2006 Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new application? ❑ ❑ ■ ❑ Is the facility as described in the permit? ■ ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ ❑ ■ ❑ Is access to the plant site restricted to the general public? ■ ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? ■ ❑ ❑ ❑ . Comment: The Division issued a permit modification on January 23, 2004 regarding the removal of Special Condition A(3)-Penstock Sump Drains and the changing of the first DMR submittal date to January 30, 2005. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? ■ ❑ ❑ ❑ Is all required information readily available, complete and current? ■ ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? ■ ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? ■ ❑ ❑ ❑ Is the chain -of -custody complete? ■ 0 ❑ ❑ Dates, times and location of sampling ■ - Name of individual performing the sampling ■ I Results of analysis and calibration ■ Dates of analysis ■ Name of person performing analyses ■ Transported COCs ■ Are DMRs complete: do they include all permit parameters? ■ ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ ■ ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 2417 with a certified operator on each shift? ❑ ❑ ■ ❑ Is the ORC visitation log available and current? ■ ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? ■ ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility classification? ■ ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? ■ ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ■ ❑ Page # 3 . Permit: NCO081957 Inspection Date: 11/16/2006 Owner - Facility: Narrows Powerhouse Inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Comment: DMRs were reviewed for year of 2005. No limit violations were reported and all monitoring frequencies were correct. Weekly inspections at the oil/water separator were documented in a maintenance/visitation log book. The facility staff incorporate a commendable record keeping system. Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? ■ ❑ Are all other parameters(excluding field parameters) performed by a certified lab? ■ ❑ n ❑ # Is the facility using a contract lab? ■ ❑ ❑ ❑ Is proper temperature set for sample storage (kept at 1.0 to 4.4 degrees Celsius)? n ■ Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ Q ■ ❑ Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ ■ n Comment: On -site field analyses are performed under the laboratory certification #5122. The laboratory instrumentation utilized for field analyses appeared to be properly calibrated. The facility staff must ensure the pH meter calibration times are documented in the future. Effluent Sampling Yes No NA NE Is composite sampling flow proportional? n n ■ Cl Is sample collected below all treatment units? ■ ❑ ❑ ❑ Is proper volume collected? ■ ❑ 0 Is the tubing clean? Cl n ■ n Is proper temperature set for sample storage (kept at 1.0 to 4.4 degrees Celsius)? n n ■ rl Is the facility sampling performed as required by the permit (frequency, sampling type representative)? ■ n n n Comment: Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? ■ Q ❑ Cl Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge n ❑ ■ n Judge, and other that are applicable? Comment: The facility appeared to be properly operated and well maintained. Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? n n ■ n Is flow meter calibrated annually? n ❑ ■ n Is the flow meter operational? n n ■ n (If units are separated) Does the chart recorder match the flow meter? n n ® n Page # 4 Permit: NCO081957 Inspection Date: 11/16/2006 Flow Measurement - Effluent Owner - Facility: Narrows Powerhouse Inspection Type: Compliance Evaluation Comment: The effluent flows for all outfalls are based on engineering calculations. Effluent Pipe Is right of way to the outfall properly maintained? Are the receiving water free, of foam other than trace amounts and other debris? If effluent (diffuser pipes are required) are they operating properly? Comment: The effluents from all outfalls (001, 002, 003, 005, 006, 007) appeared clear with no foam. The receiving stream did not appear to be negatively impacted. Page # 5 o f, 2006 May 15 1 NC Division of Water Quality 610 East Center Ave Mooresville, NC 28125 Attention: D. Rex Gleason, P.E. Alcoa Primary Metals Alcoa Power Generating Inc. 293 NC 740 Hwy PO Box 576 Badin, NC 28009-0576 USA Fax:1 704 422 5776 CERTIFIED MAIL�`,;,r M:z - `11e1=S RETURN RECEIPT REQ,I ,5.TEV `. 2011 9448r' MAY 1 2ot: RE: Oil Spill at the Narrows Powerhouse — NCO081957 Dear Mr. Gleason, CATER k'-' LITY SECTI As a follow-up to our conversation with Mr. Mike Parker of your office today, Alcoa Power Generating Inc is providing the Division of Water Quality with this follow-up letter to report a minor oil spill which occurred at the Narrows Powerhouse this morning. The spill occurred about 9:30 a.m. on 5/15/06 while a contractor was utilizing a concrete saw to cut through the concrete decking above the flood gates at the Narrows Powerhouse. While making a cut, the contractor noticed oil dripping from the breather cap on the saw. In the process of moving the saw, it is estimated that approximatel 6 — 8 ounces of oil spilled onto the concrete deck. The contractor's employees took imme 1a e steps to contain and clean-up the oil that was spilled by applying oil absorbent and using rags to wipe it up. The defective equipment was removed from the job site and replaced with properly operating equipment. There was no release to any surface water, however, since the spill occurred within 100 feet of Badin Lake, Alcoa is reporting the spill in accordance with G.S.143-215.85. If you have any questions regarding this matter, please feel free to contact me at (704) 422 -5774. Sincerely, Mark J. ss Vice President of Operations Alcoa Power Generating,, Inc_ cc:email L T. Gibson Dudley Dean — Fluor Engineering W. L. McCaskill B. P.- Whitley p:\winword\environ\water\n.c.division ofwater quality\incident reporting\na rows oil spill 5-15-06.doc