HomeMy WebLinkAboutWQ0003902_BIMS Report_20200325Compliance Inspection Report
Permit: WQ0003902 Effective: 06/01/15 Expiration: 05/31/20 Owner: City of Newton
SOC: Effective: Expiration: Facility: City of Newton Residuals Land Application Pro(
County: Catawba PO Box 550
Region: Mooresville
Newton NC 28658
Contact Person: James Dusty Wentz Title: Phone: 828-695-4286
Directions to Facility:
System Classifications: LA,
Primary ORC: James Eric Jones
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Inspection Date: 03/19/2020 Entry Time 08:40AM
Primary Inspector: Edward Watson
Secondary Inspector(s):
Certification: 25000 Phone:828-695-4370
Exit Time: 04:OOPM
Phone:
Reason for Inspection: Routine Inspection Type: Annual Report Review
Permit Inspection Type: Land Application of Residual Solids (503)
Facility Status: Compliant ❑ Not Compliant
Question Areas:
Miscellaneous Questions Record Keeping Sampling
Pathogen and Vector Attraction
(See attachment summary)
Page 1 of 4
Permit: WQ0003902 Owner - Facility: City of Newton
Inspection Date: 03/19/2020 Inspection Type: Annual Report Review Reason for Visit: Routine
Inspection Summary:
This permit will expire on May 31, 2020. The Renewal Application was submitted to DWR and a renewed permit is pending
action in the central office.
During 2019, a total of 1,264.18 dry tons of class "B" residuals were applied over 310.8 acres
Both SAR calculations are consistantly presented for all four quarters. A spot check of the calculations indicate both PAN
and SAR are within permit limits.
Page 2 of 4
Permit: WQ0003902 Owner - Facility: City of Newton
Inspection Date: 03/19/2020 Inspection Type: Annual Report Review Reason for Visit: Routine
Type Yes No NA NE
Distribution and Marketing ❑
Land Application
Record Keeping
Yes No NA NE
Is GW monitoring being conducted, if required?
❑
❑ 0 ❑
Are GW samples from all MWs sampled for all required parameters?
❑
❑ 0 ❑
Are there any GW quality violations?
❑
❑ 0 ❑
Is GW-59A certification form completed for facility?
❑
❑ 0 ❑
Is a copy of current permit on -site?
0
❑ ❑ ❑
Are current metals and nutrient analysis available?
0
❑ ❑ ❑
Are nutrient and metal loading calculating most limiting parameters?
❑
0 ❑ ❑
a. TCLP analysis?
0
❑ ❑ ❑
b. SSFA (Standard Soil Fertility Analysis)?
0
❑ ❑ ❑
Are PAN balances being maintained?
0
❑ ❑ ❑
Are PAN balances within permit limits?
0
❑ ❑ ❑
Has land application equipment been calibrated?
❑
❑ ❑
Are there pH records for alkaline stabilization?
0
❑ ❑ ❑
Are there pH records for the land application site?
0
❑ ❑ ❑
Are nutrient/crop removal practices in place?
0
❑ ❑ ❑
Do lab sheets support data reported on Residual Analysis Summary?
0
❑ ❑ ❑
Are hauling records available?
❑
0 ❑ ❑
Are hauling records maintained and up-to-date?
❑
❑ ❑
# Has permittee been free of public complaints in last 12 months?
0
❑ ❑ ❑
Has application occurred during Seasonal Restriction window?
❑
0 ❑ ❑
Comment: This is an AR review. A Compliance Inspection for
permit renewal was performed on January
2,
2020. An LA event did not occur during the January
2020 site visit.
The AR report indicates that field CA-15-10 required 1.7 tons of lime to raise the pH from 4.9 to
the minimum reauirement of 6.0.
Hauling records for 2019 were requested by email. Please remember to include truck hauling
records in future ARs.
Pathogen and Vector Attraction Yes No NA NE
a. Fecal coliform SM 9221 E (Class A or B) ❑ ❑ ❑
Class A, all test must be <1000 MPN/dry gram ❑
Geometric mean of 7 samples per monitoring period for class B<2.0*10E6 CFU/dry gram ❑
Fecal coliform SM 9222 D (Class B only) ❑ ❑ ❑
Page 3 of 4
Permit: WQ0003902 Owner - Facility: City of Newton
Inspection Date: 03/19/2020 Inspection Type: Annual Report Review Reason for Visit: Routine
Geometric mean of 7 samples per monitoring period for class B<2.0*10E6 CFU/dry gram
b. pH records for alkaline stabilization (Class A)
❑
❑ ❑
c. pH records for alkaline stabilization (Class B)
0
❑ ❑ ❑
Temperature corrected
❑
d. Salmonella (Class A, all test must be < 3MPN/4 gram day)
❑
❑ 0❑
e. Time/Temp on:
❑ ❑ ❑
Digester (MCRT)
Compost
❑
Class A lime stabilization
❑
f. Volatile Solids Calculations
❑
❑ 0 ❑
g. Bench -top Aerobic/Anaerobic digestion results
❑
❑ 0 ❑
Comment: PVAR is achieved by Alkine Stabilization. The Time on Temperature records
presented in the AF
appear to be complete and accurate.
Sampling Yes No NA NE
Describe sampling:
Sampling is 7 grab samples for Fecal Coliform using SM 9222D 2 x 10 to the 6th power MPN to prove
adequate reduction has been achieved. Based on the Alkaline Stabilization tables, reduction is being
achieved.
Is sampling adequate? ❑ ❑ ❑
Is sampling representative? 0 ❑ ❑ ❑
Comment: The seven grab samples from different areas is used to obtain representative sampling.
Page 4 of 4