HomeMy WebLinkAboutNC0072664_Regional Office Historical File Pre 2018 (76)WA .� Fg Meml F_ Emley. Governor
QG -William G. Ross Jr_, Secretary
North Carolina Department of Environment and Natural Reisouco
r Alan W. Klimek, P `, Director
D_U_ a
Division of Water Quality
October 14, 2002
Mr. Mark Hawes, Director of Environment and Safety
Shurtape Technologies, Inc.
Post Office Box .1530
:Hickory, North Carolina 28603-.1530
Subject: Notice of Deficiency
Compliance Evaluation Inspection
Shurtape Technologies, Inc. WWTP.
NPDES Permit No. NCO072664
Alexander County., N.C.
Dear Mr. Hawes:
Enclosed is a copy of the Compliance Evaluation Inspection Report for the inspection
conducted at the subject facility on October 4, 2002, by Mr. Wes Bell of this Office. Please inform
the facility's Operator -in -Responsible Charge of our findings by forwarding a copy, of the enclosed
report.
It is requested -that a written response be submitted to -this Office by November 4, 2002,
addressing the deficiencies_ noted in the Facility Site Review/Operations & Maintenance and Self -
Monitoring, Sections the report. In responding, please address your comments to the attention
:of Mr. Richard Bridgeman.
The.report should be.self-explanatory;_however, should.you'have:any questions concerning
this report, please_do n6t hesitate to contact Mr. Bell orme at.(704) 663-1699.
Sincerely.,
� L'�c.^ c� ire ��.i.,✓�'Y�--tic��i
1 D. Rex Gleason, P.E.
Water Quality. Regional Supervisor
Enclosure
cc: Alexander County Health Department
WB
=A
NMEM
N. C. Division of Water Quality 919 North Main Street, Mooresvilie NC 28115 Phone_ (704) 653-1699
FAX (7G4) 663-6040
C
US Environmental Protection Agency, Washington, D.C., 20460 LV-KWA Form Approved.
OMB No.2040-0057
Water Compliance Inspection Report Alp"A
Approval Expires 8-31-98
NC Division of Water Quality. Mooresville Regional Office NCDENR
Transaction Code NPDES No. Yr/Mo/Day Inspection Type Inspector Facility Type
N 5 NCO072664 02/10/04 C S 2
- Remarks:
Inspection Work Days Facility Evaluation. Rating BI QA ..........Reserved...........
1.5 3 N N
�s
ii) fiM:, zc�lit" 'F � yr-p
-Name and Location of Facility:lnspected: Entry Time: Permit Effective Date:
Shurtape Technologies, Inc./Stony r Point WWTP 9:40 am 00/02/01
NC Highway 90
Stony Point Exit Time/Date: Permit Expiration Date:
Alexander County, North Carolina 1:34 pm 04/07/31
02/10/04
Name(s) of On -Site Representative(s)/Title(s)/Phone No(s)/Fax No(s):
Mr. Travis Brannon/ORC/704-585-6511
Mr. Mark Hawes/Director of Environment and Safety/828-322-2700 Ext. 4428
.Name and Address of Responsible Official: Title: Director of Environment and Safety
Mr. Mark Hawes
Shurtape Technologies, Inc.
Post Office Box-1530 Phone No: Contacted?
Hickory, North Carolina 28603-1530 828-322-2700 Yes
:Section�C.Arent'.,Bv.aluaied.-Duiilig Insp ectiolit(Cheek. n Ah6se;areas.- alusitid)-. -
X Permit X Flow Measurement X Operations & Maintenance X Sewer Overflow
X Records/Reports X Self -Monitoring Program X Sludge Handling/Disposal Pollution Prevention
X Facility Site Review Compliance Schedules Pretreatment Multimedia
_X -Effluent/ReceivingVaters X Laboratory Storm Water Other:
C-o"
-.7-_ 4VAiiJiling i innients: 6
Sicti6ii3biSuinmaii
See AttachedSheet(s) for .Summary.
Name(s) and Signature(s) of Inspectors: Agency/Office/Telephone No: Date:
Wes Bell NCDWQ/MOORESVILLE/(704)663-1699 10/11/02
Date:
Signature of Management QA Reviewer: Agency/Office/Phone & Fax No: Date:
EPA Form 3560-3 (Rev. 9-94) Previous editions are obsolete
Shurtape Technologies, Inc. W VTP
Page Two
The facility was"last inspected by Roberto Scheller.ofthis Office on July 19, 2000.
PERMIT:
The permit authorizes the continued operation of . an existing 0.010 MGD wastewater
treatment system consisting of a flow meter, aeration tank, clarifier, sludge holding tank, and
chlorination unit. It was observed that a flow.meter does not exist -and the facility has a bar screen
and chlorine contact chamber; therefore, .the permit does not. adequately describe the wastewater
treatment facility.
The permit for this facility became effective 2/.1/00 and expires on 7/31/04.
RECORDS AND REPORTS:
Records and reports consisting of discharge monitoring reports, chain of custody forms,
laboratory analyses, Operator -in -Responsible Charge (ORC)/maintenance log, daily operation log,
process control data, calibration log, and sludge records were reviewed during the inspection. The
.records were organized and well kept.
FACILITY SITE REVIEW/OPERATIONS & MAINTENANCE:
All treatment units appeared to be operating properly and the surrounding grounds were well
maintained. The, mixed. liquor appeared to be well mixed and .adequately oxygenated. A thirty -
minute settleability test was performed on the aeration basin. The mixed liquor adequately settled
(530 ml/L) with a clear supernate and trace pin floc. Bar .screenings aredisposed at the county
landfill. Both blowers were operational; however, a belt on one of the blowers appeared to need
replacement (in the near future). The process control program consists of dissolved oxygen (DO),
settleability tests, MLSS, and "MLVSS measurements. Sludge wasting is based on the MLSS
measurements.
The chlorine contact chamber contained a thick accumulation of solids on top of the water's
surface; however, the accumulation of solids were -not entering the effluent (via baffle). In addition,
approximately.2 - 21/z feet of solids were measured (via sludge judge) at the"bottom of the -contact
chamber. The settled solids (in the contact chamber) should be.maintained at -less than one foot and
visual observations should be made in the contact chamber to insure an accumulation of solids does
not exist. The Permit requires that the facility be properly operated and maintained at all times. The
ORC and staff indicated that a septage hauler would be contacted for the removal of the solids.
The facility currently utilizes BioGuard chlorine tablets. The container did not specify
approval for wastewater usage. The Director of Environment and Safety contacted the manufacturer
and determined that these tablets were not approved for wastewater usage. Please be advised that
only wastewater approved chlorine tablets shall be used for disinfection. In addition, the tablet
chlorinator was not being utilized for disinfection. The chlorine tablets were being positioned in the
clarifier effluent weir. The chlorine tablets shall be placed in the approved disinfection unit
(chlorinator) and removed from the clarifier weir as to prevent the leaching of metals into the
effluent stream.
Shurtape Technologies, Inc. WWTP
Page Three
FACILITY'SITE REVIEW/OPERATIONS & MAINTENANCE cont'd:
The facility is staffed .with one Grade II ORC. A certified back-up operator has been
designated and is available when the ORC is unable to visit the facility. The ORC and staff were
very knowledgeable of the treatment processes and equipment used at the facility.
LABORATORY:
Water Tech Labs, Inc. (Certification #50) in Granite Falls, MC..has been contracted -to
provide analytical support. The laboratory was not evaluated during this inspection. The facility has
applied for and received a laboratory certification (#5087) by the Division's Laboratory Certification
Unit to perform on -site field analyses.
The pH, TRC,;and DO meters and thermometer appeared to be properly calibrated. The ORC
and staff must insure that 0 -calibration times are documented to verify that the meters are calibrated
prior to analysis. In addition, the temperature correction factor for the temperature measuring device
on -the pH meter (utilized to measure/report effluent temperature) was not incorporated. The ORC
made the necessary corrective actions at the time of the inspection.
EFFLUENT/RECEIVING WATERS:
The effluent discharge was clear with no floatable solids or foam. The facility discharges
into Third Creek, which is a Class C water in the Yadkin -Pee Dee River Basin. The receiving stream
did not appear to be negatively impacted. The outfall was accessible and well maintained.
A review of the DMRs have indicated numerous TRC values in excess of 28,ug/l. Be aware
that a stream action .level of 17 /.cg/l .has been established for total residual chlorine for chronic
toxicity effects. An -action level of 28 gg/1 has been set as the maximum allowable effluent
concentration to protect the receiving stream against acute toxicity effects. Please maintain -the total
residual chlorine concentration as low as possible, while still complying with fecal coliform limits.
SELF -MONITORING :PROGRAM:
Self -monitoring reports were reviewed for the period July 2001 through June 2002, inclusive.
No limit violations were reported. Only one TRC value was reported for the week of December 23
through December 29, 2001; however, the inspection verified that a second TRC value was analyzed
on December 26, 2001. Due to the inspection verifying a second TRC value was performed for the
noted week, all monitoring frequencies were correct. Note: Please resubmit an amended December
2001 DMR to the Division.
The same upstream and downstream times were reported on the July and August 2001
DMRs; however, the ORC and staff began documenting separate times during the remainder of the
review period.
On numerous occasions, TRC and pH analyses were performed on the effluent as process
control. Please be advised that all analyses performed on the effluent must be collected/analyzed and
reported according to the requirements of the NPDES Permit.
Shurtape Technologies, Inc. WWTP
Page Four
SELF -MONITORING P.ROGRAM:cont'd:
All samples appeared to. be properly preserved and meet the required holding times. The
downstream sampling location appeared to be consistent with the permit requirements; however, the
upstream sampling location was approximately .5 - 10 feet above the discharge outfall. Please be
advised that the Permit requires that the .upstream sampling location be at least 100 feet upstream
of the discharge outfall.
FLOW:MEASUREMENT:
Instantaneous flow is currently being measured by the bucket and stop watch method.
SLUDGE DISPOSAL:
Sludge is removed'by Lentz Septic Tank�Services of Statesville, N.C. and disposed at the
Mooresville WWTP.
SEWER OVERFLOW:
Please be, advised that pursuant to Part II, Section E of your NPDES permit, and North
Carolina Administrative Code (NCAC) .15A 2B .0506 (a)(2), any failure of a collection system,
pumping station or treatment facility resulting in a bypass without treatment of all or any portion of
the wastewater shall be reported to the central office or the appropriate regional office (Mooresville
Regional Office 704-663-1699) as soon as possible but no later than 24 hours from the time the
permittee became aware of the bypass. Overflows and spills occurring outside normal business hours
may also be reported to the Division's Emergency Response personnel at 800-662-7956, 800-858-
0368, or 919-733-3300. A written report shall also be provided within five (5) days of the time of
the incident. The report shall contain a description of the bypass, and its cause; the period of the
bypass, including exact dates and times, and if the bypass has.not been corrected; the anticipated time
'it is expected to continue; and steps taken (or planned) to reduce, eliminate, and prevent recurrence
of the -similar events. Any spill that reaches surface waters. (i.e. any spill .that reaches .any water
already present in a conveyance, stream, ditch, etc...) -or any spill greater than .1;000 gallons on the
ground that does not reach surface .waters must be reported.
An adequate `spill response for those spills reaching surface waters should include- an
evaluation downstream of the point at which the spill entered surface waters to determine if a fish
kill occurred. The evaluation should also include the collection of upstream dissolved oxygen and
pH measurements for background information and dissolved oxygen and pH measurements at
multiple points downstream of the entry point to document any negative impact. Failure to report
the bypass of collection system, pumping station or treatment facility subjects violators to penalties
of up to $25,000.00 per day per violation.