Subject: Notice of Violation
Compliance Evaluation Inspection
NOV-2017-PC-0693
IMC-MetalsAmerica, LLC.
NPDES Permit No. NCG500221
Cleveland County
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted
at the subject facility on November 2, 2017 by Mr. Ori Tuvia. Your representative Scott Lankas
cooperation during the site visit was much appreciated. Please advise the staff involved with this
NPDES Permit by forwarding a copy of the enclosed report.
Two main areas of concern were observed during the inspection:
1) At the time of the inspection, the facility staff was unable to indicate the location of the
boiler blowdown discharge.
2) At the time of the inspection, the facility did not have any sampling records for pH, flow and
temperature as required. Sampling records must be kept for a minimum of 3 years.
In order to address these issues, sampling should be conducted on days when the boiler is
in use and there is no precipitation. The sampling location should be at the same point storm
water sampling is collected.
Mooresville Regional Office
Location: 610 East Center Ave„ Suite 301 Mooresville, NC 28115
Phone: (704) 663-16991 Fax: (704) 663.60401 Customer Service:1.877=623-6748
E'nvironmen tal
Quality
ROY COOPER
Governor
MICHAEL S. REGAN
Secretary
LINDA CULPEPPER
I Interim Director
The report should be self-explanatory; however, should you have any questions
concerning this report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at
ori.tuviana,ncdenr. gov.
Sincerely,
W. Corey Basinger
Regional Supervisor
Mooresville Regional Office
Division of Water Resources
cc: NPDES (Derek Denard)
MRO Files
Mooresville Regional Office
Location: 610 East Center Ave., Suite 301 Mooresville, NC 28115
Phone: (704) 663-1699 \ Fax: (704) 663-6040 \ Customer Service: 1-877-623-6748
1_.--- I. ....... _......__.._: __
F,
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fee Type
1 IN 2 15 1 3 I NCG500221 1.11 12 17/11/02 17 18 ICI 19 I s I 20I I
21111.1111111111111111111111111111111111� f6
Inspection Work Days Facility Self -Monitoring Evaluation Rating 131 QA Reserved
67 1.0 70 71 72 LNJ 731 751 1 1 1 1 1 1J80
Section B: FacilityData
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
12:OOPM 17/11/02
15/11/19
IMC-MetalsAmerica, LLC
135 Old Boiling Springs Rd
Exit Time/Date
Permit Expiration Date
Shelby NC 28152
01:15PM 17/11/02
20/07/31
Name(s) of Onsite Representative(s)/Tities(s)/Phone and Fax Number(s)
Other Facility Data
///
Scott Lankas/1704-692-3057!
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Steve Ryan,135 Old Boiling Springs Rd Shelby NC 28152/Plant
Man ager/704-471-6505/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Facility Site Review Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ori A Tuvia MRO WQ//704-663-1699/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger MRO WQ//704-235-2194/
EPA Form 60-3 (Rev 9-94) Previous edit ns are obsolete.Afto DEW 1A-
Page#
NPDES yr/mo/day Inspection Type
31 NCG500221 121 1 7/l 1/02 17 18 ICI
Section D: Summary of Finding/Comments (Attach additional -sheets of narrative and checklists as necessary)
Page# 2
F
Permit: NCG500221 Owner - Facility: IMC-MetalsAmerica, LLC
Inspection Date: 11/02/2017 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
M
❑
application?
Is the facility as described in the permit?
M
❑
❑
❑
# Are there any special conditions for the permit?
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment:
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
❑
0
❑
❑
Is all required information readily available, complete and current?
❑
0
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
❑
M
❑
❑
Are analytical results consistent with data reported on DMRs?
❑
❑
E
❑
Is the chain -of -custody complete?
❑
❑
M
❑
Dates, times and location of sampling
❑
Name of individual performing the sampling
❑
Results of analysis and calibration
❑
Dates of analysis
❑
Name of person performing analyses
❑
Transported COCs
❑
Are DMRs complete: do they include all permit parameters?
❑
❑
M
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
0
❑
(If the.facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
0
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
M
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
M
❑
Is a copy of the current NPDES permit available on site?
M
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Comment: No sampling recordes were avilable for review at the time of the inspection. pH sampling
was done during the inspection.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? M ❑ ❑ ❑
Page# 3
Permit: NCG500221 Owner - Facility: IMC-MetalsAmerica, LLC
Inspection Date: 11/02/2017 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑' ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The following processes are present at the facility:
Air Compressor — oily water from the air compressor flows to the floor of the basement
liquids are pumped into two tanks capable of holding up to 13,000 gallons Heritage Crystal
pumps out said tanks Bi-monthly averaging approximately 4,500 Gallons. Cooling Towers -
new cooling towers installed at the facility coolers are closed loop with no discharge: only
discharge during maintenance. Maintenance related discharge goes into wastewater
collection system treated by the city of Shelby.
Boiler — boiler is used once a week. Blowdown from the boiler goes into the storm water
system. Boiler must be sampled semi-annually for PH. Flow and temperature. PH calibration
standards were out of date at the time of the inspection. At the time of the inspection facility
staff was instructed as to how to properly calibrate, sample and record the required
sampling.
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ ❑
M ❑
Is sample collected below all treatment units? ❑ ❑
0 0
Is proper volume collected? ❑ ❑
0 ❑
Is the tubing clean? ❑ ❑
0 ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type ❑0
❑ ❑
representative)?
Comment: Facility does not test for DH, flow and temperature like it is required. Samplinq will be
conducted bi-annually on day when the boiler is used and there is no
precipitation. The
sampling location should be at the same point storm water sampling
is collected.
Effluent Pipe
Yes No NA NE
Is right of way to the outfall properly maintained?
❑
0
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
❑
❑
0
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
N
❑
Comment: Effluent location was not identified at the time of the inspection. facility staff must find the
discharge location of boiler blowdown.
Page# 4
C2�
Environmen t-al
Quality
November 20, 2015
Mr. Steven Ryan, Plant Manager
IMC-MetalsAmerica, LLC.
135 Old Boiling Springs Road
Shelby, NC 28152
PAT M.C.CRORY
CoYetrtnr
D.ONALD R. VA DER'.VA:ART
Secretary
Subject: Notice of Deficiency
Compliance Evaluation Inspection
NOD-2015-PC-0287
IMC-MetalsAmerica, LLC.
NPDES Permit No. NCG500221
Cleveland County
Dear Mr. Ryan:
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted at
the subject facility on November 19, 2015 by Mr. Ori Tuvia. Your representative Jeff Adeholdt
cooperation during the site visit was much appreciated. Please advise the staff involved with this
NPDES Permit by forwarding a copy of the enclosed report.
Two main areas of concern were observed during the inspection:
1) The average PH sampled of the boiler blowdown was 9.5, higher than the required range of 6-9.
2) The facility does not test for flow and temperature like it is required.
In order to address these issues sampling should be conducted on day when the boiler is used
and there is no precipitation. Sampling location, in order to let the temperature of the water
and the PH settle down, should be at the same point storm water sampling is collected.
The report should be self-explanatory; however, should you have any questions concerning
this report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at ori.tuviakncdenr.2ov.
Sincerely,
�4+tom
Michael L. Parker Regional Supervisor
Pr
Mooresville Regional Office
Water Quality Regional Operations Section
Division of Water Resources, DEQ
Enclosure:
Inspection Report
cc: MSC 1617-Central Files/Baserrient
Cleveland County Health Department
Mooresville Regional Office
Location: 610 East Center Ave., Suite 301 Mooresville, NC 28115
Phone: (704) 663-1699 \ Fax: (704) 663-6040 \ Customer Service:1-877-623-6748
Internet: www.ncwaterquality.org
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
1
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day 'Inspection Type Inspector Fac Type
1 IN 2 15 1 3 I NCG500221 I11 12 15,11/19 17 181r.1 191 c I 20Lj
211I I l l l i I I �I I II l l l i l i l l l l l l i l l l l l l l II I I f6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
67
73I 74 75 1 1 1 1 1
72 LNJ
1.0 70 [aJ 71 [li
80
Section B: FacilityData
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
09:30AM 15/11/19
15/11/19
IMC-MetalsAmerica, LLC
Exit Time/Date
permit Expiration Date
135 Old Boiling Springs Rd
Shelby NC 28152
11:00AM 15/11/19
20/07/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Jeff Aderholdt//704-471-6528 /
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Steve Ryan,135 Old Boiling Springs Rd Shelby NC 28152/Plant
No
Managerf704-471-6505/
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenanct: Records/Reports
Self -Monitoring Program Facility Site Review Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ori A Tuvia MRO WQ/f704-663-1699/
Signature of Management Q A Review Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES
yr/mo/day
31 NCG500221 I11 121 15/11/19 I17
Inspection Type
18 lCl
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCG500221 Owner -Facility: IMC-MetalsAmerica, LLC
Inspection Date: 11/19/2015 Inspection Type: Compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
M
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
M
❑
❑
Is access to the plant site restricted to the general public?
M
❑
❑
❑
Is the inspector granted access to all areas for inspection?
i
❑
❑
❑
Comment:
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
❑
0
❑
❑
Is all required information readily available, complete and current?
❑
S
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
❑
❑
M
❑
Is the chain -of -custody complete?
❑
❑
M
❑
Dates, times and location of sampling
❑
Name of individual performing the sampling
❑
Results of analysis and calibration
❑
Dates of analysis
❑
Name of person performing analyses
❑
Transported COCs
❑
Are DMRs complete: do they include all permit parameters?
❑
❑
®
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
M
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24n with a certified operator
❑
❑
®
❑
on each shift?
Is the ORC visitation log available and current?
❑
❑
M
❑
Is the ORC certified at grade equal to or higher than the facility classification?
❑
❑
0
❑
Is the backup operator certified at one grade less or greater than the facility classification?
❑
❑
M
❑
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
M
❑
Comment: Monthly Sampling of boiler been done for PH, no sampling been done for flow or
tempertaure.
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? ❑ ❑ 0 ❑
Page# 3
Permit: NCG500221
Inspection Date: 11/19/2015
Owner -Facility: IMC-MetalsAmerica, LLC
Inspection Type: Compliance Evaluation
Laboratory
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/-1.0 degrees?
Comment: Sampling done inhouse sampels are then iced and sent to shealby lab for testing.
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Yes No NA NE
❑ ❑ N ❑
❑ ❑ N ❑
❑ ❑ N ❑
❑ ❑ ■ ❑
❑ ❑ M ❑
Yes No NA NE
❑ ❑ ❑.
❑ ❑ ■ ❑
Comment: The following processes are present at the facility:
Air Compressor — oily water from the air compressor flows to the floor of the basement,
liquids are pumped into two tanks capable of holding up to 13,000 gallons. Heritage Crystal
pumps out said tanks Bi-monthly averaging approximately 4,500 Gallons.
Cooling Towers- new cooling towers installed at the facility coolers are closed loop with no
discharge: only discharge during maintenance. Maintenance related discharge goes into
wastewater collection system treated by the city of Shelby.
Boiler — boiler is used once a week. Blowdown from the boiler goes into the storm water
system. Boiler is sampled for PH, no sampling been done for Flow or temperature.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Yes No NA NE
❑ ❑ ■ ❑
M ❑ ❑ ❑
❑ ❑ N ❑
❑ ❑ E ❑
❑ ❑ ■ ❑
Is the facility sampling performed as required by the permit (frequency, sampling type ❑ 0 ❑ ❑
representative)?
Comment: Facility does not test for flow and temperature like it is required. Sampling will be conducted
bi-annually. on day when the boiler is used and there is no precipitation. Sampling location, in
order to let the temperature of the water and the PH settle down, should be at the same
point storm water sampling is collected.
Page# 4
Weaver, Charles
From: Weaver, Charles GOC ✓ A,
Sent: Thursday, November 19, 2015 10:15 AM
To: 'dick@imc-group.com'
Cc: 'dick@imc-ma.com'; 'david@imc-ma.com'
Subject: renewal of NCG500221 / IMC-MetalsAmerica
Attachments: NCG50 Final 093015.pdf, Technical Bulletin - NCG500000 2015.doc
Importance: High
Attached you will find the updated version of NPDES General Permit NCG500000, effective 10/1/2015. Discard any
previous versions of the General Permit and use this version until further notice.
You do not need a reprinted Certificate of Coverage, as the one issued to you in 2007 is still applicable.
Thank you for your patience during the longer -than -expected renewal period.
If you have any questions about this matter, simply reply to this message.
Charles H. Weaver
Environmental Specialist
N.C. Division of Water Resources
N.C. Department of Environmental Quality
919-807-6391
charles.weaver(aMcdenr.gov
(physical address) 512 North Salisbury Street, Raleigh, NC 27604
(mailing address) 1617 Mail Service Center, Raleigh, NC 27699-1617
--"Nothing Compares . _
Email correspondence to and from this address is subject to the North Carolina Public Records Law and may be disclosed
to third parties.
RECE!V ED IN C D EN R I DVU R
s•
u' b
WOROS
M0ORE5�1!LL.E RF ,!ONIALOFFICE
1
Weaver, Charles
From: Microsoft Outlook
To: dick@imc-ma.com; david@imc-ma.com
Sent: Thursday, November 19, 2015 10:16 AM
Subject: Relayed: renewal of NCG500221 / IMC-MetalsAmerica
Delivery to these recipients or groups is complete, but no delivery notification was sent by.the
destination server:
dick(abimc-ma.com (dick(-gbimc-ma.com)
david(&imc-ma.com (david(&imc-ma.com)
Subject: renewal of NCG500221 / IMCGMetalsAmerica
renewal of
NCG50a221 / IM...
1
tr#
Zlow
::
L A��
NCDENR
North Carolina Department of Environment and Natural Resources
Beverly Eaves Perdue
Governor
Mr. Richard W. Strachan
IMC-MetalsAmerica, LLC
135 Old Boiling Springs Rd
Shelby, NC 28152
Dear Permittee:
Division of Water Quality
Charles Wakild, P.E.
Director
August 3, 2012
Dee Freeman
RECEIVED �cretary
DIVISIONS OF IArA, i ER QUANI
Y
SEP 2 8 2012
SWP ,'d+EC T iON
iAOORESVILLE REGIONAL OFFICE
Subject: Renewal of coverage / General Permit NCG500000
IMC-MetalsAmerica
Certificate of Coverage NCG500221
Cleveland County
The Division is renewing Certificate of Coverage (CoC) NCG500221 to discharge under NPDES
General Permit NCG500000. This CoC is issued pursuant to the requirements of North Carolina General
Statue 143-215.1 and the Memorandum of Agreement between North Carolina and the US Environmental
Protection agency dated October 15, 2007 [or as subsequently amended].
If any parts, measurement frequencies or sampling requirements contained in this General Permit
are unacceptable to you, you have the right to request an individual permit by submitting an individual
permit application. Unless such demand is made, the certificate of coverage shall be final and binding.
Please take notice that this Certificate of Coverage is not transferable except after notice to the
Division. The Division may require modification or revocation and reissuance of the certificate of coverage.
Contact the Mooresville Regional Office prior to any sale or transfer of the permitted facility.
Regional Office staff will assist you in documenting the transfer of this CoC.
This permit does not affect the legal requirements to obtain other permits which may be required by
the Division of Water Quality or permits required by the Division of Land Resources, Coastal Area
Management Act or any other Federal or Local governmental permit that may be required.
If you have any questions concerning the requirements of the General Permit, please contact John
Hennessy [919 807-6377 or john.hennessy@ncdenr.gov].
Sincerely,
Original signed by John Hennessy
for Charles Wakild, P.E.
cc: 1,11gooresville Regional Office % Sur fice Water Protection
NPDES file - _ -- --- - - - — - -
1617 Mail Service Center, Raleigh, North Carolina 27699-1617
512 North Salisbury Street, Raleigh, North Carolina 27604
Phone: 919 807-63001 FAX 919 807-6489 / Internet: wvvw.ncwaterquality.org
An Equal Opportunity/Affirmative Action Employer - 50% Recycled/10% Post Consumer Paper
Nne
orthCarohna
Naturally
STATE OF NORTH CAROLINA
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
DIVISION OF WATER QUALITY
GENERAL PERMIT NCG500000
CERTIFICATE OF COVERAGE NCG500221 4 ,
TO DISCHARGE NON -CONTACT COOLING WATER, COOLING TOWER AND
BOILER BLOWDOWN, CONDENSATE AND SIMILAR WASTEWATERS UNDER THE
NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM
In compliance with the provision of North Carolina General Statute 143-215.1, other lawful standards and
regulations promulgated and adopted by the North Carolina Environmental Management Commission, and
the Federal Water Pollution Control Act, as amended,
IMC-MetalsAmerica, LLC
is hereby authorized to discharge Boiler Blowdown & Cooling Tower Blowdown from a
facility located at
IMC-MetalsAmerica
135 Old Boiling Springs Rd
Shelby
Cleveland County
to receiving waters designated as Brushy Creek in subbasin 03-08-04 of the Broad River
Basin in accordance with the effluent limitations, monitoring requirements, and other
conditions set forth in Parts I, II, III and IV hereof.
This Certificate of Coverage shall become effective August 3, 2012.
This Certificate of Coverage shall remain in effect for the duration of the General Permit.
Signed this day August 3, 2012
Original signed by John Hennessy
for Charles Wakild, Director
Division of Water Quality
By Authority of the Environmental Management Commission
COMPLIANCE EVALUATION INSPECTION CHECKLIST
DATE:.. ORC:
ENTRY TIME: NPDES PERMIT NO: NC00...
EXIT TIME: FACILITY NAME:
COUNTY:
NIET WITH ON -SITE:
PERMIT: EFFECTIVE DATE: EXPIRATION DATE:
FLOW MEASUREMENT: INSTANTANEOUS/CONTINUOUS-RECORDING/TOTALIZER (IN PERMIT) .
EFFLUENT/RECEIVING STREAM: STREAM NAME:
SLUDGE DISPOSAL: NON -DISCHARGE PERMIT #:(If Applicable)
RECORD KEEPING:
LABORATORY: CERTIFICATION (FIELD) #. (pH, TRC, DO; Temp., SS, Cond.)
-OPERATION & MAINTENANCENACILITY SITE REVIEW:
IMC-MetalsAmerica, LLC
135 Old Boiling Springs Road, Shelby, NC 28152
(phone) 704-471-6505 (fax) 704-471-6513 (email) dickgimc-group.com
November 10, 2011
Mrs. Marcia Allocco
Division of Water Quality
NCDENR
610 East Center Ave., Suite 301
Mooresville, NC 28115
Ref: Tracking #: NOV-2011-PC-0585
Dear Mrs. Allocco,
DIVISION OFWq RECEIVED
NOV 14 2011
SW, SECTION
MOORESVILLE REGIONAL OFFICE
Although we were aware of the stormwater runoff sampling required under our Stormwater
Discharge Permit, we were unaware of the requirement to sample non -contact cooling water
discharges as explained by Mr. Wes Bell during his visit here on November 1, 2011. Mr. Bell
explained the requirements of our NPDES Permit No. NCG500221 to me.
We utilize an outside laboratory, Shealy Environmental Services Inc. Of Charlotte NC, for
sampling and testing of other plant discharges. I will engage them to perform the required semi-
annual non -contact cooling water discharge testing as required by the permit and will set up the
required files at our facility to comply with the permit requirements. The next sampling will be
performed in approximately one month, and semi-annually thereafter.
Sincerely,
Richard W. Strachan
Technical Director
IMC-MetalsAmerica, LLC
cc: Steven Ryan, Plant Manager
r
Beverly Eaves Perdue
Governor
a
North Carolina Department of Environment and Natural Resources
Mr. Steve Ryan, Plant Manager
IMC Metals America
135 Old Boiling Springs Road
Shelby, North Carolina 28152
Dear Mr. Ryan:
Division of Water Quality
Coleen H. Sullins
Director
November 3, 2011
Subject: Notice of Violation
Compliance Evaluation Inspection
IMC Metals America
NPDES Permit No. NCG500221
Cleveland County, N.C.
Tracking #: NOV-201 1 -PC-05 85
Enclosed is a copy of the Compliance Evaluation Inspection Report for the inspection
conducted at the subject facility on November 1, 2011 by Mr. Wes Bell of this Office.
Dee Freeman
Secretary
This report is being issued as a Notice of Violation (NOV) due to the facility's failures to
monitor the effluent which are all violations of the subject NPDES Permit and North Carolina
General Statute (G.S.) 143-215.1, as detailed in the Effluent Sampling section of the attached
report. Pursuant to G.S. 143-215.6A, a civil penalty of not more than twenty-five thousand
dollars ($25,000.00) per violation, per day, may be assessed against any person who violates or
fails to act in accordance with the terms, conditions, or requirements of any permit issued
pursuant to G.S. 143-215.1.
It is requested that a written response be submitted to this Office by November 25, 2011,
addressing the above -noted violations in the attached report. In responding to the violations,
please address your comments to the attention of Mrs. Marcia Allocco. Please be advised that if
any chemicals are added to the cooling tower or boiler systems and were not included in the
renewal application, then a Biocides Worksheet — Form 101 must be completed (for each
chemical) along with the manufacturer's information on the additive. The completed form(s)
should be mailed to the following address: Division of Water Quality, Aquatic Toxicity Unit,
1621 Mail Service Center, Raleigh, NC, 27699-1621.
Mooresville Regional Office
Location: 610 East Center Ave., Suite 301 Mooresville, NC 28115
Phone: (704) 663-1699 l Fax: (704) 663-60401 Customer Service:1-877-623-6748
Internet: http:/Ipoilal.ncdem*.oig;tvebhvq
An Equal Opportunity', Affirmative Action Employer — 50% Racycledil O% Post Consumer paper
One
NorthCarollna
A7azza,1�`
r
Mr. Steve Ryan
November 3, 2011
Page Two
Should you have questions concerning this report, please do not hesitate to contact Mr.
Bell at (704) 663-1699.
Sincerely,
Robert B. Krebs
Surface Water Protection Regional Supervisor
Enclosure:
Inspection Report
Biocide Worksheet — Form 101
cc: Richard Strachan, IMC Metals America
Cleveland County Health Department
ON
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 INI 2 15I 31 NCG500221 111 121 11/11/0, 117 18I C I 19I S I 20I_I
Remarks
2111111111111111111111111111111111111111111111116
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA --------------------Reserved--------- -- ---
67 I 1.0 169 70I 1 I 711 N I 721 N I 73 W 74 751 I I I I III 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
10:00 AM 11/11/01
07/08/01
IMC-MetalsAmerica, LLC
Exit Time/Date
Permit Expiration Date
135 Old.Boiling Springs Rd
Shelby NC 28152
12:15 PM 11/11/01
12/07/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Richard W Strachan//704-471-650517044716513
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Steve Ryan,135 Old Boiling Springs Rd Shelby NC 28152/Plant Manager/704-471-6505/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Facility Site Review Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(*} Agency/Office/Phone and Fax Numbers Date
Z�
MRO WQ//704-663-1699 Ext.2192/
Wesley N Bell �,° `,' 1 �) { •-;
Signature of Management Q A Re sewer, a iZ Agency/Office/Phone and Fax Numbers + at
Marcia Allocco MRO WQ//704-663-1699 Ext.2204/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page # 1
NPDES
yr/mo/day
3I NCG500221 111 12I 11/11/0, I17
Inspection Type
18I CI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page # 2
Permit: NCG500221
Inspection Date: 11/01/2011
Owner - Facility: IMC-MetalsAmerica, LLC
Inspection Type: Compliance Evaluation
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment: The facility was reissued the subject permit on 7/30/2007 with an effective
date of 8/1/2007. The permit will expire on 7/31/2012.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Comment: No effluent monitoring has been performed during the entire permit cycle.
The permittee and staff should review the entire permit to ensure the facility complies
with all permit conditions including the record keeping requirements.
Yes No NA NE
Yes No NA NE
n
n
n
n
n
n
Page # 3
Permit: NCG500221 Owner - Facility: IMC-MetalsAmerica, LLC
Inspection Date: 11/01/2011 Inspection Type: Compliance Evaluation
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? ❑ ❑ ■ El
Are all other parameters(excluding field parameters) performed by a certified lab? n n ■ n
# Is the facility using a contract lab? n n ■ n
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? n n ■ n
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ n ■ n
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? n ❑ ■ ❑
Comment: If the facility staff perform any of the permit -required analyses on -site, then
the testing procedures must conform with Standard Methods for the Examination of
Wastewater, 18th - 20th Editions. All supporting documentation should also be
maintained on -site that includes: instrument calibrations, date of analyses,
collection/analysis times, sampling location, lab analyst, effluent results, etc.
Effluent Sampling
Yes
No
NA
NE
Is composite sampling flow proportional?
n
n
■
n
Is sample collected below all treatment units?
n
■
n
n
Is proper volume collected?
n
❑
■
n
Is the tubing clean?
n
n
■
n
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)?
n
n
■
n
Is the facility sampling performed as required by the permit (frequency, sampling type representative)? n ■ ❑ n
Comment: The semi-annual (twice per year) monitoring for flow and effluent pH,
temperature and total residual chlorine has not been performed during the entire permit
cycle.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? n n ■ n
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge n n ■ n
Judge, and other that are applicable?
Comment: The facility staff indicated that no biocides and/or corrosion inhibitors are
added to the cooling tower system.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter? -
Yes No NA NE
Page # 4
11
PF
Permit: NCG500221
Inspection Date: 11101/2011
Flow Measurement - Effluent
Owner -Facility: IMC-MetalsAmerica, LLC
Inspection Type: Compliance Evaluation
Comment: The permit requires semi-annual flow measurements (estimate). The
facility staff must ensure that the flow is measured and documented during each effluent
sampling event.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: The effluent appeared clear with no floatable solids or foam. The effluent
is discharged into the stormwater drainage system. The facility staff must ensure that
the effluent is sampled prior to the confluence with any other waters or substances,
such as stormwater or surface water.
Yes No NA NE
Yes No NA NE
Page # 5