HomeMy WebLinkAboutWQ0020248_Monitoring - 07-2020_20200827NON DISCHARGE WASTEWATER MONITORING REPORT
Page: 1 of 3
PERMIT NUMBER: WQ0020248 MONTH: July YEAR: 2020
FACILITY NAME: Big Buffalo Creek WWTP CLASS: IV COUNTY: LEE
D
a
t
e
Operator
Arrival Time
1 2400 Time
Operator
Time On Site
ORC on
Site?
50050
00400 1 50060 1 80082 1 00610 1 00530 31616
Daily Rate
(Flow) into
Treatment
System
Sampled
at the point prior to irrigation
pH
Residual
Chlorine
CBOD-5
20°C
NH3-N
TSS
Fecal
Coliform
(Geometric
Mean)
HRS
Y/N
MGD
UNITS
UG/L
MG/L
MG/L
MG/L
mpn/100ML
1
24
24
Y
0.2043778
6.6
3950
< 2.0
< 1.0
< 2.5
< 1
2
24
24
Y
0.0000000
3
24
24
N
0.0000000
4
24
24
N
0.0000000
5
24
24
N
0.0000000
6
24
24
Y
0.0000000
7
24
24
Y
0.0000000
8
24
24
Y
0.0000000
9
24
24
Y
0.0000000
10
24
24
N
0.0000000
11
24
24
N
0.0000000
12
24
24
N
0.0000000
13
24
24
Y
0.0000000
14
24
24
Y
0.0000000
15
24
24
Y
0.1774105
6.5
3500
3.4
< 1.0
< 2.5
< 1
16
24
24
Y
0.0000000
17
24
24
Y
0.1253113
6.4
2600
2.1
< 1.0
< 2.5
< 1
18
24
24
N
0.0000000
19
24
24
N
0.0000000
20
24
24
Y
0.0000000
21
24
24
Y
0.0000000
22
24
24
Y
0.0000000
23
24
24
Y
0.0000000
24
24
24
Y
0.1802681
6.5
2400
2.2
< 1.0
< 2.5
< 1
25
24
24
N
0.0000000
26
24
24
N
0.0000000
27
24
24
Y
0.0000000
28
24
24
Y
0.1911307
6.4
3600
< 2.0
< 1.0
< 2.5
< 1
29
24
24
Y
0.0000000
30
24
24
Y
0.0000000
31
1 24
24
Y
0.0000000
Average
0.02834
3210
1.5
0
0
0
Maximum
0.20438
6.6
3950
3.4
< 1.0
< 2.5
< 1
Minimum
0.00000
6.4
2400
< 2.0
< 1.0
< 2.5
< 1
Monthly Limit
6--9
----
10 m /L
4 m /L
5 m /L
14 er/100
Composite (C) / Grab (G)
G
G
C
C
C
G
OPERATOR IN RESPONSIBLE CHARGE (ORC) Scott A. Siletzky GRADE IV PHONE (919) 775-8305
CHECK BOX IF ORC HAS CHANGED ❑
CERTIFIED LABORATORIES 1 Environmental 1, Incorporated 2
PERSON(S) COLLECTING SAMPLES Dale Deaton/ Joseph Lynch
and
Information Processing Unit
1617 Mail Service Center
Raleigh, NC 27699-1617
114
: 4
X
(SIGNATURE OF OPERA -OR IN R N BLE CHARGE)
BY THIS SIGNATURE, I CERTIFY THAT T REPORT IS ACCURATE
AND COMPLETE TO THE BEST OF MY KNOWLEDGE.
t�
c =,
_ �a
FACILITY STATUS:
Page: 2 of 3
Please check one of the following:
1. All monitoring data and sampling frequencies meet permit requirements. Compliant
1. All monitoring data and sampling frequencies do NOT meet permit requirements. ❑ Non -Compliant
If the facility is non -compliant, please explain in the space below the reason(s) the facility was not in compliance
with its permit. Provide in your explanation the date(s) of the noncompliance and describe the corrective action(s)
taken. Attach additional sheets if necessary.
The Setpoint is programmed to shut off before the Turbidity exceeds 10 NTUs during run times.
I certify, under penalty of law, that this document and all attachments were prepared under my direction or
supervision in accordance with a system designed to assure that qualified personnel properly gathered and evaluated
the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons
directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief,
true, accurate, and complete. I am aware that there are significant penalties for submitting false information,
including the possibility of fines and imprisonment for knowing violations."
Victor Czar
( ittee - lease print or type)
(Signature of Permi ) (Date)
5327 Iron Furnace Road, Sanford, NC 27330 (919) 775-8305 30-Sept -2020
(Permittee Address) (Phone Number) (Permit Exp. Date)
PARAMETER CODES
01002
Arsenic
31504
Coliform,
01067
Nickel
00929
Sodium
Total
01022
Boron
00094
Conductivity
00600
Nitrogen,
00931
SAR
Total
00310
BOD5
01042
Copper
00630
NO2&NO3
00745
Sulfide
01027
Cadmium
00300
Dissolved
00620
NO3
00515
TDS
Oxygen
00916
Calcium
31616
00556
Oil -Grease
00010
Temperature
CFecal
00940
Chloride
01051
Lead
00400
pH
00625
TKN
Chlorine,
50060
Total
00927
Magnesium
32730
Phenols
00680
TOC
Residual
01034
Chromium
71900
Mercury
00665
Phosphorus
00530
TSS
Total
00340
COD
00610
NH3 as N
00937
Potassium
01092
Zinc
Parameter Code assistance may be obtained by calling the Water Quality Compliance Group at (919)773-5083, ext. 536
The monthly average for Fecal Coliform is to be reported as a GEOMETRIC mean. Use only units designated in the reporting facility's permit for
reporting data.
— If signed by other than the permittee, delegation of signatory authority must be on file with the state per 15A NCAC 2B.0506 (b)(2)(D).
NON DISCHARGE WASTEWATER MONITORING REPORT
PERMIT NUMBER: W00020248
FACILITY NAME: Big Buffalo Creek WWTP
Page: 3 of 3
MONTH: July YEAR: 2020
CLASS: IV COUNTY: LEE
..
-0�0000--
' Daily Maximum